Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Age of Home: New Construction, Under 5 Years | Inspection Type: Standard Home Inspection, Ancillary Service | Home Status: Vacant |
Weather: Cloudy, Light Rain | In Attendance: Inspector Only | Temperature: Over 60 (F) = 15.5 (C) |
Type of building: Single Family (2 story), Crawlspace | Radon Test: Yes Test ID : 2203JG3953Titovets RADON |
|
Styles & Materials
Roof Description: Steep Slope Roof Covering/Type: Architectural Estimated Age: 0 to 5 years Design Life: 25 to 30 Years Inspection Method: Ladder at Eaves Binoculars from the Ground Location: Whole Roof Limitations: height, design, pitch Wet roofing component Wet weather |
|
Styles & Materials
Siding Style: Brick Shiplap Siding Material: Cement-Fiber Brick veneer Porch: Masonry/Concrete Covered Front Columns: Wood Deck: Rear |
|
Styles & Materials
Walkway: Concrete Driveway: Concrete |
|
Styles & Materials
Description: Pull Down Stairs Walk up/in Multiple areas Inspection Method: Entered from Entry Framing: Trusses Wood Frame Sheathing: Structural Panels Insulation: Bat & Loose Limitations: Design Floored Areas Height/No Walkway/Insulation HVAC Ductwork Tools Used for Inspection: Flashlight Camera Moisture Meter |
|
Styles & Materials
Description: Multiple Car Attached Garage Door Type: One automatic Garage Door Material: Metal Special Limitations: Finished Materials |
|
Styles & Materials
Location: Main Level Rear Right Side Ventilator: Exhaust Fan Dishwasher: New 0-5 years old Built In Microwave: New 0-5 Years old Cook Top: New Gas 0-5 Years old Wall Oven: New Electric 0-5 Years old Special Limitations: Appliances Finished Materials |
|
Styles & Materials
Ceiling Materials: Gypsum Board/Wood Wall Material: Gypsum Board/Wood Predominant Floors: Wood Window Types: Thermal/Insulated Single-hung Tilt feature Smoke Detectors: Battery & Hard Wired Detector Location: Halls & Bedrooms Fireplace: Gas Burner Vented Special Limitations: Appliances Finish Materials |
|
Styles & Materials
Bathroom: Full Bath Location: Jack n Jill Left Side of House Upper Level Ventilator: Exhaust Fan Special limitations: Under Tub not Accessible |
|
Styles & Materials
Bathroom: Full Bath Location: Upper Level Rear Right Side of House Ventilator: Window Exhaust Fan Special limitations: Under Tub not Accessible |
|
Styles & Materials
Bathroom: Full Bath w/Stall Location: Main Level Primary Bedroom Ventilator: Window Exhaust Fan |
|
Styles & Materials
Bathroom: 1/2 Bath Location: Hallway Main Level Ventilator: Exhaust Fan |
|
Styles & Materials
Electrical Service Conductors: Below ground Entrance Line: Bus Bar Service Disconnect: Single Main Location / Distribution Panel Left Side Exterior 200 Amps Major Appliances/240 volts: Aluminum/Copper Distribution Panel: Circuit Breakers W/Sub Panels Estimated Amps: 200 Left Side Exterior Sub Panel: W/AFCI Breakers Garage Household Circuits: Copper GFCI: At Receptacles Special Limitations: Appliances Finished Materials |
|
Styles & Materials
System Type: Electric Air Conditioner System Location: Right Side of Dwelling System Make: GrandAire Estimated Age: New 0-5 Years Design Life: 8-12 Years General Distribution: Ducted/Register |
|
Styles & Materials
System Make: GrandAire System Type: Hot Air Natural Gas System Location: Attic Crawlspace Estimated Age: New 0-5 Years Design Life: 8-12 Years General Distribution: Ducte/Registers Panels Removed on Unit: Yes |
|
Styles & Materials
Water Piping: Pex Water Source: Public Water Shut Off/Location: Garage Gas Shut Off/Location: Meter Plumbing Waste: PVC Special Limitations: Finsished Materials Main Water Line: Plastic Front of Crawlspace |
|
Styles & Materials
Manufacturer: Navien Water Heater Location: Garage Water Heater Type: Direct Heated Natural Gas Tankless Capacity: Not Applicable Age: New 0-5 Years old Design Life: 10-15 Years |
|
Styles & Materials
Crawlspace: Full House Crawlspace Inspection Method: Entered from Entry Foundation Walls/Piers: Block Brick House Floor Structure: Wood Frame Joist Insulation: Blanket/Batt/Fiberglass Special Limitations: Insulation Finish Materials Moisture Barrier Tools Used for Inspection: Flashlight Camera Moisture Meter Screw Driver/Probe |
|
Styles & Materials
Description: crawlspace Special Limitations: Finish Materials Insulation Moisture Barrier |
