Inspection Report

Cameron Milton

Property Address:
310 Windy Hills Drive
Columbus, SC

HomeBuyers Inspection HBI

Russell Buchanan
18 Business Park Circle
Arden, NC 28704
877-274-4299
Top Table of Contents Bottom
 

Table of Contents


Top Table of Contents Bottom
 
Date: 12/17/2007 Time: Report ID: Sam 2
Property:
310 Windy Hills Drive
Columbus, SC
Customer:
Cameron Milton
Real Estate Professional:

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.

Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.

Not Present (NP) = This item, component or unit is not in this home or building.

Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.

In Attendance:
Customer and their agent

Age Of Home:
Over 50 Years

Weather:
Clear

Temperature:
Over 60

Ground/Soil surface condition:
Dry

Rain in last 3 days:
No

Radon Test:
No

Water Test:
No

 
Top Table of Contents Bottom
1.  Roofing
The home inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components. The home inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing. The home inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors.

Styles & Materials
Roof Covering:
3-Tab fiberglass
Viewed roof covering from:
Ground
Sky Light(s):
None
Chimney (exterior):
Brick
  

 INNINPRR
1.0 ROOF COVERINGS   X
1.1 FLASHINGSX   
1.2 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONSX   
1.3 ROOF DRAINAGE SYSTEMS   X
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
Comments:
1.0 (1) The roof covering is old, and the life of covering has expired. The covering does need to be replaced. While it could last a year or so, some areas may need patching with tar as leaks develop. Some shingles are missing on main roof and daylight can be seen from attic. Immediate repairs are needed here.
1.0 Picture 1
1.0 Picture 2

(2) The tree limbs that are in contact with roof or hanging near roof should be trimmed.
1.0 Picture 3
1.3 (1) The gutter is loose or daylight between gutters and fascia at the rear. Loose or leaking gutters can cause deterioration of fascia, soffit or roof edge. It can also cause gutters to pull loose and lead to possible water intrusion. A qualified contractor should inspect and repair as needed.
1.3 Picture 1

(2) The gutter screens collapsed inside gutter at the front of home. A qualified person should repair or replace as needed. The gutter needs cleaning of debris at the front and as needed elsewhere. Gutters that drain poorly or clogged can lead to many costly problems such as deterioration of fascia, soffit or roof edge. It can also cause gutters to pull loose and lead to possible water intrusion. A qualified person should repair or replace as needed.
1.3 Picture 2
The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
2.  Exterior
The home inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The home inspector shall: Describe wall cladding materials; Operate all entryway doors and a representative number of windows; Operate garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components where deterioration is suspected. The home inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks. The home inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility.

Styles & Materials
Siding Style:
Brick
Siding Material:
Wood
Full brick
Exterior Entry Doors:
Wood
Appurtenance:
Covered porch
Porch
Sidewalk
Driveway:
Asphalt
 

 INNINPRR
2.0 WALL CLADDING FLASHING AND TRIMX   
2.1 DOORS (Exterior)   X
2.2 WINDOWS   X
2.3 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS   X
2.4 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building)X   
2.5 EAVES, SOFFITS AND FASCIAS   X
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
Comments:
2.1 The side entry door to basement reveals daylight when latched at areas missing weather-stripping. This is a small repair. A qualified person should repair or replace as needed.
2.1 Picture 1 Basement entry
2.2 The sill plate is deteriorated at right side (facing front). This is a small repair. A qualified person should repair or replace as needed.
2.2 Picture 1 Basement window (s)
2.3 (1) The support column(s) on covered porch at the left side (facing front) are split or cracked in areas and are deteriorated in areas. A repair or replacement is needed. A qualified contractor should perform the work.
2.3 Picture 1 Front Porch

(2) The steps on the porch at the rear of home are not uniform in"riser height" and are a tripping hazard. A fall or injury could occur if not corrected. I recommend repair as needed.
2.3 Picture 2 Rear Porch

