INSPECTION REPORT
123 Sample Street
AnyTown NC 00000
|
INSPECTED BY Larry D Young HomeTek Inspection Services, LLC NCHIL #4032 |
INSPECTION DATE
![]() ![]() |
INSPECTION REPORT
123 Sample Street
AnyTown NC 00000
|
INSPECTED BY Larry D Young HomeTek Inspection Services, LLC NCHIL #4032 |
INSPECTION DATE
![]() ![]() |
Date: 6/1/2022 | Time: 08:00:00 AM | Report ID: 060122DY2 |
Property: 123 Sample Street AnyTown NC 00000 |
Customer: Sample Buyer |
Real Estate Professional: |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed and/ or operated the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect or operate this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit was inspected and found not to be functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
What is DDID?
DDID is an acronym for Describe, Determine, Implication, and Direction. This is the framework for wording used to indicate defects within a home inspection report. DDID is prescribed by the standards of practice of the North Carolina Home Inspector Licensure Board. Home inspectors are required to use this wording style to demonstrate defects within the report.
General Inspection Limitations
Weather Conditions: Systems and components of the home can perform and or appear different depending on weather conditions. The inspector assumes no responsibility for unknown defects which appeared functional at the time of inspection and are only discovered under different and or abnormal weather conditions.
Construction Regulations: Building codes and construction standards vary regionally. A home inspection does not include evaluation of a property for compliance with building or health codes. Existing structures generally do not meet current code standards, nor is such compliance usually required.
Home Maintenance: All homes require routine maintenance to maximize the economic life spans of elements and to minimize unanticipated repair or replacement needs. Every homeowner should develop a preventative maintenance program and budget for normal maintenance and unexpected repairs.
Environmental and Mold Issues: A home inspection does not include the detection, identification or analysis of any such element or related concerns such as, but not limited to, mold, allergens, radon, formaldehyde, asbestos, lead, electromagnetic fields, carbon monoxide, insecticides, refrigerants, and fuel oils. An environmental health specialist should be contacted for evaluation of any potential health or environmental concerns. When wood framing/ interior components have surface discolorations and or decay typical of fungal growths such as mold, mildew, and wood destroying fungi, the home inspector is concerned with the moisture concerns and evidence of wood damage; however, health related issues concerning mold are beyond the scope of the home inspection. If the buyer has additional concerns related to the presence of the fungal growths such as mold an industrial hygienist should be consulted.
Aesthetic Condition: A home inspection does not include cosmetic issues such as appearance, surface flaws, finishes, furnishings, paint chipping, dented door knobs, torn screens or other conditions of normal wear and tear.
Descriptions: Any description of material, type, design size, dimensions etc., are based primarily on visual observation of inspected or representative components. However there is no guarantee of the accuracy of any material or product descriptions listed in this report; other or additional materials may be present.
Pictures in Report: Any pictures included in or otherwise provided in conjunction with this Inspection Report generally portray overviews. These pictures do not necessarily reflect all conditions or issues that may need attention or be of concern. Furthermore, the lack of a picture for any element or condition also does not change the significance or severity of any defect or condition described in the Inspection Report.
Seller Disclosure: This report is not a substitute for a Seller Disclosure. The buyer(s) should review this form with the seller(s) prior to closing for clarification or resolution of any questionable items. A final buyer inspection (walk through) should be done prior to closing.
Inspection Notice: Home inspectors are not required to report on the following: Life expectancy of any component or system. The causes of the need for a repair. The methods, materials, and cost of corrections. Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions. The presence or absence or rodents, insects, cosmetic items, underground items, or items not permanently installed. Furthermore, home inspectors are not required to offer warranties or guarantees of any kind. Calculate the strength, adequacy, or efficiency of any system or component. Operate any system or component that is shut down or does not respond to normal operating controls. Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility.
The General Home Inspection is based on the Standards of Practice (SOPs) followed by the Inspector. The SOPs are minimum guidelines that determine what an inspector must and need not inspect and report on. The Inspector is free to exceed these guidelines at his discretion, however, comments on systems, components, or conditions that exceed the scope of the General Home Inspection are not meant to imply that the scope of the inspection is expanded to include all systems, components, or conditions, the inspection of which lies beyond the scope of the General Home Inspection. Additional defects that lie beyond the scope of the General Home Inspection may exist in the home and may not be identified by the Inspector.
Final Walk-Thru: The final walk-thru is the clients responsibility. Any deficiency noted during the final walk-thru should be brought to the sellers attention and corrected prior to the close of escrow.
Other Information: The inspection is a representation of the home at the date and time of the inspection only. The inspection is for the original customer listed on the report and not valid to any other party. It is strongly recommended that you (the buyer) have the appropriate licensed contractors evaluate each concern and or the entire system(s) for additional repairs or concerns. Please Note: The point of reference for this report is from the street looking at the front of the house
PLEASE READ FULL REPORT. DO NOT RELY ON PICTURES. PICTURES ARE A COURTESY AND USED AS EXAMPLES ONLY.
In Attendance: Inspector | Access: Vacant | Ground/Soil Surface Condition: Dry |
Precipitation in last 2 days: No | Services: Pre-purchase, Termite, Air Quality Test | Standards of Practice: North Carolina Home Inspector Licensure Board |
Weather: Partly Sunny | Temperature: Estimated temperature at arrival 72, Estimated temperature at departure 79 | Type of Building: Single Family |
96
Items Inspected
Total number in report.
71
Summary Comments
Total number in report.
136
Photos
Total number in report.
1.0 |
FOOD WASTE DISPOSER
Comments: |
![]() |
The disposal at the kitchen sink is making a buzzing/humming noise. Not doing job as intended. This may suggest that the disposal is
jammed and or damaged. A plumbing contractor is recommended to evaluate and make all needed repairs.
![]() 1.0 Item 1(Picture) |
1.1 |
DISHWASHER
Comments: |
1.2 |
RANGE HOOD
Comments: |
![]() |
The hood vent is loose or not properly installed. Further movement and damage may occur. A qualified contractor is recommended to
repair.