P.O. Box 5087
Clover, SC 29710
704-718-0043
Customer
New Homeowner
Address
760 In Your Neighborhood Rd.
York SC 29745
"The North Carolina Home Inspection Licensure Board requires a summary which includes only items which do not function as intended or adversely affects the habitability of the dwelling; or appears to warrant further investigation by a specialist or requires a subsequent observation." The law stipulates tthat the summary shall not contain recommendations to upgrade or engance the function, efficiency or safety of the home. The following statement is required: This summary is not the entire report. The full report may include additional information of interest or concern to the client. It is strongly recommended that the client promptly read the complete report. For information regarding the negotiability of any itemm in this report under a real estate purchase contract, contact your North Carolina real estate agent or an attorney. "It is recommended that the client read the complete report." The summary includes only items, which in the inspector's opinion meet the states's requirements. The inspector nor Galop Home Concepts are responsible for the items which in the opinion of any interested part were either included in the suemmary, but should not be omitted, or should have been included in the summary but were omitted. Please call our office 704-718-0043 with any concerns after review. Any questionable issues should be discussed with the Inspector and or/the Inspection Company before closing.
Note#1 While listings in this Summary may serve as a guide to help prioritize remedial needs, the final decision regarding any action to be taken must be made by the client following consultation with the appropriate specialists and/or professional qualified contractors.
Note#2 Directions are normally as though facing the dwelling from the street unless otherwise stated.
Note#3 Not all areas of concerns were photographed. The client should consider the photos/videos as a continuation/enhancement of the original report. Client is advised to read the entire inspection report and any other reports/inspections performed prior to closing. If there are any concerns with rot/decay/wood destroying insect damage of components of the dwelling either at the exterior/interior/sub-structure, client is advised that all areas of wood were not probed, photographed or reported. Client should infer that there are/may be additional areas of decay/damage at other locations and the entire element should be evaluated by a qualified professional contractor. Any repiars made from this report should be considered a starting point and concealed/hidden items not reported/mentioned within this report due to not being readily visible and should always be further evaluated by qualified professional. This is always the recommendation of Galop Home Concepts LLC.
1.4 | Gutters | |
Inspected, Repair or Replace | ||
(1) Damaged area of gutter observed at the front side of dwelling, dry at time of inspection
integrity was not able to be determined for overflow of the gutter due to damage.
Recommend client verify proper function of the component with the builder prior to
closing.
![]() 1.4 Item 1(Picture)
|
||
(2) Gutters for all sides of house observed with excessive debris. This is conducive to the
drainage system not able to function as intended for carrying water away from the
foundation/dwelling. Recommend correction by the builder.
![]() 1.4 Item 2(Picture)
|
1.5 | Downspouts | |
Inspected, Repair or Replace | ||
Recommend adding downspout extensions for all downspouts to move water away from
the dwelling to avoid erosion at the foundation wall. Recommend correction by the
builder. Also refer to Gutters element above for additional comments/concerns.
