New Construction Sample Report
Date:
2/16/2021
Report
Prepared For: Jenna Buyer
Client: Jenna Buyer |
Date: 2/16/2021 | Report ID: New Construction Sample Report |
Property: 789 New St Sunnyvale PA 54321 |
Client's Agent: |
Present at Inspection: Inspector, Painters | Approximate age: New Construction | Structure Style: Colonial |
Temperature: 45 Degrees | Weather: Sunny | Occupancy Status: Vacant, Unfurnished |
Safety Concern: Denotes an observation, defect or recommendation that is considered an immediate safety concern. Safety standards have increased over the years. The inspector will use today's standards as a baseline to evaluate the home. Safety standards may have changed since your home was built however, it is recommended when ever practical to bring the home up to current standards.
Correction recommended: Denotes a system or component of the home that is deficient or at the end of its service life, and needs corrective action by a professional to assure proper and reliable function. We recommend the professional making any repairs to inspect the property further, in order to discover and repair related problems that were not identified in the report. All evaluations corrections and should be made prior to end of inspection contingency.
Further evaluation recommended: Denotes an observation, defect or recommendation where the full extent of the issue cannot be ascertained in a visual inspection. A more technically exhaustive evaluation or destructive testing may be need to determine the full extent of the issue. All evaluations corrections and should be made prior to end of inspection contingency.
Improvement recommended: Denotes a system or component that should receive normal maintenance, repair, or adjustment in order to continue
functioning properly.
The American Society of Home Inspectors (ASHI): ASHI #261399 |
International Association of Certified Home Inspectors: InterNACHI #15033120 |
Certified Pesticide Applicator: BU13789 Certification #710880 |
PA DEP Radon: Firm #2288 Certification #3356 |
Certified Residential Thermographer: CRT # 2020042407 |
North American Deck & Railing Association (NADRA): Deck Professional - Code Certified |
Method used to Inspect: Viewed from ladder at gutters edge |
Roof Covering Materials: Asphalt Fiberglass Shingles |
Number of layers visible: One layer |
Approximate Age: New |
Average Service Life: 20-30 years |
Gutter Type: 6" K |
Gutter Guards: No |
Method Used to Inspect Attic: Attic access hatch |
Roof Structural Type: Engineered Roof Trusses |
Rafter Board Dimension: 2 X 4, 24 inches on center |
Attic Ventilation Visible: Ridge Vent Soffit Vents |
Attic Insulation Type: Loose-Fill Fiberglass |
Aproxomate R Value: R38 |
Attic Restrictions: Limited Access No Flooring Framing and bracing Low Clearance Insulation |
Exterior Wall Covering Materials: Vinyl Simulated Stone (Adhered Masonry Veneer)) |
Number of Garage Doors: Two |
Number of Openers: Two |
Photoelectric Eyes: Installed |
Heating Type: Gas Furnace |
Distribution Method: Duct Work |
Location: Basement |
Approximate Age: New |
Average Service Life: 20-25 years |
Thermostat(s): Dining room |
Heating Type: Gas Furnace |
Distribution Method: Duct Work |
Location: Attic |
Approximate Age: New |
Average Service Life: 20-25 years |
Thermostat(s): Master bedroom |
Cooling Type: Central Air |
Distrubution Method: Duct Work |
Location: Basement Exterior-Right side |
Aproximate Age: New |
Average Service life: 15-20 years |
Thermostat: Dining room |
Cooling Type: Central Air |
Distrubution Method: Duct Work |
Location: Attic Exterior-Right side |
Aproximate Age: New |
Average Service life: 15-20 years |
Thermostat: Master bedroom |
Hot Water Soure:: Gas Water Heater |
Capacity: 50 Gallon |
Approximate Age: New |
Average Service Life: 9-12 years |
Water Supply System: Well System |
Water Supply Piping: CPVC Cross linked polyethylene (PEX) |
Main Water shut off location: Rear of Basement |
Sewage/Waste System:: Septic System |
Sewage Waste Piping:: PVC |
The waste disposal system appeared to be functional at the time of this inspection.
The pipes are well supported with no visible cracks in any of the lines.
Water was run at all the plumbing fixtures in the house there were no leaks observed in any of the visible sewer lines.