![]() 1.2 Item 1(Picture) ![]() 1.2 Item 2(Picture) ![]() 1.2 Item 3(Picture) |
1.3 |
MICROWAVE COOKING EQUIPMENT
Comments: |
1.4 |
RANGE-OVEN-COOKTOP
Comments: |
2.0 |
CEILINGS
Comments: |
![]() |
(1) Cracks are present at the ceiling at dining room at living room. Cracks appear to be following tape seam at drywall. No adverse
conditions noted at time of inspection. Recommend subsequent observation and all needed repairs to restore to original condition.
![]() 2.0 Item 1(Picture) ![]() 2.0 Item 2(Picture) |
![]() |
(2) Moisture stains located at the ceiling at primary bedroom. No high moisture readings at time of inspection. This could suggest an old
leak stain or intermittent leaks. Further staining and abnormal moisture concern. Hidden damage may be present. A qualified
contractor is recommended to evaluate and make all needed repairs.
![]() 2.0 Item 3(Picture) ![]() 2.0 Item 4(Picture) |
![]() |
(3) Ceiling(s) damaged at primary bathroom. Deterioration and further damage may occur. Hidden damage may be present. A qualified
contractor is recommended to evaluate and make all needed repairs.
![]() 2.0 Item 5(Picture) |
2.1 |
WALLS
Comments: |
![]() |
(1) There are holes present in the ceramic tile at upstairs hall bathroom combo tub/shower. Further deterioration may occur. Moisture
entry concerns, there may be hidden damage. A qualified contractor is recommended to evaluate and make all needed repairs.
![]() 2.1 Item 1(Picture) ![]() 2.1 Item 2(Picture) |
![]() |
(2) Fungi growth is located at the wall at primary bedroom closet and foyer closet. This may suggest prior or intermittent abnormal
moisture concern. Testing and evaluation is recommended by a qualified contractor.
![]() 2.1 Item 3(Picture) ![]() 2.1 Item 4(Picture) |
![]() |
(3) Moisture stains located at the wall in the primary bedroom. No high moisture readings at time of inspection. This could suggest an old
leak stain or intermittent leaks. Further staining may occur. Hidden damage may be present. A qualified contractor is recommended to
evaluate and make all needed repairs.
![]() 2.1 Item 5(Picture) |
![]() |
(4) Crack(s) located at the wall(s) at primary bedroom and primary bathroom. This may suggest movement of the wall structure. It can not
be determined as part of a home inspection if movement has stabilized or will continue. Further cracking/ damage may occur. A
qualified contractor is recommended to evaluate and make all needed repairs.
![]() 2.1 Item 6(Picture) ![]() 2.1 Item 7(Picture) |
2.2 |
DOORS (REPRESENTATIVE NUMBER)
Comments: |
![]() |
Door(s) will not latch properly at upstairs hall bathroom and primary bathroom. Not doing job as intended. Door(s) not securing
properly. A qualified contractor is recommended to evaluate and make all needed repairs.
![]() 2.2 Item 1(Picture) |
2.3 |
WINDOWS (REPRESENTATIVE NUMBER)
Comments: |
![]() |
(1) The window latch will not secure located at kitchen. Not functioning as intended. This is a safety concern. A qualified contractor should
evaluate and make all needed repairs.
![]() 2.3 Item 1(Picture) |
![]() |
(2) Window(s) are difficult to operate when opening and or closing at areas of the residence. Not functioning as intended. A qualified
contractor is recommended to evaluate and make all needed repairs.
![]() 2.3 Item 2(Picture) ![]() 2.3 Item 3(Picture) |
![]() |
(3) Window(s) will not open at basement. Not functioning as intended. Safety concern. A qualified contractor is recommended to evaluate
and make all needed repairs.
![]() 2.3 Item 4(Picture) |
2.4 |
FLOORS
Comments: |
![]() |
(1) Damaged laminate flooring at areas of the kitchen. Further deterioration may occur. A qualified contractor is recommended to evaluate
and repair or replace.
![]() 2.4 Item 1(Picture) ![]() 2.4 Item 2(Picture) |
![]() |
(2) Flooring transition damaged and or missing at kitchen at living room. Further deterioration may occur. A qualified contractor is
recommended to repair or replace.
![]() 2.4 Item 3(Picture) |
![]() |
(3) Abnormal transition(s) between floors at upstairs hall bathroom. Trip hazard. Use caution in these areas and or further
evaluation/repair by qualified contractor is warranted.
![]() 2.4 Item 4(Picture) |
![]() |
(4) Loose carpeting is present in upstairs left front bedroom and other areas of the residence. Possible trip hazard and further
deterioration may occur. Use caution in this area or further evaluation/ repair by a qualified contractor as desired by the client.
![]() 2.4 Item 5(Picture) ![]() 2.4 Item 6(Picture) ![]() 2.4 Item 7(Picture) |
2.5 |
STEPS, STAIRWAYS, BALCONIES AND RAILINGS
Comments: |
![]() |
The interior staircase railing is not closed off to the wall. Safety concern. Items may become caught on railing and create a fall hazard.
Use caution in these areas and or further evaluation/repair by qualified contractor as desired by client.
![]() 2.5 Item 1(Picture) ![]() 2.5 Item 2(Picture) ![]() 2.5 Item 3(Picture) |
2.6 |
COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS
Comments: |
![]() |
Cabinet door(s) will not shut properly at kitchen under sink. Not functioning as intended. A qualified contractor is recommended to
repair.
![]() 2.6 Item 1(Picture) |
2.7 |
INTERIOR COLUMNS
Comments: |
2.8 |
OTHER
Comments: |
![]() |
Sealant requires regular maintenance at areas of interior components such as countertops, showers, tubs, back-splash, woodwork,
and windows. Energy loss and moisture entry may occur. A qualified contractor is recommend to properly seal as needed.
![]() 2.8 Item 1(Picture) |
3.0 |
PLUMBING WATER SUPPLY, DISTRIBUTION SYSTEMS, FIXTURES, AND FUNCTIONAL FLOW
Comments: |
![]() |
(1) The faucet fixture is loose at kitchen sink. Movement and improper operation concern. Leaks may develop. Plumbing contractor is
recommended to evaluate and make all needed repairs.
![]() 3.0 Item 1(Picture) |
![]() |
(2) Toilet(s) loose at floor at upstairs hall bath and primary bathroom. Repairs may involve re-setting the toilet on a new wax seal. Leaking
and further deterioration may occur. There could be hidden damage. A qualified plumbing contractor should evaluate and make all
needed repairs.
