| Date: 12/17/2007 | Time: | Report ID: Sam 2 |
| Property: 310 Windy Hills Drive Columbus, SC |
Customer: Cameron Milton |
Real Estate Professional: |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
In Attendance: Customer and their agent | Age Of Home: Over 50 Years | Weather: Clear |
Temperature: Over 60 | Ground/Soil surface condition: Dry | Rain in last 3 days: No |
Radon Test: No | Water Test: No |
| IN | NI | NP | RR | Inspection Items | ||||
| X | 1.0 | ROOF COVERINGS Roof Covering: 3-Tab fiberglass Viewed roof covering from: Ground Comments: (1)
The roof covering is old, and the life of covering has expired. The
covering does need to be replaced. While it could last a year or so, some
areas may need patching with tar as leaks develop. Some shingles are
missing on main roof and daylight can be seen from attic. Immediate
repairs are needed here.
(2)
The tree limbs that are in contact with roof or hanging near roof should be
trimmed.
|
||||||
| X | 1.1 | FLASHINGS Comments: |
||||||
| X | 1.2 | SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS Sky Light(s): None Chimney (exterior): Brick Comments: |
||||||
| X | 1.3 | ROOF DRAINAGE SYSTEMS Comments: (1)
The gutter is loose or daylight between gutters and fascia at the rear.
Loose or leaking gutters can cause deterioration of fascia, soffit or roof
edge. It can also cause gutters to pull loose and lead to possible water
intrusion. A qualified contractor should inspect and repair as needed.
(2)
The gutter screens collapsed inside gutter at the front of home.
A qualified person should repair or replace as needed. The
gutter needs cleaning of debris at the front and as needed
elsewhere. Gutters that drain poorly or clogged can lead to
many costly problems such as deterioration of fascia, soffit or
roof edge. It can also cause gutters to pull loose and lead to
possible water intrusion. A qualified person should repair or
replace as needed.
|
||||||
| IN | NI | NP | RR | Inspection Items |
| IN | NI | NP | RR | Inspection Items | ||||
| X | 2.0 | WALL CLADDING FLASHING AND TRIM Siding Style: Brick Siding Material: Wood, Full brick Comments: |
||||||
| X | 2.1 | DOORS (Exterior) Exterior Entry Doors: Wood Comments:
The side entry door to basement reveals daylight when latched at areas
missing weather-stripping. This is a small repair. A qualified person
should repair or replace as needed.
|
||||||
| X | 2.2 | WINDOWS Comments:
The sill plate is deteriorated at right side (facing front). This is a small
repair. A qualified person should repair or replace as needed.
|
||||||
| X | 2.3 | DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS Appurtenance: Covered porch, Porch, Sidewalk Comments: (1)
The support column(s) on covered porch at the left side (facing front) are
split or cracked in areas and are deteriorated in areas. A repair or
replacement is needed. A qualified contractor should perform the work.
(2)
The steps on the porch at the rear of home are not uniform
in"riser height" and are a tripping hazard. A fall or injury could
occur if not corrected. I recommend repair as needed.
(3)
Some of the rafters of covered porch shows weakening by
previous damage from leaks or other. Appears to remain strong
to function. FYI
|
||||||
| X | 2.4 | VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) Driveway: Asphalt Comments: |
||||||
| X | 2.5 | EAVES, SOFFITS AND FASCIAS Comments: (1)
The eave boards at eave on the gables and various roof edges are
deteriorated. Repairs are needed. A qualified contractor should inspect
and repair as needed.
(2)
The soffit panel at eave on the front (right of main entry) are
weathered and peeling paint. Further deterioration may occur
if not repaired. A qualified person should repair or as needed.
I am unable to determine if leak exists here or was a result of
clogged gutters.
|
||||||
| IN | NI | NP | RR | Inspection Items |
![]() | ![]() |
![]() |
| IN | NI | NP | RR | Inspection Items | |||
| X | 3.0 | CEILINGS Ceiling Materials: Plaster, Suspended ceiling panels, Ceiling Tile, Painted-over wallpaper Comments: (1)
Plaster ceiling is in need of repair in bathroom. Currently it is covered by
drop panels.