![]() 1.5 Item 1(Picture)
|
2.3 | Windows | |
Inspected, Repair or Replace | ||
Window screens observed missing throughout the dwelling. This is conducive to the
component not able to function as intended. Recommend correction by the builder. Also
refer to interior element/windows for comments/concerns.
![]() 2.3 Item 1(Picture)
|
2.6 | Railings | |
Inspected, Repair or Replace | ||
A Graspable handrail is one that can readily be grasped to prevent a fall if loss of
balance should occur when ascending or descending a stairway. A handrail is
considered readily grasped if it is a 2x4 placed with it's longest width laid horizontal to
the ground for exterior deck applications. The component observed placed for the
handrail at the rear deck for this dwelling is observed larger than a 2x4. Recommend
correction by the builder.
![]() 2.6 Item 1(Picture)
![]() 2.6 Item 2(Picture)
|
2.7 | Deck | |
Inspected, Repair or Replace | ||
(1) Left side of deck rim joist board at the foundation for joist attachment observed what
appears to be an improper attaching method, nailed. This is conducive to fatigue/failure
of the component over time. Recommend proper attachment method by the builder.
![]() 2.7 Item 1(Picture)
|
||
(2) 4x4 supporting posts for deck observed notched, nuts also not properly engaged. This
is conducive to potential fatigue/failure of decking component. The standard for deck
support posts attached by notching to be a 6x6. Recommend correction by the builder.
(Pictures shown as examples of concern for some areas but not all)
![]() 2.7 Item 2(Picture)
![]() 2.7 Item 3(Picture)
![]() 2.7 Item 4(Picture)
|
4.0 | Attic Framing | |
Inspected, Repair or Replace | ||
Truss framing members should not be cut field-altered or damaged without the proper
design analysis. Once altered or damaged a change in the loading pattern often dictates
that the manufacturer or a qualified engineer determine what remedial action is
required. Truss in the main attic of dwelling on the left hand side center area observed
with damaged/not attached gusset plate. Recommend correction by the builder with
proper engineering attached near the repair.
![]() 4.0 Item 1(Picture)
|
6.1 | Range | |
Inspected, Repair or Replace | ||
(2) Drip leg observed missing for the cooktop, this is conducive to debris/water intrusion of
the component. Recommend correction by the builder. (Picture 2 shows the proper
placement of drip leg for this application)
![]() 6.1 Item 2(Picture)
![]() 6.1 Item 3(Picture)
|
6.4 | Dishwasher | |
Not Inspected, Repair or Replace | ||
Dishwasher was not inspected due to dishwasher noted not plugged in and GFCI
receptacle tripped upon arrival to inspection. This may indicate an issue with the
component not able to be determined at time of inspection. Recommend client discuss
with builder for disclosure of any concerns and correction by the builder if necessary.
![]() 6.4 Item 1(Picture)
![]() 6.4 Item 2(Picture)
|
6.6 | Cabinets | |
Inspected, Repair or Replace | ||
Hole/penetration under the kitchen cabinet at the base and under the cooktop at the
base observed, this is conducive to lost items falling into this area with no easy means
of retrieval. Recommend evaluation/correction by the builder. (Pictures shown as
examples of concern)
![]() 6.6 Item 1(Picture)
![]() 6.6 Item 2(Picture)
|
6.8 | Dryer Vent | |
Inspected, Repair or Replace | ||
Length of dryer vent/piping observed not marked on dryer vent housing. It is important
to verify with the manufacturer of dryer being installed for proper length of venting to
avoid voiding any warranties. Recommend correction by the builder.