(3) Some of the rafters of covered porch shows weakening by previous damage from leaks or other. Appears to remain strong to function. FYI
2.3 Picture 3
2.5 (1) The eave boards at eave on the gables and various roof edges are deteriorated. Repairs are needed. A qualified contractor should inspect and repair as needed.
2.5 Picture 1
2.5 Picture 2

(2) The soffit panel at eave on the front (right of main entry) are weathered and peeling paint. Further deterioration may occur if not repaired. A qualified person should repair or as needed. I am unable to determine if leak exists here or was a result of clogged gutters.
2.5 Picture 3 Front (right of main entry)
The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
3.  Interiors
The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installed cabinets; and A representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments.
Living Room
Dining Room
Kitchen

Styles & Materials
Ceiling Materials:
Plaster
Suspended ceiling panels
Ceiling Tile
Painted-over wallpaper
Wall Material:
Drywall
Plaster
Floor Covering(s):
Hardwood T&G
Tile
Vinyl
Interior Doors:
Wood
Window Types:
Double-hung
Single pane
Storm windows
Cabinetry:
Wood
Veneer
Countertop:
Laminate
  

 INNINPRR
3.0 CEILINGS   X
3.1 WALLSX   
3.2 FLOORSX   
3.3 STEPS, STAIRWAYS, BALCONIES AND RAILINGS   X
3.4 COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS   X
3.5 DOORS (REPRESENTATIVE NUMBER)   X
3.6 WINDOWS (REPRESENTATIVE NUMBER)   X
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
Comments:
3.0 (1) Plaster ceiling is in need of repair in bathroom. Currently it is covered by drop panels.
3.0 Picture 1

(2) The Ceiling Tile on the ceiling reveals a water stain indicating a leak did or still exists at the Bedroom. Due to recent dry weather, I am unable to determine if the leak still exists. A qualified contractor should inspect and repair as needed.

 

3.0 Picture 2
3.3 The hand/guard rail for the stairs to basement are missing balusters (on both sides). A fall or injury could occur if not corrected. A qualified contractor should repair or replace as needed.
3.3 Picture 1 basement stairs
3.3 Picture 2
3.4 Sink base is damaged under sink at bottom shelf likely from leaking faucet. Recommend repair or replace sink base cabinetry as necessary.
3.4 Picture 1 under kitchen sink
3.5 The Entry door and Closet door rubs at jamb when closing at the Living Room and hallway closet and Small bedroom. The Living room second door to porch is painted shut or will not open. A qualified person should repair or replace as needed.
3.6 There are cracked and broken glass at numerous windows throughout home. At least five windows missing sash cords at the Living Room, pantry and Small bedroom (left of hall bath) and at top of stairs. A qualified person should repair or replace as needed.
The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
4.  Structural Components
The Home Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilings and roof. The home inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The home inspector shall: Probe structural components where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to: Enter any area or perform any procedure that may damage the property or its components or be dangerous to or adversely effect the health of the home inspector or other persons.

Styles & Materials
Foundation:
Brick
Method used to observe Crawlspace:
No crawlspace
Floor Structure:
2 X 8
2 X 10
Wood joists
Wall Structure:
Wood
Brick
Columns or Piers:
Masonry block
Supporting walls
Ceiling Structure:
2X4
Roof Structure:
Stick-built
2 X 6 Rafters
Common board
Roof-Type:
Gable
Method used to observe attic:
Walked
Attic info:
Attic access
  

 INNINPRR
4.0 FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.)   X
4.1 WALLS (Structural)X   
4.2 COLUMNS OR PIERSX   
4.3 FLOORS (Structural)X   
4.4 CEILINGS (structural)X   
4.5 ROOF STRUCTURE AND ATTIC   X
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
Comments:
4.0 (1) Brick Foundation wall at the basement entry has missing mortar around windows . Repairs are needed. A skilled masonry contractor should perform the repairs.
4.0 Picture 1

(2) The brick foundation has been coated with a water proof sealer except behind shelving. If water intrusion occurs here, then shelving may need removing in order to coat area properly.
4.0 Picture 2 basement wall
4.5 The common board roofing indicates roof leaks or has leaked around the chimneys. Leaking roofs should be repaired to prevent damage. I recommend a qualified contractor perform the work. (See Roof Coverings comments)
4.5 Picture 1
The structure of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
5.  Plumbing System
The home inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; and Sump pumps. The home inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of main water supply shutoff device. The home inspector shall operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The home inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials.