![]() 3.0 Item 2(Picture) ![]() 3.0 Item 3(Picture) |
![]() |
(3) Plumbing fixture is loose behind the wall at upstairs hallway combo tub/shower and at the primary shower. Movement and improper
operation concern. Leaks may develop. Plumbing contractor is recommended to evaluate and make all needed repairs.
![]() 3.0 Item 4(Picture) ![]() 3.0 Item 5(Picture) |
![]() |
(4) Toilet(s) not functioning at upstairs hall bath. Not working as intended. A plumbing contractor is recommended to evaluate and make
all needed repairs.
![]() 3.0 Item 6(Picture) |
(5) There is no sink drain overflow located at the areas of the residence. Flooding may occur if left unattended. A plumbing contractor is
recommended to make all needed repairs or upgrades as desired by client.
![]() 3.0 Item 7(Picture) ![]() 3.0 Item 8(Picture) |
|
![]() |
(6) No backflow protection at hose faucet at the front and rear . Cross contamination concern. A qualified person is recommended to add
a backflow preventing device.
![]() 3.0 Item 9(Picture) ![]() 3.0 Item 10(Picture) |
![]() |
(7) The hose faucet is loose located at the front and rear . Improper operation concern. Damage to plumbing lines may occur. A qualified
contractor should evaluate and make all needed repairs.
![]() 3.0 Item 11(Picture) |
3.1 |
PLUMBING DRAIN, WASTE AND VENT SYSTEMS
Comments: |
3.2 |
HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS, VALVES
Comments: |
![]() |
Water heater(s) appear to be aged. While the water heater is still functional, it could fail at any time. Recommend budgeting for
maintenance, repairs, and eventual replacement.
![]() 3.2 Item 1(Picture) |
3.3 |
FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks)
Comments: |
3.4 |
SUMP PUMP
Comments: |
4.0 |
CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat systems)
Comments: |
4.1 |
NORMAL OPERATING CONTROLS
Comments: |
4.2 |
HEATING EQUIPMENT
Comments: |
![]() |
HVAC system(s) are older. While the HVAC is still functional, it could fail at any time. Recommend budgeting for maintenance,
repairs,and eventual replacement.
![]() 4.2 Item 1(Picture) |
4.3 |
COOLING AND AIR HANDLER EQUIPMENT
Comments: |
![]() |
HVAC system(s) and or Heat Pump(s) are older. While the HVAC/Heat Pump is still functional, it could fail at any time. Recommend
budgeting for maintenance, repairs,and eventual replacement.
![]() 4.3 Item 1(Picture) |
4.4 |
AUTOMATIC SAFETY CONTROLS
Comments: |
4.5 |
PRESENCE OF INSTALLED HEATING/COOLING SOURCE IN EACH ROOM
Comments: |
4.6 |
DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)
Comments: |
![]() |
(1) Ducts were visibly dirty at the time of inspection. Improper operation may occur. A qualified contractor is recommended to evaluate
and make all needed repairs.
![]() 4.6 Item 1(Picture) |
![]() |
(2) There are moisture stains located at the HVAC duct registers at areas of the residence. This may suggest abnormal
moisture/condensation concern. A qualified contractor is recommended to evaluate and make all needed repairs.
![]() 4.6 Item 2(Picture) |
![]() |
(3) Ductwork is aged. May be reaching the end of it's useful life. Repairs/replacement may be needed in the future. Recommend subsequent observations.
|
![]() |
(4) Damaged HVAC ducts located at crawl space. Insulation wrap is missing/damaged. Not doing job as intended. In need of
evaluation/repair by mechanical contractor.
![]() 4.6 Item 3(Picture) |
4.7 |
SOLID FUEL HEATING DEVICES (Fireplaces, Woodstove)
Comments: |
![]() |
The fireplace/ chimney should be inspected by a qualified chimney sweep prior to use. This is for your information.
![]() 4.7 Item 1(Picture) |
4.8 |
GAS/LP FIRELOGS AND FIREPLACES
Comments: |
5.0 |
SERVICE ENTRANCE CONDUCTORS
Comments: |
5.1 |
SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS
Comments: |
![]() |
(1) Breakers have been altered at the distribution panel. This is considered a safety hazard. Electrical contractor should be contacted to
identify and label breakers/fuses properly.
![]() 5.1 Item 1(Picture) |
![]() |
(2) Protective grommets are missing where wiring enters the distribution panel. Damage may result causing a safety hazard. An electrical
contractor is recommended to evaluate and make all needed repairs.
![]() 5.1 Item 2(Picture) ![]() 5.1 Item 3(Picture) |
5.2 |
BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE
Comments: |
![]() |
The electrical system of this home has single strand aluminum wiring present on the lighting and receptacle branch circuits. As a
result of documented fire hazards, the use of single strand aluminum wiring for lighting and receptacle branch circuits was discontinued
in 1974 until material improvement could be made. Due to the concealed nature of the electrical components, the general condition of
the system could not be determined during the home inspection. A licensed electrical contractor should be consulted for a complete
evaluation of the electrical system to determine if repair, modification, or replacement is needed to ensure safe and reliable service.
For more information on aluminum household wiring and recommended repair methods, refer to the C.P.S.C. booklet "Repairing
Aluminum Wiring." The toll-free hotline number for obtaining this booklet is 1-800-638-2772, or you can visit:
https://www.cpsc.gov/s3fs-public/516.pdf
![]() 5.2 Item 1(Picture) ![]() 5.2 Item 2(Picture) ![]() 5.2 Item 3(Picture) ![]() 5.2 Item 4(Picture) |
5.3 |
CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)
Comments: |
![]() |
(1) Light bulb(s) are missing and or nonfunctional at dining room. This may suggest abnormal operation of the light bulbs or a more
involved repair. An electrical contractor is recommended to evaluate and make all needed repairs.
![]() 5.3 Item 1(Picture) ![]() 5.3 Item 2(Picture) |
![]() |
(2) The receptacle prongs are worn at the areas of the residence Not properly holding tester when inserted. Further deterioration make
occur. Electrical issues are considered a hazard until evaluated and repaired by a qualified electrical contractor.
