Property Address:
11 N Terrace Ave
Chicago IL 60018
Julio C Patino Pacheco 450.012079
221 W Dempster St
Des Plaines, IL, 60016
Date: 3/7/2022 | Time: 12:00 PM | Report ID: 20220307-1132-Hartrey-Ave |
Property: 11 N Terrace Ave Chicago IL 60018 |
Customer: Joe C |
Real Estate Professional: Bosede Enyiema |
Comment Key or Definitions
This inspection was conducted in accordance with the State of Illinois Home Inspector Licensing Act. The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI) = I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Watch List (WL) = The item, component or unit requires schedule maintenance or monitoring.
Significantly Deficient (SD) = Defined by Illinois State Law as either a) not functioning or b) posing a safety hazard. It should be noted that a large number of significantly deficient items can be addressed at little cost. It is important to remember that the safety of a significantly deficient item is not based upon mere local building codes, which contain 'grandfathering' clauses, or the common 'accepted' practices of tradesmen, but on current national and international safety requirements and with the well being of the property and the client in mind.
Observations:
Text in red denotes an observation that in the inspectors opinion is a safety hazard, needs immediate repair, further evaluation, or is otherwise significantly deficient. These observations should generally be addressed before the close of escrow. You should read the entire report to understand all observations and recommendations.
Please Note: If you have any questions or any thing is unclear, please do not hesitate to contact Condo Home Inspections LLC and/or your specific inspector. We are happy to answer any of your questions.
PHOTOS: Your completed report may contain photographs of various conditions noted during the inspection. Photographs provided in this report are intended to help interested parties understand the context of this report, but may not represent the sum total of all conditions. You must read the entire report.
In Attendance: Customer representative | Type of building: Two-Flat Building | Approximate age of building: Over 50 Years |
Home Faces: East | Temperature: Over 65 (F) = 18 (C) | Weather: Clear |
Ground/Soil surface condition: Damp | Rain in last 3 days: Yes | Radon Test: No |
Water Test: No | Occupied or Vacant: Both |
75
Items Inspected
Total number in report.
24
Summary Comments
Total number in report.
1
Videos
Total number in report.
58
Photos
Total number in report.
1.0 |
Roof Coverings
Comments: |
![]() 1.0 Item 1(Picture) ![]() 1.0 Item 2(Picture) |
|
(2) Flat roofs are designed to be waterproof, not just water resistant, and to last approximately 10
years. They are not actually flat, but generally slope towards drains. However, water can form
puddles on many of these roofs that will only be dispersed by evaporation. For this and related
reasons, flat roofs have always been problematic and must be maintained. They are comprised
of several layers of rolled roofing materials, which are either hot-mopped or torched down, that
expand and contract in the daily and sometimes radical temperature extremes, and eventually
buckle, split, separate, and finally deteriorate. When this happens, the roof is susceptible to
leaks. However, although gradual decomposition of the roofing materials is inevitable, most
leaks result from poor maintenance. Therefore, regardless of the age of a flat roof, it should be
inspected seasonally, kept clean, and serviced frequently. Although less expensive than other
roofs, they can end up costing more if they are not maintained.
![]() 1.0 Item 3(Picture) ![]() 1.0 Item 4(Picture) |
1.1 |
Underlayment
Comments: |
1.2 |
Flashings
Comments: |
1.3 |
Skylights, Chimneys and Roof Penetrations
Comments: |
The chimney brick displayed brick spalling. Correction by a qualified chimney sweep
contractor is recommended so that further brick deterioration is avoided.
![]() 1.3 Item 1(Picture) |
1.4 |
Roof Drainage Systems
Comments: |
(1) Gutters had significant debris and require cleaning. Clogged gutters can cause water intrusion
problems. Cleaning should be performed as soon as possible.
![]() 1.4 Item 1(Picture) |
|
(2) There were underground downspouts installed. Although these systems can work effectively, it
is recommended that downspouts extend and discharge onto grade level at least 5ft to 6 ft away
from property. These systems may clog and flood basement areas.