Styles & Materials
Water Source:
Public
Water Filters:
None
Plumbing Water Supply (into home):
Galvanized (old)
Plumbing Water Distribution (inside home):
Galvanized
Copper
Washer Drain Size:
2" Diameter
Plumbing Waste:
PVC
Cast iron
lead waste (old)
Water Heater Power Source:
Electric
Water Heater Capacity:
40 Gallon (1-2 people)
Manufacturer:
A.O. SMITH

 INNINPRR
5.0 PLUMBING DRAIN, WASTE AND VENT SYSTEMS   X
5.1 PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES   X
5.2 HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS   X
5.3 MAIN WATER SHUT-OFF DEVICE (Describe location)X   
5.4 FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks)X   
5.5 MAIN FUEL SHUT OFF (Describe Location)X   
5.6 SUMP PUMP  X 
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
Comments:
5.0 (1) Upon arriving water was on and spilling onto floor of basement from nearby faucet and water heater. The hvac person who was their at the time of inspection claimed that he turned the water on at the street. I turned off the valve at faucet and water heater. FYI
5.0 Picture 1

(2) The stop-valve does not work properly at the Hall Bath sink. Repairs are needed. The tub drain drains slowly at main bath. There is a leak under bathtub that can be seen from removing access panel on wall. Repairs are needed. A qualified licensed plumber should repair or correct as needed.
5.0 Picture 2 Upstairs bath

(3) The basket strainer is leaking at left side and at right side at the Kitchen sink. Repairs are needed. A qualified licensed plumber should repair or correct as needed.
5.0 Picture 3

(4) The floor drain has a plug as if to keep something from coming in? After the inspection, the owner of the adjacent property volunteered information that the city sewer occasionally will back up and come into basement. This may be the reason for the plug? I am unable to determine if plug will prevent this from occurring. FYI
5.0 Picture 4 basement floor drain
5.1 (1) The lever on faucet leaks at the kitchen sink. Repairs are needed to stop leaking water from further damaging the cabinet bottom or to eliminate moisture that may contribute to fungi growth. I recommend repair as necessary by a qualified person. The spray nozzle is not working properly which could be as a result of no volume or pressure at the kitchen sink. Repairs are needed. A qualified licensed plumber should repair or correct as needed.

(2) The water pressure over-all is poor and would not pass "functional flow." A possible reason for weak volume or pressure could be old galvanized piping that is corroded inside. NOTE: NO SHOWER FOR BATH

Toilet will not fill with water likely due to clogged piping. I could not inspect the toilet fixture for leaks.

5.1 Picture 1
5.1 Picture 2
5.2 Water heater was empty and drain open at bottom when I arrived. I closed drain but at the end of inspection, drips were still occurring. Repairs may be needed.
5.2 Picture 1
5.2 Picture 2
5.3 The main shut off is the red knob located in the basement on the front wall. This is for your information.
5.3 Picture 1
5.5 The main fuel shut off is at gas meter outside
The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
6.  Electrical System
The home inspector shall observe: Service entrance conductors; Service equipment, grounding equipment, main over current device, and main and distribution panels; Amperage and voltage ratings of the service; Branch circuit conductors, their over current devices, and the compatibility of their ampacities and voltages; The operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interior plumbing fixtures, and all receptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and Smoke detectors. The home inspector shall describe: Service amperage and voltage; Service entry conductor materials; Service type as being overhead or underground; and Location of main and distribution panels. The home inspector shall report any observed aluminum branch circuit wiring. The home inspector shall report on presence or absence of smoke detectors, and operate their test function, if accessible, except when detectors are part of a central system. The home inspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate any over current device except ground fault circuit interrupters; Dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; Security system devices, heat detectors, or carbon monoxide detectors; Telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or Built-in vacuum equipment.