![]() 5.3 Item 3(Picture) |
![]() |
(3) Receptacle(s) were improperly secured and moved when plug tester was inserted at areas of the residence. Receptacles should be
securely installed to prevent fire, shock hazard. Loose outlets should be made secure by a qualified electrical contractor.
![]() 5.3 Item 4(Picture) |
![]() |
(4)
Switch(s) loose at primary bedroom. Potential hazard. Further movement may occur. An electrical contractor is recommended to
evaluate and repair.
![]() 5.3 Item 5(Picture) |
![]() |
(5) Electrical cover plate(s) missing at primary bedroom. Energized components pose a shock hazard. Safety hazard. The inspector
recommends a cover plate be installed by a qualified contractor.
![]() 5.3 Item 6(Picture) |
5.4 |
OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)
Comments: |
![]() |
There is no GFCI outlet protection located at kitchen. Improper by today's methods. Safety concern. An electrical contractor is
recommended to evaluate and make all needed repairs.
![]() 5.4 Item 1(Picture) ![]() 5.4 Item 2(Picture) |
5.5 |
POLARITY AND GROUNDING OF RECEPTACLES AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE
Comments: |
![]() |
Hot neutral reversed outlet(s) are located at left front bedroom. Improper install method. Electrical issues are considered a hazard until
repaired. Recommend a licensed electrician to repair.
![]() 5.5 Item 1(Picture) ![]() 5.5 Item 2(Picture) ![]() 5.5 Item 3(Picture) |
5.6 |
SMOKE ALARM
Comments: |
![]() |
The number of smoke alarms in the residence is improper. Safety hazard. Recommend installing additional smoke alarms in the home
to improve safety.
![]() 5.6 Item 1(Picture) ![]() 5.6 Item 2(Picture) |
5.7 |
CARBON MONOXIDE ALARM
Comments: |
![]() |
No carbon monoxide detector was found in the home. It is recommended that one be installed when gas appliances, solid fuel sources
and an attached garage are present in and around the home. A qualified contractor is recommended to evaluate and make all needed
repairs.
![]() 5.7 Item 1(Picture) ![]() 5.7 Item 2(Picture) |
7.0 |
EAVES, SOFFITS AND FASCIAS
Comments: |
7.1 |
WALL CLADDING FLASHING AND TRIM
Comments: |
7.2 |
EXTERIOR WINDOWS
Comments: |
7.3 |
EXTERIOR DOORS
Comments: |
![]() |
Daylight is visible at the storm door(s) located at front . Energy loss may occur. A qualified contractor is recommended to repair.
![]() 7.3 Item 1(Picture) |
7.4 |
EXTERIOR COLUMNS
Comments: |
![]() |
There is corrosion/moisture damage located at the exterior columns. Further damage may occur. A qualified contractor is
recommended to evaluate and make all needed repairs.
![]() 7.4 Item 1(Picture) ![]() 7.4 Item 2(Picture) |
7.5 |
DECK-BALCONY-STOOP-STEPS-AREAWAY-PORCH-PATIO
Comments: |
![]() |
Mortar needs pointing in areas between the bricks at the front steps. Further deterioration is likely. A qualified contractor is
recommended to repair.
![]() 7.5 Item 1(Picture) ![]() 7.5 Item 2(Picture) ![]() 7.5 Item 3(Picture) |
7.6 |
DRIVEWAY-PATIO-WALKWAYS-RETAINING WALL
Comments: |
![]() |
(1) Walkway appears to have settled and or shifted at various locations. Further movement may occur. This condition is a trip hazard. A
qualified contractor is recommended to evaluate and make all needed repairs.
![]() 7.6 Item 1(Picture) ![]() 7.6 Item 2(Picture) ![]() 7.6 Item 3(Picture) |
![]() |
(2) Driveway is damaged. Further damage may occur during freezing and moisture saturation. Damage appears to be from root system.
Recommend repair by a qualified contractor.
![]() 7.6 Item 4(Picture) |
7.7 |
VEGETATION-GRADING-DRAINAGE (Only with respect to their effect on the condition of the building)
Comments: |
![]() |
Trees near the house have limbs that overhang the home. Falling limbs due to conditions such as wood decay, high winds or heavy
snow loads may cause injury, death or damage. Significant weakening of large limbs by conditions such as core decay may not be
visible by persons without special training. Consider having these trees evaluated by a qualified arborist. Evaluating trees lies beyond
the scope of the general Home Inspection.
![]() 7.7 Item 1(Picture) ![]() 7.7 Item 2(Picture) |
8.0 |
CHIMNEYS-ROOF PENETRATIONS-SKYLIGHTS-VENTS
Comments: |
8.1 |
ROOF COVERINGS
Comments: |
![]() |
(1) Raised shingles at the roof at areas. Further movement and improper operation may occur. Roofing contractor should evaluate and
make all needed repairs.
![]() 8.1 Item 1(Picture) ![]() 8.1 Item 2(Picture) |
![]() |
(2) The asphalt shingle coverings exhibited weathering at areas. Other portions of the roof were in better condition. This condition can be
due to exposure to prevailing weather patterns, directional exposure to sunlight, or it may be a result of overhanging trees. Further
deterioration may occur and leaks could develop. It is recommended to budget for maintenance and repairs. The Inspector
recommends that before the expiration of your Inspection Objection Deadline you consult with a qualified roofing contractor to discuss
options and costs for any necessary shingle replacement and or repairs.
![]() 8.1 Item 3(Picture) ![]() 8.1 Item 4(Picture) ![]() 8.1 Item 5(Picture) |
8.2 |
FLASHINGS
Comments: |
![]() |
(1) Sealant was used to seal areas that normally would be protected by metal flashing, Unless they are diligently maintained, these areas
will allow roof leakage sooner than if they were properly protected by metal flashing. Sealant will need to be examined annually and re-applied as needed. Flashing is also loose and popping up. Proper flashing should be installed by a qualified roofing contractor at the
first opportunity.
![]() 8.2 Item 1(Picture) |
![]() |
(2) Vent boot(s) popped upward at rear. Further movement may occur and leaks could develop. A qualified contractor is recommended to
repair.