(2)
The Ceiling Tile on the ceiling reveals a water stain indicating a
leak did or still exists at the Bedroom. Due to recent dry
weather, I am unable to determine if the leak still exists. A
qualified contractor should inspect and repair as needed.
|
|||||
| X | 3.1 | WALLS Wall Material: Drywall, Plaster Comments: |
|||||
| X | 3.2 | FLOORS Floor Covering(s): Hardwood T&G, Tile, Vinyl Comments: |
|||||
| X | 3.3 | STEPS, STAIRWAYS, BALCONIES AND RAILINGS Comments:
The hand/guard rail for the stairs to basement are missing balusters (on
both sides). A fall or injury could occur if not corrected. A qualified
contractor should repair or replace as needed.
|
|||||
| X | 3.4 | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS Cabinetry: Wood, Veneer Countertop: Laminate Comments:
Sink base is damaged under sink at bottom shelf likely from
leaking faucet. Recommend repair or replace sink base cabinetry
as necessary.
|
|||||
| X | 3.5 | DOORS (REPRESENTATIVE NUMBER) Interior Doors: Wood Comments:
The Entry door and Closet door rubs at jamb when closing at the
Living Room and hallway closet and Small bedroom. The
Living room second door to porch is painted shut or will not
open. A qualified person should repair or replace as needed. |
|||||
| X | 3.6 | WINDOWS (REPRESENTATIVE NUMBER) Window Types: Double-hung, Single pane, Storm windows Comments:
There are cracked and broken glass at numerous windows
throughout home. At least five windows missing sash cords at
the Living Room, pantry and Small bedroom (left of hall bath)
and at top of stairs. A qualified person should repair or replace
as needed. |
|||||
| IN | NI | NP | RR | Inspection Items |
| IN | NI | NP | RR | Inspection Items | |||
| X | 4.0 | FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) Foundation: Brick Method used to observe Crawlspace: No crawlspace Comments: (1)
Brick Foundation wall at the basement entry has missing mortar around
windows . Repairs are needed. A skilled masonry contractor should
perform the repairs.
(2)
The brick foundation has been coated with a water proof sealer
except behind shelving. If water intrusion occurs here, then
shelving may need removing in order to coat area properly.
|
|||||
| X | 4.1 | WALLS (Structural) Wall Structure: Wood, Brick Comments: |
|||||
| X | 4.2 | COLUMNS OR PIERS Columns or Piers: Masonry block, Supporting walls Comments: |
|||||
| X | 4.3 | FLOORS (Structural) Floor Structure: 2 X 8, 2 X 10, Wood joists Comments: |
|||||
| X | 4.4 | CEILINGS (structural) Ceiling Structure: 2X4 Comments: |
|||||
| X | 4.5 | ROOF STRUCTURE AND ATTIC Roof Structure: Stick-built, 2 X 6 Rafters, Common board Roof-Type: Gable Method used to observe attic: Walked Attic info: Attic access Comments:
The common board roofing indicates roof leaks or has leaked
around the chimneys. Leaking roofs should be repaired to
prevent damage. I recommend a qualified contractor perform
the work. (See Roof Coverings comments)
|
|||||
| IN | NI | NP | RR | Inspection Items |
| IN | NI | NP | RR | Inspection Items | |||||
| X | 5.0 | PLUMBING DRAIN, WASTE AND VENT SYSTEMS Washer Drain Size: 2" Diameter Plumbing Waste: PVC, Cast iron, lead waste (old) Comments: (1)
Upon arriving water was on and spilling onto floor of basement from
nearby faucet and water heater. The hvac person who was their at the time
of inspection claimed that he turned the water on at the street. I turned off
the valve at faucet and water heater. FYI
(2)
The stop-valve does not work properly at the Hall Bath sink. Repairs are
needed. The tub drain drains slowly at main bath. There is a leak under
bathtub that can be seen from removing access panel on wall. Repairs are
needed. A qualified licensed plumber should repair or correct as needed.
(3)
The basket strainer is leaking at left side and at right side at the Kitchen
sink. Repairs are needed. A qualified licensed plumber should repair or
correct as needed.