![]() 1.4 Item 2(Picture) |
2.0 |
Wall Cladding Flashing and Trim
Comments: |
I recommend sealing exterior light fixtures against moisture. If not sealed, moisture can come
in contact with electrical wiring and create arcing.
![]() 2.0 Item 1(Picture) |
2.1 |
Windows
Comments: |
2.2 |
Doors (Exterior)
Comments: |
2.3 |
Decks, Balconies, Stoops, Steps, Areaways, Porches, Patio/Cover and Applicable Railings
Comments: |
2.4 |
Vegetation, Grading, Drainage, Driveways, Patio Floor, Walkways and Retaining Walls (With respect to their effect on the condition of the building)
Comments: |
(1) Tree limbs that are in contact with roof should be trimmed to avoid roof damage.
![]() 2.4 Item 1(Picture) |
|
(2) Tree in proximity with foundation may cause structural foundation damage in the future. I
recommend tree removal performed by a qualified arborist contractor.
Note: Observable areas in the basement did not display any signs of structural damage during the inspection. ![]() 2.4 Item 2(Picture) |
2.5 |
Driveway, Walkways, Carports
Comments: |
2.6 |
Eaves, Soffits and Fascias
Comments: |
2.7 |
Exterior Wall Vents
Comments: |
3.0 |
Ceilings
Comments: |
Ceilings exhibited some signs of sag, warp, loose tape joints or nail pops. There were minor
irregularities normally seen in this type of construction. It should be noted that minor cracking,
nail pops and tape cracks will appear over the next few years as the house goes through the
normal settling process. The best way to minimize this is to keep the temperature and humidity
in the property constant on a year round basis.
![]() 3.0 Item 1(Picture) ![]() 3.0 Item 2(Picture) |
3.1 |
Walls
Comments: |
Walls were finished with drywall and exhibited wall damage, signs of sag, warp, loose tape
joints or nail pops. These were minor irregularities, normally seen in houses of this age. Have
these areas corrected as needed by a qualified drywall and paint contractor.
![]() 3.1 Item 1(Picture) |
3.2 |
Floors
Comments: |
The kitchen floor in west unit was weak and needs to be reinforced or corrected from under
the crawlspace. I recommend further evaluation and correction performed by a qualified
general contractor.
![]() 3.2 Item 1(Picture) ![]() X
3.2 Item 2(Video) ![]() 3.2 Item 3(Picture) |
3.3 |
Windows (representative number)
Comments: |
Interior windows displayed no signs of cracked glass or condensation stains. However, more
than one window operated poorly when tested. Have all windows serviced and repaired as
needed by a qualified window installer.
![]() 3.3 Item 1(Picture) |
3.4 |
Doors (representative number)
Comments: |
The middle floor bedroom closet in east unit was blocked with furniture and I was not able to
fully open the door and inspect this closet. This is for your information only.
![]() 3.4 Item 1(Picture) |
3.5 |
Steps, Stairways, Balconies and Railings
Comments: |
More than one stair handrail was loose. Make sure that all handrails are secured before or
upon moving.
![]() 3.5 Item 1(Picture) |
3.6 |
Counters and Cabinets (representative number)
Comments: |
3.7 |
Pests & Rodents
Comments: |
I saw cockroach traps in the mechanical room. I recommend monitoring and to have the
building treated if needed by a licensed pest control contractor.
![]() 3.7 Item 1(Picture) |
3.8 |
Bathroom Vanity Tops & Cabinets
Comments: |
4.0 |
Foundations, Basement and Crawlspace (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.)
Comments: |
There was one sill plate location in the crawlspace that was rotted. The affected area was more
or less located below the exterior spigot. The sill plate should be repaired or replaced to prevent
floor joist movement.