![]() 8.2 Item 2(Picture) ![]() 8.2 Item 3(Picture) |
![]() |
(3) The vent boot(s) are weathered. A weathered vent boot may begin to leak. A roofing contractor is recommended to evaluate and replace as needed.
|
8.3 |
ROOF DRAINAGE SYSTEMS
Comments: |
![]() |
(1) Downspout extensions were not present at areas of the downspouts. Downspouts are discharging adjacent to the foundation. This can
cause foundation settlement or basement moisture intrusion problems. Make sure all downspouts divert rain water at least 5 feet away
from the foundation. Action should be taken to correct this condition. A qualified contractor is recommended to properly install.
![]() 8.3 Item 1(Picture) ![]() 8.3 Item 2(Picture) ![]() 8.3 Item 3(Picture) |
![]() |
(2) Gutter downspout(s) loose at front . Further movement and deterioration may occur. A qualified contractor is recommended to repair.
![]() 8.3 Item 4(Picture) |
9.0 |
VENTILATION FANS - THERMOSTATIC CONTROLS (ATTIC)
Comments: |
![]() |
The thermostatic fan has been removed from the attic. This is an Improper ventilation concern. The lack of ventilation may cause
damage to the roofing system and its components. A qualified contractor should evaluate and make all needed repairs.
![]() 9.0 Item 1(Picture) |
9.1 |
VENTILATION OF ATTIC - FOUNDATION AREAS
Comments: |
![]() |
Foundation vent(s) are at or below ground level at areas which can allow water to enter crawlspace. A half-round vent well should be
installed. The dirt inside well should be replaced with approximately 6-8 inches of gravel. A couple of inches clearance between gravel
and vent opening recommended. Moisture entry concern. A qualified contractor should evaluate and make all needed repairs.
![]() 9.1 Item 1(Picture) ![]() 9.1 Item 2(Picture) ![]() 9.1 Item 3(Picture) |
9.2 |
VENTING SYSTEMS (Kitchens, baths and laundry)
Comments: |
![]() |
(1) Vinyl duct is used for the dryer vent. This duct type is a safety hazard and is improper by today's standards. A qualified contractor is
recommended to replace.
![]() 9.2 Item 1(Picture) |
![]() |
(2) The dryer louver(s) were missing where the dryer duct exits the residence. Pest intrusion and energy loss may occur. A qualified
contractor is recommended to seal.
![]() 9.2 Item 2(Picture) |
9.3 |
INSULATION IN ATTIC
Comments: |
![]() |
(1) Installing additional insulation to bring ceiling insulation levels in the home current with modern recommendations will help save on
heating and cooling costs. The modern recommended value for ceilings is R-38. A insulation contractor should evaluate and make all
necessary adjustments.
![]() 9.3 Item 1(Picture) |
![]() |
(2) Joist are exposed in the attic due to compressed or settled insulation. Energy loss and thermal bridging concern. A qualified contractor
is recommended to evaluate and properly insulate.
![]() 9.3 Item 2(Picture) |
9.4 |
INSULATION UNDER FLOOR SYSTEM
Comments: |
9.5 |
VAPOR RETARDERS (ON GROUND IN CRAWL SPACE OR BASEMENT)
Comments: |
![]() |
No vapor barrier was installed at the time of the inspection. A vapor barrier will help reduce elevated moisture levels in crawl spaces by
limiting moisture evaporation into the air from soil. Reducing humidity levels can help prevent conditions that encourage mold growth
and wood decay. A qualified contractor is recommended to install
![]() 9.5 Item 1(Picture) ![]() 9.5 Item 2(Picture) |
10.0 |
ROOF STRUCTURE AND ATTIC
Comments: |
![]() |
(1) The attic access door does not shut flush. This will allow energy loss. Not making proper seal. A qualified contractor is recommended
to evaluate and make all needed repairs.
![]() 10.0 Item 1(Picture) |
![]() |
(2) Attic pull down stairs have missing and or loose hardware. Not functioning as intended. Further damage may occur. Safety hazard. A
qualified contractor is recommended to evaluate and properly repair.
![]() 10.0 Item 2(Picture) ![]() 10.0 Item 3(Picture) |
![]() |
(3) Moisture stain(s) located at the attic roof structure components at areas. Unable to take moisture readings due to location.
Recommend further evaluation by a roofing contractor for any needed repairs.
![]() 10.0 Item 4(Picture) ![]() 10.0 Item 5(Picture) ![]() 10.0 Item 6(Picture) |
10.1 |
WALLS (Structural) Unfinished
Comments: |
10.2 |
FLOORS (Structural) Unfinished
Comments: |
10.3 |
COLUMNS - PIERS
Comments: |
10.4 |
FOUNDATIONS - BASEMENTS - CRAWL SPACES
Comments: |
![]() |
(1) There are moisture stains on the foundation wall. Moisture intrusion can lead to fungal growth, cracking, shifting and foundation issues.
A qualified waterproofing contractor should evaluate further, and make recommendations how to resolve reoccurring moisture entry
concerns.
![]() 10.4 Item 1(Picture) |
![]() |
(2) Efflorescence (powder substance) on foundation wall indicates moisture is in contact with the masonry. This may suggest present/past
abnormal moisture entry at masonry wall. Further moisture entry/staining may occur. Proper professional should evaluate for cause
and make any needed repairs.
![]() 10.4 Item 2(Picture) ![]() 10.4 Item 3(Picture) |
13.0 |
Check List Items
Comments: |
(1) All lights were turned off following the inspection
|
|
(2) All thermostats were reset to original setting following the inspection
|
|
(3) All doors were locked following the inspection
|
806 Green Valley Road, Suite 200
Greensboro, NC 27408
336-989-8185
Customer
Sample Buyer
Address
123 Sample Street
AnyTown NC 00000
1.0 | FOOD WASTE DISPOSER | |
Repair or Replace | ||
![]() |
The disposal at the kitchen sink is making a buzzing/humming noise. Not doing job as intended. This may suggest that the disposal is
jammed and or damaged. A plumbing contractor is recommended to evaluate and make all needed repairs.
|
1.2 | RANGE HOOD | |
Repair or Replace | ||
![]() |
The hood vent is loose or not properly installed. Further movement and damage may occur. A qualified contractor is recommended to
repair.
|
2.0 | CEILINGS | |
Repair or Replace | ||
![]() |
(1) Cracks are present at the ceiling at dining room at living room. Cracks appear to be following tape seam at drywall. No adverse
conditions noted at time of inspection. Recommend subsequent observation and all needed repairs to restore to original condition.