(4)
The floor drain has a plug as if to keep something from coming in? After
the inspection, the owner of the adjacent property volunteered
information that the city sewer occasionally will back up and come into
basement. This may be the reason for the plug? I am unable to determine if
plug will prevent this from occurring. FYI
|
|||||||
| X | 5.1 | PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES Water Source: Public Water Filters: None Plumbing Water Supply (into home): Galvanized (old) Plumbing Water Distribution (inside home): Galvanized, Copper Comments: (1)
The lever on faucet leaks at the kitchen sink. Repairs are needed to
stop leaking water from further damaging the cabinet bottom or to
eliminate moisture that may contribute to fungi growth. I recommend
repair as necessary by a qualified person. The spray nozzle is not
working properly which could be as a result of no volume or pressure
at the kitchen sink. Repairs are needed. A qualified licensed plumber
should repair or correct as needed. (2)
The water pressure over-all is poor and would not pass "functional
flow." A possible reason for weak volume or pressure could be old
galvanized piping that is corroded inside. NOTE: NO SHOWER FOR
BATH
Toilet will not fill with water likely due to clogged piping. I could not inspect the toilet fixture for leaks.
|
|||||||
| X | 5.2 | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS Water Heater Power Source: Electric Water Heater Capacity: 40 Gallon (1-2 people) Manufacturer: A.O. SMITH Comments:
Water heater was empty and drain open at bottom when I arrived. I closed
drain but at the end of inspection, drips were still occurring. Repairs may
be needed.
|
|||||||
| X | 5.3 | MAIN WATER SHUT-OFF DEVICE (Describe location) Comments:
The main shut off is the red knob located in the basement on the front
wall. This is for your information.
|
|||||||
| X | 5.4 | FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) Comments: |
|||||||
| X | 5.5 | MAIN FUEL SHUT OFF (Describe Location) Comments: The main fuel shut off is at gas meter outside |
|||||||
| X | 5.6 | SUMP PUMP Comments: |
|||||||
| IN | NI | NP | RR | Inspection Items |
| IN | NI | NP | RR | Inspection Items | |||||
| X | 6.0 | SERVICE ENTRANCE CONDUCTORS Electrical Service Conductors: Overhead service, Aluminum, 220 volts Comments: |
|||||||
| X | 6.1 | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS Panel capacity: 100 AMP Panel Type: Fuses, Circuit breakers Comments: |
|||||||
| X | 6.2 | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE Branch wire 15 and 20 AMP: Copper Wiring Methods: Romex, Knob and Tube Comments:
Problem(s) discovered with Branch Circuits such as doubled wiring at
fuse(s), doubled wiring at circuit(s), and edison base fuse(s) under stairs,
and any other problems that an electrician may discover while performing
repairs need correcting. I recommend a licensed electrician inspect further
and correct as needed.
|
|||||||
| X | 6.3 | CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) Comments: (1)
"Two-prong" outlets are missing cover-plates in the dining room and in
the living room. This is a safety issue that needs to be corrected. I
recommend repair as needed.
(2)
Loose light fixture needs securing in closet. Loose or unfinished wiring in
attic should be corrected to remain safe ( Picture 2 ) .One splice box needs
a cover-plate in the basement. I recommend repair as needed ( Picture 4 ) .
|
|||||||
| X | 6.4 | POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE Comments: |
|||||||
| X | 6.5 | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) Comments: |
|||||||
| X | 6.6 | LOCATION OF MAIN AND DISTRIBUTION PANELS Comments: The main panel box is located at the basement. |
|||||||
| X | 6.7 | SMOKE DETECTORS Comments: |
|||||||
| X | 6.8 | CARBON MONOXIDE DETECTORS Comments: |
|||||||
| IN | NI | NP | RR | Inspection Items |
| IN | NI | NP | RR | Inspection Items | |||
| X | 7.0 | HEATING EQUIPMENT Heat Type: Circulating boiler Energy Source: Gas Number of Heat Systems (excluding wood): One Comments:
The gas-fired boiler did not function or is non-operational. A repair or replacement is needed. I recommend further inspection by a licensed
HVAC contractor.