![]() 6.8 Item 1(Picture)
|
7.1 | Walls | |
Inspected, Repair or Replace | ||
Exterior walls at the rear left of center, front left, front center, right side front and right
side center areas observed with improper attachment for some bolts and ends of sill
plates. Improper attachment of the walls is conducive to potential movement of the
component under certain conditions. Recommend correction by the builder. (Pictures
shown as examples of concern)
![]() 7.1 Item 1(Picture)
![]() 7.1 Item 2(Picture)
![]() 7.1 Item 3(Picture)
![]() 7.1 Item 4(Picture)
![]() 7.1 Item 5(Picture)
|
7.4 | Railings | |
Inspected, Repair or Replace | ||
Railing for the stairs to the upper level observed loose at the bottom and center of
stairs, this is a safety concern for potential personal injury due to loss of balance.
Recommend evaluation/correction by the builder.
![]() 7.4 Item 1(Picture)
|
7.5 | Windows | |
Inspected, Repair or Replace | ||
(2) Broken/damaged window pane observed in the upper level bonus room front wall top
sash, this is a potential safety concern and the window not functioning as intended for
R-Value. Recommend evaluation/correction by the builder.
![]() 7.5 Item 2(Picture)
|
7.6 | Doors | |
Inspected, Repair or Replace | ||
(1) Door for the upper level jack n jill wet room entry and upper level walk-in attic entry
observed with missing latching/knob mechanism. This does not allow the door to
function as intended. Recommend correction by the builder.
![]() 7.6 Item 1(Picture)
![]() 7.6 Item 2(Picture)
|
||
(2) Upper level hallway closet entry top of door ball mechanism observed not engaging, this
is conducive to the door not able to function/close or latch as originally intended.
Recommend correction by the builder.
![]() 7.6 Item 3(Picture)
|
7.7 | Detector Test | |
Inspected, Repair or Replace | ||
Upper level hallway detector observed as a smoke detector only with no carbon
monoxide detection ability. This is a potential safety concern. It is recommended to
today's standard of a smoke detector in each bedroom and a smoke and carbon
monoxide detector in the hallways for safety by the builder.
![]() 7.7 Item 1(Picture)
|
8.2.A | Bathtub | |
Inspected, Repair or Replace | ||
Cracked/missing caulking observed at the tub/surround in various areas, this is
conducive to water intrusion of the substructure. Recommend correction by the builder.
(Pictures shown as examples of concern)
![]() 8.2.A Item 1(Picture)
![]() 8.2.A Item 2(Picture)
|
8.2.B | Bathtub | |
Inspected, Repair or Replace | ||
Cracked/missing caulking observed at the tub/surround in various areas, this is
conducive to water intrusion of the substructure. Recommend correction by the builder.
(Pictures shown as examples of concern)
![]() 8.2.B Item 1(Picture)
![]() 8.2.B Item 2(Picture)
|
8.2.C | Bathtub | |
Inspected, Repair or Replace | ||
Cracked/missing caulking observed at the tub/surround in various areas, this is
conducive to water intrusion of the substructure. Recommend correction by the builder.
(Pictures shown as examples of concern)
![]() 8.2.C Item 1(Picture)
![]() 8.2.C Item 2(Picture)
![]() 8.2.C Item 3(Picture)
|
8.3.C | Stall Shower | |
Inspected, Repair or Replace | ||
(1) Cracked/missing caulking observed at the floor/surround in various areas for shower,
this is conducive to water intrusion of the substructure. Recommend correction by the
builder. (Picture shown as example of concern)
![]() 8.3.C Item 1(Picture)
|
||
(2) Shower observed slow to drain, this is conducive a clogged drain and the component
not functioning as intended. Recommend correction by the builder.
![]() 8.3.C Item 2(Picture)
|
||
(4) Water observed leaking into the crawlspace environment underneath primary bath. This
may indicate an issue with the stall shower pan. Recommend evaluation/correction by
the builder.
![]() 8.3.C Item 4(Picture)
![]() 8.3.C Item 5(Picture)
![]() 8.3.C Item 6(Picture)
|
9.4 | Sub Panel | |
Inspected, Repair or Replace | ||
Only 3 out 6 screws observed installed to hold the panel cover to the panel, this does
not allow the panel to be properly secured as intended. Recommend correction by the
builder.