|
|
![]() |
(2) Moisture stains located at the ceiling at primary bedroom. No high moisture readings at time of inspection. This could suggest an old
leak stain or intermittent leaks. Further staining and abnormal moisture concern. Hidden damage may be present. A qualified
contractor is recommended to evaluate and make all needed repairs.
|
|
![]() |
(3) Ceiling(s) damaged at primary bathroom. Deterioration and further damage may occur. Hidden damage may be present. A qualified
contractor is recommended to evaluate and make all needed repairs.
|
2.1 | WALLS | |
Repair or Replace | ||
![]() |
(1) There are holes present in the ceramic tile at upstairs hall bathroom combo tub/shower. Further deterioration may occur. Moisture
entry concerns, there may be hidden damage. A qualified contractor is recommended to evaluate and make all needed repairs.
|
|
![]() |
(2) Fungi growth is located at the wall at primary bedroom closet and foyer closet. This may suggest prior or intermittent abnormal
moisture concern. Testing and evaluation is recommended by a qualified contractor.
|
|
![]() |
(3) Moisture stains located at the wall in the primary bedroom. No high moisture readings at time of inspection. This could suggest an old
leak stain or intermittent leaks. Further staining may occur. Hidden damage may be present. A qualified contractor is recommended to
evaluate and make all needed repairs.
|
|
![]() |
(4) Crack(s) located at the wall(s) at primary bedroom and primary bathroom. This may suggest movement of the wall structure. It can not
be determined as part of a home inspection if movement has stabilized or will continue. Further cracking/ damage may occur. A
qualified contractor is recommended to evaluate and make all needed repairs.
|
2.2 | DOORS (REPRESENTATIVE NUMBER) | |
Repair or Replace | ||
![]() |
Door(s) will not latch properly at upstairs hall bathroom and primary bathroom. Not doing job as intended. Door(s) not securing
properly. A qualified contractor is recommended to evaluate and make all needed repairs.
|
2.3 | WINDOWS (REPRESENTATIVE NUMBER) | |
Repair or Replace | ||
![]() |
(1) The window latch will not secure located at kitchen. Not functioning as intended. This is a safety concern. A qualified contractor should
evaluate and make all needed repairs.
|
|
![]() |
(2) Window(s) are difficult to operate when opening and or closing at areas of the residence. Not functioning as intended. A qualified
contractor is recommended to evaluate and make all needed repairs.
|
|
![]() |
(3) Window(s) will not open at basement. Not functioning as intended. Safety concern. A qualified contractor is recommended to evaluate
and make all needed repairs.
|
2.4 | FLOORS | |
Repair or Replace | ||
![]() |
(1) Damaged laminate flooring at areas of the kitchen. Further deterioration may occur. A qualified contractor is recommended to evaluate
and repair or replace.
|
|
![]() |
(2) Flooring transition damaged and or missing at kitchen at living room. Further deterioration may occur. A qualified contractor is
recommended to repair or replace.
|
|
![]() |
(3) Abnormal transition(s) between floors at upstairs hall bathroom. Trip hazard. Use caution in these areas and or further
evaluation/repair by qualified contractor is warranted.
|
|
![]() |
(4) Loose carpeting is present in upstairs left front bedroom and other areas of the residence. Possible trip hazard and further
deterioration may occur. Use caution in this area or further evaluation/ repair by a qualified contractor as desired by the client.
|
2.5 | STEPS, STAIRWAYS, BALCONIES AND RAILINGS | |
Repair or Replace | ||
![]() |
The interior staircase railing is not closed off to the wall. Safety concern. Items may become caught on railing and create a fall hazard.
Use caution in these areas and or further evaluation/repair by qualified contractor as desired by client.
|
2.6 | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS | |
Repair or Replace | ||
![]() |
Cabinet door(s) will not shut properly at kitchen under sink. Not functioning as intended. A qualified contractor is recommended to
repair.
|
2.8 | OTHER | |
Repair or Replace | ||
![]() |
Sealant requires regular maintenance at areas of interior components such as countertops, showers, tubs, back-splash, woodwork,
and windows. Energy loss and moisture entry may occur. A qualified contractor is recommend to properly seal as needed.
|
3.0 | PLUMBING WATER SUPPLY, DISTRIBUTION SYSTEMS, FIXTURES, AND FUNCTIONAL FLOW | |
Repair or Replace | ||
![]() |
(1) The faucet fixture is loose at kitchen sink. Movement and improper operation concern. Leaks may develop. Plumbing contractor is
recommended to evaluate and make all needed repairs.
|
|
![]() |
(2) Toilet(s) loose at floor at upstairs hall bath and primary bathroom. Repairs may involve re-setting the toilet on a new wax seal. Leaking
and further deterioration may occur. There could be hidden damage. A qualified plumbing contractor should evaluate and make all
needed repairs.
|
|
![]() |
(3) Plumbing fixture is loose behind the wall at upstairs hallway combo tub/shower and at the primary shower. Movement and improper
operation concern. Leaks may develop. Plumbing contractor is recommended to evaluate and make all needed repairs.
|
|
![]() |
(4) Toilet(s) not functioning at upstairs hall bath. Not working as intended. A plumbing contractor is recommended to evaluate and make
all needed repairs.
|
|
![]() |
(6) No backflow protection at hose faucet at the front and rear . Cross contamination concern. A qualified person is recommended to add
a backflow preventing device.
|
|
![]() |
(7) The hose faucet is loose located at the front and rear . Improper operation concern. Damage to plumbing lines may occur. A qualified
contractor should evaluate and make all needed repairs.
|
3.2 | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS, VALVES | |
Repair or Replace | ||
![]() |
Water heater(s) appear to be aged. While the water heater is still functional, it could fail at any time. Recommend budgeting for
maintenance, repairs, and eventual replacement.
|
4.2 | HEATING EQUIPMENT | |
Repair or Replace | ||
![]() |
HVAC system(s) are older. While the HVAC is still functional, it could fail at any time. Recommend budgeting for maintenance,
repairs,and eventual replacement.
|
4.3 | COOLING AND AIR HANDLER EQUIPMENT | |
Repair or Replace | ||
![]() |
HVAC system(s) and or Heat Pump(s) are older. While the HVAC/Heat Pump is still functional, it could fail at any time. Recommend
budgeting for maintenance, repairs,and eventual replacement.