|
|||||
| X | 7.1 | NORMAL OPERATING CONTROLS Comments: |
|||||
| X | 7.2 | AUTOMATIC SAFETY CONTROLS Comments: |
|||||
| X | 7.3 | DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) Comments:
Due to the concern for water volume or pressure and because of
the old piping that was turned off for an extended period of time,
and the fact that the boiler is non-operational, I am concerned of
whether or not the radiators will function properly when boiler is
repaired. A clogged or failed radiator can be expensive to
replace. I strongly recommend that an HVAC person inspect all
the radiators when boiler becomes operable. You should
obtain a letter from the HVAC company as to the condition of
radiators, piping and boiler before you close on home. |
|||||
| X | 7.4 | PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM Comments:
There is no heat source for Bedroom on right (at top of stairs).
|
|||||
| X | 7.5 | CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat systems) Comments:
The liner for fireplace was partially visible and appears good
except for creosote dust that may conceal a hairline crack until
cleaned and inspected by a licensed chimney sweep. I did not
inspect the liner for gas fired boiler. For a detailed inspection
of liner, I recommend a qualified chimney sweep inspect for
safety. |
|||||
| X | 7.6 | SOLID FUEL HEATING DEVICES (Fireplaces, Woodstove) Types of Fireplaces: Conventional Operable Fireplaces: One Number of Woodstoves: None Comments: |
|||||
| X | 7.7 | GAS/LP FIRELOGS AND FIREPLACES Comments: |
|||||
| X | 7.8 | COOLING AND AIR HANDLER EQUIPMENT Number of AC Only Units: None Comments: There is no central air conditioning in this home. This home has no
central air (No AC). This is for your information. |
|||||
| X | 7.9 | NORMAL OPERATING CONTROLS Comments: |
|||||
| X | 7.10 | PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM Comments: |
|||||
| IN | NI | NP | RR | Inspection Items |
| IN | NI | NP | RR | Inspection Items | |
| X | 8.0 | INSULATION IN ATTIC Attic Insulation: Blown, Fiberglass, R-19 or better Comments:
The attic has a small amount of insulation and "Knob and Tube" wiring is
present. As a safety rule Knob and Tube wiring should never have
insulation covering this wire or over heating can occur. If new insulation
is added, an electrician should first replace knob and tubing wires with
updated wiring. |
|||
| X | 8.1 | INSULATION UNDER FLOOR SYSTEM Floor System Insulation: NONE Comments: |
|||
| X | 8.2 | VAPOR RETARDERS (ON GROUND IN CRAWLSPACE OR BASEMENT) Comments: |
|||
| X | 8.3 | VENTILATION OF ATTIC AND FOUNDATION AREAS Ventilation: Gable vents, Passive Comments: |
|||
| X | 8.4 | VENTING SYSTEMS (Kitchens, baths and laundry) Exhaust Fans: None Dryer Power Source: 220 Electric Dryer Vent: Flexible Vinyl Comments: |
|||
| X | 8.5 | VENTILATION FANS AND THERMOSTATIC CONTROLS (ATTIC) Comments: |
|||
| IN | NI | NP | RR | Inspection Items |
| IN | NI | NP | RR | Inspection Items | |
| X | 9.0 | DISHWASHER Dishwasher Brand: KENMORE Comments: |
|||
| X | 9.1 | RANGES/OVENS/COOKTOPS Range/Oven: NONE Comments: |
|||
| X | 9.2 | RANGE HOOD Exhaust/Range hood: NONE Comments: |
|||
| X | 9.3 | TRASH COMPACTOR Comments: |
|||
| X | 9.4 | FOOD WASTE DISPOSER Disposer Brand: IN SINK ERATOR Comments: |
|||
| X | 9.5 | MICROWAVE COOKING EQUIPMENT Built in Microwave: NONE Comments: |
|||
| IN | NI | NP | RR | Inspection Items |

18 Business Park Circle
Arden, NC 28704
877-274-4299
Customer
Cameron Milton
Address
310 Windy Hills Drive
Columbus, SC
1. Roofing |
||||||||||||||||
|
2. Exterior |
||||||||||||||||||||||||||||||
|
3. Interiors |
||||||||||||||||||||||||||||||||
|
4. Structural Components |
||||||||||||||
|
5. Plumbing System |
||||||||||||||||||||||||||
|
6. Electrical System |
||||||||||||||
|
7. Heating / Central Air Conditioning |
||||||||||||||||||||||||
|
8. Insulation and Ventilation |
||||||
|