![]() 9.4 Item 1(Picture)
![]() 9.4 Item 2(Picture)
![]() 9.4 Item 3(Picture)
|
9.6 | Devices | |
Inspected, Repair or Replace | ||
Loose outlets at the wall observed at the primary bathroom storage area, upper level
bonus room rear wall, and upper level left side rear bedroom rear wall right side. This is
conducive to a potential safety concern for damage of the electrical component.
Recommend evaluation/correction by a qualified electrical contractor.
![]() 9.6 Item 1(Picture)
![]() 9.6 Item 2(Picture)
![]() 9.6 Item 3(Picture)
|
10.3 | Condensate Provisions | |
Inspected, Repair or Replace | ||
No secondary condensate provision observed for the air handler in the crawlspace.
This is conducive to the potential of condensation collecting in the unit if primary
condensate should fail. Recommend placement of secondary condensate provision by
the builder.
![]() 10.3 Item 1(Picture)
|
10.4 | Distribution System | |
Inspected, Repair or Replace | ||
(1) Damaged insulation for the HVAC system observed in the rear center area of the attic,
this is conducive to affecting the original/proper performance of the HVAC system.
Recommend evaluation/correction by the builder. (Pictures shown as examples of
concern)
![]() 10.4 Item 1(Picture)
![]() 10.4 Item 2(Picture)
|
||
(2) Return ductwork observed not properly sealed to side of air handler in attic and at
plenum for return ductwork at front side of furnace in crawlspace. This is conducive to
potential circulation of unfiltered attic and crawlspace air into the dwelling. Recommend
correction by the builder. (Pictures shown as examples of concern)
![]() 10.4 Item 3(Picture)
![]() 10.4 Item 4(Picture)
![]() 10.4 Item 5(Picture)
![]() 10.4 Item 6(Picture)
![]() 10.4 Item 7(Picture)
|
11.3 | Vent Connector | |
Inspected, Repair or Replace | ||
Vent connector for the crawlspace unit on the right side of dwelling observed sloped
upward with no shroud at the exterior. This is conducive to pest/water intrusion of the
duct. Recommend correction by the builder.
![]() 11.3 Item 1(Picture)
![]() 11.3 Item 2(Picture)
|
15.0 | Crawlspace | |
Inspected, Repair or Replace | ||
(2) Wood to soil contact observed for added support to substructure in the right side area
of the substructure. This is conducive to potential attraction of wood destroying insects.
Recommend evaluation/correction by the builder.
![]() 15.0 Item 5(Picture)
|
![]() |
INVOICE |
Galop Home Concepts
P.O. Box 5087 Clover, SC 29710 704-718-0043 Inspected By: John Galop |
Inspection Date: 3/30/2022
Report ID: 2203JG3953TitovetsCOPY |
Customer Info: | Inspection Property: |
New Homeowner
Customer's Real Estate Professional: Helen Harp Keller Williams Realty |
760 In Your Neighborhood Rd. York SC 29745 |
| ||||||||||||
Tax $0.00 | ||||||||||||
Total Price $570.00 |
Payment Method:
Payment Status: Awaiting Payment
Note: Uploaded Prior to Payment
![]() Galop Home Concepts P.O. Box 5087 |
ATTENTION: This inspection report is incomplete without reading the information included herein at these links/attachments. Note If you received a printed version of this page and did not receive a copy of the report through the internet please contact your inspector for a printed copy of the attachments.
INSPECTION AGREEMENT
THIS IS A LEGALLY BINDING CONTRACT PLEASE READ IT CAREFULLY |
Address of
Structure to be Inspected:
|
760 In Your Neighborhood Rd. York SC 29745 |
Inspection
Fee:
|
$ 570.00 |