Styles & Materials
Electrical Service Conductors:
Overhead service
Aluminum
220 volts
Panel capacity:
100 AMP
Panel Type:
Fuses
Circuit breakers
Branch wire 15 and 20 AMP:
Copper
Wiring Methods:
Romex
Knob and Tube
 

 INNINPRR
6.0 SERVICE ENTRANCE CONDUCTORSX   
6.1 SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELSX   
6.2 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE   X
6.3 CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)   X
6.4 POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTUREX   
6.5 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)  X 
6.6 LOCATION OF MAIN AND DISTRIBUTION PANELSX   
6.7 SMOKE DETECTORSX   
6.8 CARBON MONOXIDE DETECTORSX   
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
Comments:
6.2 Problem(s) discovered with Branch Circuits such as doubled wiring at fuse(s), doubled wiring at circuit(s), and edison base fuse(s) under stairs, and any other problems that an electrician may discover while performing repairs need correcting. I recommend a licensed electrician inspect further and correct as needed.
6.2 Picture 1
6.2 Picture 2
6.3 (1) "Two-prong" outlets are missing cover-plates in the dining room and in the living room. This is a safety issue that needs to be corrected. I recommend repair as needed.
6.3 Picture 1 various rooms

(2) Loose light fixture needs securing in closet. Loose or unfinished wiring in attic should be corrected to remain safe ( Picture 2 ) .One splice box needs a cover-plate in the basement. I recommend repair as needed ( Picture 4 ) .
6.3 Picture 2
6.3 Picture 3
6.3 Picture 4
6.6 The main panel box is located at the basement.
The electrical system of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
7.  Heating / Central Air Conditioning
The home inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to home; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The home inspector shall describe: Energy source; and Heating equipment and distribution type. The home inspector shall operate the systems using normal operating controls. The home inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The home inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.

Styles & Materials
Heat Type:
Circulating boiler
Energy Source:
Gas
Number of Heat Systems (excluding wood):
One
Types of Fireplaces:
Conventional
Operable Fireplaces:
One
Number of Woodstoves:
None
Number of AC Only Units:
None
  

 INNINPRR
7.0 HEATING EQUIPMENT   X
7.1 NORMAL OPERATING CONTROLSX   
7.2 AUTOMATIC SAFETY CONTROLSX   
7.3 DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)   X
7.4 PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM   X
7.5 CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat systems) X  
7.6 SOLID FUEL HEATING DEVICES (Fireplaces, Woodstove)X   
7.7 GAS/LP FIRELOGS AND FIREPLACES  X 
7.8 COOLING AND AIR HANDLER EQUIPMENT  X 
7.9 NORMAL OPERATING CONTROLS  X 
7.10 PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM  X 
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
Comments:
7.0 The gas-fired boiler did not function or is non-operational. A repair or replacement is needed. I recommend further inspection by a licensed HVAC contractor.
7.0 Picture 1
7.0 Picture 2
7.3 Due to the concern for water volume or pressure and because of the old piping that was turned off for an extended period of time, and the fact that the boiler is non-operational, I am concerned of whether or not the radiators will function properly when boiler is repaired. A clogged or failed radiator can be expensive to replace. I strongly recommend that an HVAC person inspect all the radiators when boiler becomes operable. You should obtain a letter from the HVAC company as to the condition of radiators, piping and boiler before you close on home.
7.4 There is no heat source for Bedroom on right (at top of stairs).
7.4 Picture 1 bedroom
7.5 The liner for fireplace was partially visible and appears good except for creosote dust that may conceal a hairline crack until cleaned and inspected by a licensed chimney sweep. I did not inspect the liner for gas fired boiler. For a detailed inspection of liner, I recommend a qualified chimney sweep inspect for safety.
7.8 There is no central air conditioning in this home. This home has no central air (No AC). This is for your information.
The heating and cooling system of this home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
8.  Insulation and Ventilation
The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics and foundation areas; Kitchen, bathroom, and laundry venting systems; and the operation of any readily accessible attic ventilation fan, and, when temperature permits, the operation of any readily accessible thermostatic control. The home inspector shall describe: Insulation in unfinished spaces; and Absence of insulation in unfinished space at conditioned surfaces. The home inspector shall: Move insulation where readily visible evidence indicates the need to do so; and Move insulation where chimneys penetrate roofs, where plumbing drain/waste pipes penetrate floors, adjacent to earth filled stoops or porches, and at exterior doors. The home inspector is not required to report on: Concealed insulation and vapor retarders; or Venting equipment that is integral with household appliances.