The clean out is visible
Service Cable Location: Underground Service Line |
Service Size: 200 AMP |
Panel Type: Circuit breakers |
Main Disconnect: Breaker in panel |
Wiring Method: Romex |
Service Grounding:: Grounding Rod Exterior |
Foundation Stucture: Poured concrete |
Floor Structure: Manufactured I Joists |
Inspection Restrictions: Insulation Duct Work and/or Plumbing |
The sump pump functioned when tested.
There is a check valve installed on the discharge pipe, Good.
Remember to keep the sump pump free of debris and dirt, keep the pump hole covered, and check the pump motor at least once a year.
Smoke Detectors: Hard wired with batter back up |
Carbon Monoxide Detectors: Yes |
Dryer hook up: Both gas and electric |
Fireplace: Direct Vent |
Significant areas of chimney flues cannot be adequately viewed during a field inspection, as has been documented by the Chimney Safety Institute of America: "The inner reaches of a flue are relatively inaccessible, and it should not be expected that the distant oblique view from the top or bottom is adequate to fully document damage even with a strong light." Therefore, because our inspection of chimneys is limited to those areas that can be viewed without dismantling any portion of them, and does not include the use of specialized equipment, we will not guarantee their integrity or drafting ability and recommend that they be video-scanned (level two inspection) prior to settlement. Only a level two inspection performed by a CSIA (Chimney safety Institute of America) certified chimney sweep can determine the condition of the flue and if the fireplace is safe to use.
More information about fireplaces and chimneys can be obtained at www.csia.com.
Number of Full Baths: Four |
Number of Half Baths: One |
Outlets GFCI Protected: Yes |
Stove Cook Top: Gas |
Oven: Electric |
Microwave: Yes |
Dishwasher: Yes |
Garbage Disposal: No |
Outlets GFCI Protected: Yes |
This summary list is not intended to be a complete list. There may be other items that are in need of improvement, repair or correction that are not listed here. There may also be improvements that are necessary, but are outside the scope of this inspection.
If any evaluations or corrections are needed, then a professional should inspect the property even further, in order to discover and repair related problems that were not identified in the report. All corrections and evaluations should be made prior to purchasing the property.
The following estimate and repair costs are provided for your convenience. They are not part of you inspection report. The costs are based on HomeTeck Remodeling and Renovation Cost Estimator 2017, and direct input from contractors in the local area.
The costs are given in ranges, as required by the Pennsylvania home inspection law. The actual cost for your home repairs or improvements may be different from the cost listed here.
PEACH Inspections always recommends getting three estimates from contractors who may be performing the work. PEACH Inspections makes no warranty or guarantee as to the correctness or sufficiency of the information contained in this list. PEACH Inspections assumes no responsibility or liability in connection with the use of this list.
1.0 | Inspectors Comments | |
. | ||
CODE REFERENCESYour new home should be built to three standards; the Pennsylvania Uniform Construction Code (UCC), manufacture specifications when applicable, and current workmanship and industry standards. While inspecting your home to the ASHI Standards of Practice, if in the opinion of the inspector discrepancies are found in the visible areas of the home between the home's construction and the current building code they will be noted in the report. Code sections may be provided in the report to support the inspector's opinion.Your inspector is not a building code official and has no authority to enforce the building code. This inspection is not a code complaint inspection. The responsibility to build to the current Building Code is solely that of the home builder. A quick word about Building Codes: In July 2004 Pennsylvania adopted the Uniform Construction Code (UCC). For residential construction the bases of the UCC is the International Residential Code (IRC) published by the International Code Council (ICC), with some modification adopted by the state legislature. All builders are required to follow the UCC and all Building Code Officials are required to enforce the UCC. A Building Code Official is someone who is employed directly or indirectly by a municipality. Only the Building Code Official has the authority to enforce the building code. Building Code Officials and the UCC are regulated by the Pennsylvania Department of Labor and industry (L&I). |
3.0 | ROOF COVERINGS | |
. | ||
CORRECTION RECOMMENDED: Ridge cap shingles were missing on the lower rear roof. This will allow water intrusion. A qualified roofing contractor should replace shingles as needed. * |
5.7 | WINDOWS | |
. | ||
CORRECTION RECOMMENDED: A damaged screen was noted on the front dining room window. The screen should be repaired or replaced. |
7.0.A | HEATING EQUIPMENT | |
. | ||
There was excessive construction dust inside of the HVAC system. Heavy dust was noted in the blower compartment and on the fan blades. Dust and/or debris can damage an HVAC system. Recommend having a qualified HVAC contractor clean the first floor HVAC system prior to settlement. * |
7.0.B | HEATING EQUIPMENT | |
. | ||
There was excessive construction dust inside of the HVAC system. Heavy dust was noted in the blower compartment and on the fan blades. Dust and/or debris can damage an HVAC system. Recommend having a qualified HVAC contractor clean the second floor HVAC system prior to settlement. * |
8.0.A | AIR CONDITIONING SYSTEM | |
. | ||
The central air conditioning was not operationally tested during this inspection. There may be deficiencies with the system that are in need of repair or correction that
the inspector was unable to verify. Most manufacturers of air conditioning systems recommend that these units not be tested if the ambient temperature for the
previous 24 hours is below 60° F to avoid damaging the compressor. It is recommended that a service company check the unit when ambient temperatures permit. If
this is during the winter months and temperatures are not expected to rise to this level there is an alternative option. If there are any concerns you may wish to contact
a qualified licensed HVAC contractor, who can bring special equipment to heat up the crankcase of the compressor in order to safely test the equipment. This method
of testing is beyond the scope of this visual inspection.