|
4.6 | DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) | |
Repair or Replace | ||
![]() |
(1) Ducts were visibly dirty at the time of inspection. Improper operation may occur. A qualified contractor is recommended to evaluate
and make all needed repairs.
|
|
![]() |
(2) There are moisture stains located at the HVAC duct registers at areas of the residence. This may suggest abnormal
moisture/condensation concern. A qualified contractor is recommended to evaluate and make all needed repairs.
|
|
![]() |
(3) Ductwork is aged. May be reaching the end of it's useful life. Repairs/replacement may be needed in the future. Recommend subsequent observations.
|
|
![]() |
(4) Damaged HVAC ducts located at crawl space. Insulation wrap is missing/damaged. Not doing job as intended. In need of
evaluation/repair by mechanical contractor.
|
4.7 | SOLID FUEL HEATING DEVICES (Fireplaces, Woodstove) | |
Repair or Replace | ||
![]() |
The fireplace/ chimney should be inspected by a qualified chimney sweep prior to use. This is for your information.
|
5.1 | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS | |
Repair or Replace | ||
![]() |
(1) Breakers have been altered at the distribution panel. This is considered a safety hazard. Electrical contractor should be contacted to
identify and label breakers/fuses properly.
|
|
![]() |
(2) Protective grommets are missing where wiring enters the distribution panel. Damage may result causing a safety hazard. An electrical
contractor is recommended to evaluate and make all needed repairs.
|
5.2 | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE | |
Repair or Replace | ||
![]() |
The electrical system of this home has single strand aluminum wiring present on the lighting and receptacle branch circuits. As a
result of documented fire hazards, the use of single strand aluminum wiring for lighting and receptacle branch circuits was discontinued
in 1974 until material improvement could be made. Due to the concealed nature of the electrical components, the general condition of
the system could not be determined during the home inspection. A licensed electrical contractor should be consulted for a complete
evaluation of the electrical system to determine if repair, modification, or replacement is needed to ensure safe and reliable service.
For more information on aluminum household wiring and recommended repair methods, refer to the C.P.S.C. booklet "Repairing
Aluminum Wiring." The toll-free hotline number for obtaining this booklet is 1-800-638-2772, or you can visit:
https://www.cpsc.gov/s3fs-public/516.pdf
|
5.3 | CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) | |
Repair or Replace | ||
![]() |
(1) Light bulb(s) are missing and or nonfunctional at dining room. This may suggest abnormal operation of the light bulbs or a more
involved repair. An electrical contractor is recommended to evaluate and make all needed repairs.
|
|
![]() |
(2) The receptacle prongs are worn at the areas of the residence Not properly holding tester when inserted. Further deterioration make
occur. Electrical issues are considered a hazard until evaluated and repaired by a qualified electrical contractor.
|
|
![]() |
(3) Receptacle(s) were improperly secured and moved when plug tester was inserted at areas of the residence. Receptacles should be
securely installed to prevent fire, shock hazard. Loose outlets should be made secure by a qualified electrical contractor.
|
|
![]() |
(4)
Switch(s) loose at primary bedroom. Potential hazard. Further movement may occur. An electrical contractor is recommended to
evaluate and repair.
|
|
![]() |
(5) Electrical cover plate(s) missing at primary bedroom. Energized components pose a shock hazard. Safety hazard. The inspector
recommends a cover plate be installed by a qualified contractor.
|
5.4 | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) | |
Repair or Replace | ||
![]() |
There is no GFCI outlet protection located at kitchen. Improper by today's methods. Safety concern. An electrical contractor is
recommended to evaluate and make all needed repairs.
|
5.5 | POLARITY AND GROUNDING OF RECEPTACLES AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE | |
Repair or Replace | ||
![]() |
Hot neutral reversed outlet(s) are located at left front bedroom. Improper install method. Electrical issues are considered a hazard until
repaired. Recommend a licensed electrician to repair.
|
5.6 | SMOKE ALARM | |
Repair or Replace | ||
![]() |
The number of smoke alarms in the residence is improper. Safety hazard. Recommend installing additional smoke alarms in the home
to improve safety.
|
5.7 | CARBON MONOXIDE ALARM | |
Repair or Replace | ||
![]() |
No carbon monoxide detector was found in the home. It is recommended that one be installed when gas appliances, solid fuel sources
and an attached garage are present in and around the home. A qualified contractor is recommended to evaluate and make all needed
repairs.
|
7.3 | EXTERIOR DOORS | |
Repair or Replace | ||
![]() |
Daylight is visible at the storm door(s) located at front . Energy loss may occur. A qualified contractor is recommended to repair.
|
7.4 | EXTERIOR COLUMNS | |
Repair or Replace | ||
![]() |
There is corrosion/moisture damage located at the exterior columns. Further damage may occur. A qualified contractor is
recommended to evaluate and make all needed repairs.
|
7.5 | DECK-BALCONY-STOOP-STEPS-AREAWAY-PORCH-PATIO | |
Repair or Replace | ||
![]() |
Mortar needs pointing in areas between the bricks at the front steps. Further deterioration is likely. A qualified contractor is
recommended to repair.
|
7.6 | DRIVEWAY-PATIO-WALKWAYS-RETAINING WALL | |
Repair or Replace | ||
![]() |
(1) Walkway appears to have settled and or shifted at various locations. Further movement may occur. This condition is a trip hazard. A
qualified contractor is recommended to evaluate and make all needed repairs.
|
|
![]() |
(2) Driveway is damaged. Further damage may occur during freezing and moisture saturation. Damage appears to be from root system.