Styles & Materials
Attic Insulation:
Blown
Fiberglass
R-19 or better
Ventilation:
Gable vents
Passive
Exhaust Fans:
None
Dryer Power Source:
220 Electric
Dryer Vent:
Flexible Vinyl
Floor System Insulation:
NONE

 INNINPRR
8.0 INSULATION IN ATTICX   
8.1 INSULATION UNDER FLOOR SYSTEM  X 
8.2 VAPOR RETARDERS (ON GROUND IN CRAWLSPACE OR BASEMENT)  X 
8.3 VENTILATION OF ATTIC AND FOUNDATION AREASX   
8.4 VENTING SYSTEMS (Kitchens, baths and laundry)X   
8.5 VENTILATION FANS AND THERMOSTATIC CONTROLS (ATTIC)  X 
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace
Comments:
8.0 The attic has a small amount of insulation and "Knob and Tube" wiring is present. As a safety rule Knob and Tube wiring should never have insulation covering this wire or over heating can occur. If new insulation is added, an electrician should first replace knob and tubing wires with updated wiring.
The insulation and ventilation of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Venting of exhaust fans or clothes dryer cannot be fully inspected and bends or obstructions can occur without being accessible or visible (behind wall and ceiling coverings). Only insulation that is visible was inspected. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
9.  Built-In Kitchen Appliances
The home inspector shall observe and operate the basic functions of the following kitchen appliances: Permanently installed dishwasher, through its normal cycle; Range, cook top, and permanently installed oven; Trash compactor; Garbage disposal; Ventilation equipment or range hood; and Permanently installed microwave oven. The home inspector is not required to observe: Clocks, timers, self-cleaning oven function, or thermostats for calibration or automatic operation; Non built-in appliances; or Refrigeration units. The home inspector is not required to operate: Appliances in use; or Any appliance that is shut down or otherwise inoperable.

Styles & Materials
Dishwasher Brand:
KENMORE
Disposer Brand:
IN SINK ERATOR
Exhaust/Range hood:
NONE
Range/Oven:
NONE
Built in Microwave:
NONE
 

 INNINPRR
9.0 DISHWASHERX   
9.1 RANGES/OVENS/COOKTOPS  X 
9.2 RANGE HOOD  X 
9.3 TRASH COMPACTOR  X 
9.4 FOOD WASTE DISPOSERX   
9.5 MICROWAVE COOKING EQUIPMENT  X 
IN=Inspected, NI=Not Inspected, NP=Not Present, RR=Repair or Replace

The built-in appliances of the home were inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2007 : Licensed To HomeGauge
Top Table of Contents Bottom
 

General Summary


HomeBuyers Inspection HBI

18 Business Park Circle
Arden, NC 28704
877-274-4299

Customer
Cameron Milton

Address
310 Windy Hills Drive
Columbus, SC

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the home. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

1.  Roofing
1.0   ROOF COVERINGS
  Repair or Replace
(1) The roof covering is old, and the life of covering has expired. The covering does need to be replaced. While it could last a year or so, some areas may need patching with tar as leaks develop. Some shingles are missing on main roof and daylight can be seen from attic. Immediate repairs are needed here.
(2) The tree limbs that are in contact with roof or hanging near roof should be trimmed.
1.3   ROOF DRAINAGE SYSTEMS
  Repair or Replace
(1) The gutter is loose or daylight between gutters and fascia at the rear. Loose or leaking gutters can cause deterioration of fascia, soffit or roof edge. It can also cause gutters to pull loose and lead to possible water intrusion. A qualified contractor should inspect and repair as needed.
(2) The gutter screens collapsed inside gutter at the front of home. A qualified person should repair or replace as needed. The gutter needs cleaning of debris at the front and as needed elsewhere. Gutters that drain poorly or clogged can lead to many costly problems such as deterioration of fascia, soffit or roof edge. It can also cause gutters to pull loose and lead to possible water intrusion. A qualified person should repair or replace as needed.