|
8.0.B | AIR CONDITIONING SYSTEM | |
. | ||
The central air conditioning was not operationally tested during this inspection. There may be deficiencies with the system that are in need of repair or correction that
the inspector was unable to verify. Most manufacturers of air conditioning systems recommend that these units not be tested if the ambient temperature for the
previous 24 hours is below 60° F to avoid damaging the compressor. It is recommended that a service company check the unit when ambient temperatures permit. If
this is during the winter months and temperatures are not expected to rise to this level there is an alternative option. If there are any concerns you may wish to contact
a qualified licensed HVAC contractor, who can bring special equipment to heat up the crankcase of the compressor in order to safely test the equipment. This method
of testing is beyond the scope of this visual inspection.
|
10.1 | MANA BLOC | |
. | ||
The valve key was missing from the Mana bloc. Recommend asking builder for a valve key so the valves can be turned on or off as needed. * |
11.1 | MAIN ELECTRICAL PANEL | |
. | ||
No energy certificate was observed on the electric panel. There should be an energy certificate posted on the electrical panel. The certificate should list the R-values and U factors of the different building components as well as the efficiency rating of the heating and cooling equipment. |
13.1 | WINDOWS | |
. | ||
CORRECTION RECOMMENDED: Some of the window sills are below 24 inches to the floor. Today's standards state that where the opening of an operable window is located more than 72 inches above the finished grade or surface below, the lowest part of the clear opening of the window shall be a minimum of 24 inches above the finished floor of the room in which the window is located. Operable sections of windows shall not permit openings that allow passage of a 4 inch sphere where such openings are located within 24 inches of the finished floor. Care should be taken around windows when open. Recommend having window opening limiting devices installed by a qualified person. * |
15.1 | MICROWAVE | |
. | ||
CORRECTION RECOMMENDED: The microwave did not function at the time of inspection. Every option was checked but the screen continued to beep and say open/close door. A qualified appliance repair contractor should repair or replace as needed. * |
ATTENTION: This inspection report is incomplete without reading the information included herein at these links/attachments. Note If you received an emailed PDF version of this page and did not receive a copy of the report through the internet please contact your inspector for a PDF copy of the attachments.
CODE REFERENCES
Your new home should be built to three standards; the Pennsylvania Uniform Construction Code (UCC), manufacture specifications when applicable, and current workmanship and industry standards. While inspecting your home to the ASHI Standards of Practice, if in the opinion of the inspector discrepancies are found in the visible areas of the home between the home's construction and the current building code they will be noted in the report. Code sections may be provided in the report to support the inspector's opinion.Your inspector is not a building code official and has no authority to enforce the building code.
This inspection is not a code complaint inspection. The responsibility to build to the current Building Code is solely that of the home builder.
A quick word about Building Codes:
In July 2004 Pennsylvania adopted the Uniform Construction Code (UCC). For residential construction the bases of the UCC is the International Residential Code (IRC) published by the International Code Council (ICC), with some modification adopted by the state legislature. All builders are required to follow the UCC and all Building Code Officials are required to enforce the UCC. A Building Code Official is someone who is employed directly or indirectly by a municipality. Only the Building Code Official has the authority to enforce the building code. Building Code Officials and the UCC are regulated by the Pennsylvania Department of Labor and industry (L&I).