Recommend repair by a qualified contractor.
|
7.7 | VEGETATION-GRADING-DRAINAGE (Only with respect to their effect on the condition of the building) | |
Repair or Replace | ||
![]() |
Trees near the house have limbs that overhang the home. Falling limbs due to conditions such as wood decay, high winds or heavy
snow loads may cause injury, death or damage. Significant weakening of large limbs by conditions such as core decay may not be
visible by persons without special training. Consider having these trees evaluated by a qualified arborist. Evaluating trees lies beyond
the scope of the general Home Inspection.
|
8.1 | ROOF COVERINGS | |
Repair or Replace | ||
![]() |
(1) Raised shingles at the roof at areas. Further movement and improper operation may occur. Roofing contractor should evaluate and
make all needed repairs.
|
|
![]() |
(2) The asphalt shingle coverings exhibited weathering at areas. Other portions of the roof were in better condition. This condition can be
due to exposure to prevailing weather patterns, directional exposure to sunlight, or it may be a result of overhanging trees. Further
deterioration may occur and leaks could develop. It is recommended to budget for maintenance and repairs. The Inspector
recommends that before the expiration of your Inspection Objection Deadline you consult with a qualified roofing contractor to discuss
options and costs for any necessary shingle replacement and or repairs.
|
8.2 | FLASHINGS | |
Repair or Replace | ||
![]() |
(1) Sealant was used to seal areas that normally would be protected by metal flashing, Unless they are diligently maintained, these areas
will allow roof leakage sooner than if they were properly protected by metal flashing. Sealant will need to be examined annually and re-applied as needed. Flashing is also loose and popping up. Proper flashing should be installed by a qualified roofing contractor at the
first opportunity.
|
|
![]() |
(2) Vent boot(s) popped upward at rear. Further movement may occur and leaks could develop. A qualified contractor is recommended to
repair.
|
|
![]() |
(3) The vent boot(s) are weathered. A weathered vent boot may begin to leak. A roofing contractor is recommended to evaluate and replace as needed.
|
8.3 | ROOF DRAINAGE SYSTEMS | |
Repair or Replace | ||
![]() |
(1) Downspout extensions were not present at areas of the downspouts. Downspouts are discharging adjacent to the foundation. This can
cause foundation settlement or basement moisture intrusion problems. Make sure all downspouts divert rain water at least 5 feet away
from the foundation. Action should be taken to correct this condition. A qualified contractor is recommended to properly install.
|
|
![]() |
(2) Gutter downspout(s) loose at front . Further movement and deterioration may occur. A qualified contractor is recommended to repair.
|
9.0 | VENTILATION FANS - THERMOSTATIC CONTROLS (ATTIC) | |
Repair or Replace | ||
![]() |
The thermostatic fan has been removed from the attic. This is an Improper ventilation concern. The lack of ventilation may cause
damage to the roofing system and its components. A qualified contractor should evaluate and make all needed repairs.
|
9.1 | VENTILATION OF ATTIC - FOUNDATION AREAS | |
Repair or Replace | ||
![]() |
Foundation vent(s) are at or below ground level at areas which can allow water to enter crawlspace. A half-round vent well should be
installed. The dirt inside well should be replaced with approximately 6-8 inches of gravel. A couple of inches clearance between gravel
and vent opening recommended. Moisture entry concern. A qualified contractor should evaluate and make all needed repairs.
|
9.2 | VENTING SYSTEMS (Kitchens, baths and laundry) | |
Repair or Replace | ||
![]() |
(1) Vinyl duct is used for the dryer vent. This duct type is a safety hazard and is improper by today's standards. A qualified contractor is
recommended to replace.
|
|
![]() |
(2) The dryer louver(s) were missing where the dryer duct exits the residence. Pest intrusion and energy loss may occur. A qualified
contractor is recommended to seal.
|
9.3 | INSULATION IN ATTIC | |
Repair or Replace | ||
![]() |
(1) Installing additional insulation to bring ceiling insulation levels in the home current with modern recommendations will help save on
heating and cooling costs. The modern recommended value for ceilings is R-38. A insulation contractor should evaluate and make all
necessary adjustments.
|
|
![]() |
(2) Joist are exposed in the attic due to compressed or settled insulation. Energy loss and thermal bridging concern. A qualified contractor
is recommended to evaluate and properly insulate.
|
9.5 | VAPOR RETARDERS (ON GROUND IN CRAWL SPACE OR BASEMENT) | |
Repair or Replace | ||
![]() |
No vapor barrier was installed at the time of the inspection. A vapor barrier will help reduce elevated moisture levels in crawl spaces by
limiting moisture evaporation into the air from soil. Reducing humidity levels can help prevent conditions that encourage mold growth
and wood decay. A qualified contractor is recommended to install
|
10.0 | ROOF STRUCTURE AND ATTIC | |
Repair or Replace | ||
![]() |
(1) The attic access door does not shut flush. This will allow energy loss. Not making proper seal. A qualified contractor is recommended
to evaluate and make all needed repairs.
|
|
![]() |
(2) Attic pull down stairs have missing and or loose hardware. Not functioning as intended. Further damage may occur. Safety hazard. A
qualified contractor is recommended to evaluate and properly repair.
|
|
![]() |
(3) Moisture stain(s) located at the attic roof structure components at areas. Unable to take moisture readings due to location.
Recommend further evaluation by a roofing contractor for any needed repairs.
|
10.4 | FOUNDATIONS - BASEMENTS - CRAWL SPACES | |
Repair or Replace | ||
![]() |
(1) There are moisture stains on the foundation wall. Moisture intrusion can lead to fungal growth, cracking, shifting and foundation issues.
A qualified waterproofing contractor should evaluate further, and make recommendations how to resolve reoccurring moisture entry
concerns.
|
|
![]() |
(2) Efflorescence (powder substance) on foundation wall indicates moisture is in contact with the masonry. This may suggest present/past
abnormal moisture entry at masonry wall. Further moisture entry/staining may occur. Proper professional should evaluate for cause
and make any needed repairs.
|
![]() |
INVOICE |
HomeTek Inspection Services, LLC
806 Green Valley Road, Suite 200 Greensboro, NC 27408 336-989-8185 Inspected By: Larry D Young |
Inspection Date: 6/1/2022
Report ID: 060122DY2 |
Customer Info: | Inspection Property: |
Sample Buyer
Customer's Real Estate Professional: |
123 Sample Street AnyTown NC 00000 |
| ||||||||||||||||||||
Tax $0.00 | ||||||||||||||||||||
Total Price $730.00 |
Payment Method:
Payment Status:
Note:
![]() HomeTek Inspection Services, LLC
806 Green Valley Road, Suite 200 |
ATTENTION: This inspection report is incomplete without reading the information included herein at these links/attachments. Note If you received a printed version of this page and did not receive a copy of the report through the internet please contact your inspector for a printed copy of the attachments.