2.  Exterior
2.1   DOORS (Exterior)
  Repair or Replace
The side entry door to basement reveals daylight when latched at areas missing weather-stripping. This is a small repair. A qualified person should repair or replace as needed.
2.2   WINDOWS
  Repair or Replace
The sill plate is deteriorated at right side (facing front). This is a small repair. A qualified person should repair or replace as needed.
2.3   DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS
  Repair or Replace
(1) The support column(s) on covered porch at the left side (facing front) are split or cracked in areas and are deteriorated in areas. A repair or replacement is needed. A qualified contractor should perform the work.
(2) The steps on the porch at the rear of home are not uniform in"riser height" and are a tripping hazard. A fall or injury could occur if not corrected. I recommend repair as needed.
(3) Some of the rafters of covered porch shows weakening by previous damage from leaks or other. Appears to remain strong to function. FYI
2.5   EAVES, SOFFITS AND FASCIAS
  Repair or Replace
(1) The eave boards at eave on the gables and various roof edges are deteriorated. Repairs are needed. A qualified contractor should inspect and repair as needed.
(2) The soffit panel at eave on the front (right of main entry) are weathered and peeling paint. Further deterioration may occur if not repaired. A qualified person should repair or as needed. I am unable to determine if leak exists here or was a result of clogged gutters.

3.  Interiors
3.0   CEILINGS
  Repair or Replace
(1) Plaster ceiling is in need of repair in bathroom. Currently it is covered by drop panels.
(2) The Ceiling Tile on the ceiling reveals a water stain indicating a leak did or still exists at the Bedroom. Due to recent dry weather, I am unable to determine if the leak still exists. A qualified contractor should inspect and repair as needed.

 

3.3   STEPS, STAIRWAYS, BALCONIES AND RAILINGS
  Repair or Replace
The hand/guard rail for the stairs to basement are missing balusters (on both sides). A fall or injury could occur if not corrected. A qualified contractor should repair or replace as needed.
3.4   COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS
  Repair or Replace
Sink base is damaged under sink at bottom shelf likely from leaking faucet. Recommend repair or replace sink base cabinetry as necessary.
3.5   DOORS (REPRESENTATIVE NUMBER)
  Repair or Replace
The Entry door and Closet door rubs at jamb when closing at the Living Room and hallway closet and Small bedroom. The Living room second door to porch is painted shut or will not open. A qualified person should repair or replace as needed.
3.6   WINDOWS (REPRESENTATIVE NUMBER)
  Repair or Replace
There are cracked and broken glass at numerous windows throughout home. At least five windows missing sash cords at the Living Room, pantry and Small bedroom (left of hall bath) and at top of stairs. A qualified person should repair or replace as needed.

4.  Structural Components
4.0   FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.)
  Repair or Replace
(1) Brick Foundation wall at the basement entry has missing mortar around windows . Repairs are needed. A skilled masonry contractor should perform the repairs.
(2) The brick foundation has been coated with a water proof sealer except behind shelving. If water intrusion occurs here, then shelving may need removing in order to coat area properly.
4.5   ROOF STRUCTURE AND ATTIC
  Repair or Replace
The common board roofing indicates roof leaks or has leaked around the chimneys. Leaking roofs should be repaired to prevent damage. I recommend a qualified contractor perform the work. (See Roof Coverings comments)

5.  Plumbing System
5.0   PLUMBING DRAIN, WASTE AND VENT SYSTEMS
  Repair or Replace
(1) Upon arriving water was on and spilling onto floor of basement from nearby faucet and water heater. The hvac person who was their at the time of inspection claimed that he turned the water on at the street. I turned off the valve at faucet and water heater. FYI
(2) The stop-valve does not work properly at the Hall Bath sink. Repairs are needed. The tub drain drains slowly at main bath. There is a leak under bathtub that can be seen from removing access panel on wall. Repairs are needed. A qualified licensed plumber should repair or correct as needed.
(3) The basket strainer is leaking at left side and at right side at the Kitchen sink. Repairs are needed. A qualified licensed plumber should repair or correct as needed.
(4) The floor drain has a plug as if to keep something from coming in? After the inspection, the owner of the adjacent property volunteered information that the city sewer occasionally will back up and come into basement. This may be the reason for the plug? I am unable to determine if plug will prevent this from occurring. FYI
5.1   PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES
  Repair or Replace
(1) The lever on faucet leaks at the kitchen sink. Repairs are needed to stop leaking water from further damaging the cabinet bottom or to eliminate moisture that may contribute to fungi growth. I recommend repair as necessary by a qualified person. The spray nozzle is not working properly which could be as a result of no volume or pressure at the kitchen sink. Repairs are needed. A qualified licensed plumber should repair or correct as needed.
(2) The water pressure over-all is poor and would not pass "functional flow." A possible reason for weak volume or pressure could be old galvanized piping that is corroded inside. NOTE: NO SHOWER FOR BATH

Toilet will not fill with water likely due to clogged piping. I could not inspect the toilet fixture for leaks.

5.2   HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS
  Repair or Replace
Water heater was empty and drain open at bottom when I arrived. I closed drain but at the end of inspection, drips were still occurring. Repairs may be needed.

6.  Electrical System
6.2   BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE
  Repair or Replace
Problem(s) discovered with Branch Circuits such as doubled wiring at fuse(s), doubled wiring at circuit(s), and edison base fuse(s) under stairs, and any other problems that an electrician may discover while performing repairs need correcting. I recommend a licensed electrician inspect further and correct as needed.
6.3   CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)
  Repair or Replace
(1) "Two-prong" outlets are missing cover-plates in the dining room and in the living room. This is a safety issue that needs to be corrected. I recommend repair as needed.
(2) Loose light fixture needs securing in closet. Loose or unfinished wiring in attic should be corrected to remain safe ( Picture 2 ) .One splice box needs a cover-plate in the basement. I recommend repair as needed ( Picture 4 ) .

7.  Heating / Central Air Conditioning
7.0   HEATING EQUIPMENT
  Repair or Replace
The gas-fired boiler did not function or is non-operational. A repair or replacement is needed. I recommend further inspection by a licensed HVAC contractor.
7.3   DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)
  Repair or Replace
Due to the concern for water volume or pressure and because of the old piping that was turned off for an extended period of time, and the fact that the boiler is non-operational, I am concerned of whether or not the radiators will function properly when boiler is repaired. A clogged or failed radiator can be expensive to replace. I strongly recommend that an HVAC person inspect all the radiators when boiler becomes operable. You should obtain a letter from the HVAC company as to the condition of radiators, piping and boiler before you close on home.
7.4   PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM
  Repair or Replace
There is no heat source for Bedroom on right (at top of stairs).
7.5   CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat systems)
  Not Inspected
The liner for fireplace was partially visible and appears good except for creosote dust that may conceal a hairline crack until cleaned and inspected by a licensed chimney sweep. I did not inspect the liner for gas fired boiler. For a detailed inspection of liner, I recommend a qualified chimney sweep inspect for safety.

8.  Insulation and Ventilation
8.0   INSULATION IN ATTIC
  Inspected
The attic has a small amount of insulation and "Knob and Tube" wiring is present. As a safety rule Knob and Tube wiring should never have insulation covering this wire or over heating can occur. If new insulation is added, an electrician should first replace knob and tubing wires with updated wiring.


Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2007 : Licensed To HomeGauge