I recommend further evaluation and correction performed by a qualified general building contractor. ![]() 4.0 Item 1(Picture) ![]() 4.0 Item 2(Picture) |
4.1 |
Walls (Structural)
Comments: |
The structural walls were not seen by the inspector, but are assumed to be 2 x 4 wood studs
consistent with the type and style of the construction.
|
4.2 |
Columns, Piers and Beams
Comments: |
4.3 |
Basement Concrete Floor Slab
Comments: |
4.4 |
Floors (Structural)
Comments: |
4.5 |
Ceilings (Structural)
Comments: |
Structural ceilings could not be observed because of finished walls and ceilings obstructing
view.
|
4.6 |
Roof Structure and Attic
Comments: |
Roof structure could not be observed because of finished walls and ceilings obstructing view.
|
5.0 |
Main Water Shut-off Device (Describe location)
Comments: |
The main water shut off was located in the east basement area. One of the valve handles was
broken and should be replaced by a licensed plumber.
![]() 5.0 Item 1(Picture) ![]() 5.0 Item 2(Picture) |
5.1 |
Interior Water Supply, Distribution System
Comments: |
(1) I sensed or measured hot water flowing out of every tub spout and shower area at a
temperature that won't cause scalding.
![]() 5.1 Item 1(Picture) |
|
(2) The distribution water pipe system was composed of copper and was properly supported
where it was possible to observe. There were no distribution water leaks during the inspection.
All plumbing fixtures were properly connected to a hot water source.
|
5.2 |
Interior Drain, Waste and Vent Systems
Comments: |
Interior drain,waste and vent systems operated properly. No signs of leakage, or physical
damage was observed, where it was possible to observe.
The sewer cleanout was found in the mechanical room. ![]() 5.2 Item 1(Picture) |
5.3 |
Sump Pump & Ejector Pumps
Comments: |
5.4 |
Interior Plumbing Fixtures
Comments: |
I recommend sealing shower and tub fixture against moisture damage. Because these fixtures
were not sealed, water can seep behind the tile if not repaired.
![]() 5.4 Item 1(Picture) |
5.5 |
Whirlpools
Comments: |
5.6 |
Hot Water Systems, Controls, Chimneys, Flues and Vents
Comments: |
The life expectancy for a conventional water heater is approximately 6 to 12 years. Both units
were manufactured in 2019.
![]() 5.6 Item 1(Picture) ![]() 5.6 Item 2(Picture) |
5.7 |
Hot Water Tank TPR (Temperature Pressure Relief Valve)
Comments: |
The TPR (temperature pressure relief) pipe did not terminate at least 2 to 6 inches above the
floor. The pipes can severely burn someone if the TPR valve(s) release steam and someone is
near the tank(s). Correction by a qualified handyman contractor is recommended.
![]() 5.7 Item 1(Picture) ![]() 5.7 Item 2(Picture) ![]() 5.7 Item 3(Picture) |
5.8 |
Main Fuel Shut-off (Describe Location)
Comments: |
The main fuel gas shut off was located outside.
![]() 5.8 Item 1(Picture) |
5.9 |
Fuel Storage and Distribution Systems (Interior fuel storage, piping, venting, supports, leaks)
Comments: |
5.10 |
Exterior Hose Bibs
Comments: |
I recommend replacing the exterior hose bib with a frost proof valve known as anti-siphon
sillcock(s). During cold weather, exterior hose bibs are prone to crack due to cold water
expansion. Correction by a licensed plumber is recommended.
![]() 5.10 Item 1(Picture) ![]() 5.10 Item 2(Picture) |
6.0 |
Connected Devices and Fixtures (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)
Comments: |
(1) The rear exterior light fixture did not appear weather proofed and should be replaced.
![]() 6.0 Item 1(Picture) |
|
(2) In the vacant unit, there was no switch next to main entry door that would turn on the lights in
the living room or dining room. This is for your information only.
![]() 6.0 Item 2(Picture) ![]() 6.0 Item 3(Picture) |
6.1 |
Polarity and Grounding of Receptacles within 6 feet of interior plumbing fixtures, all receptacles in garage, carport and exterior walls of inspected structure
Comments: |
Outlets in unfinished basement areas are required to be GFCI protected. More than one outlet
needs correction for safety.
I recommend further evaluation and correction performed by a qualified electrician. ![]() 6.1 Item 1(Picture) |
6.2 |
Operation of GFCI (Ground Fault Circuit Interrupters)
Comments: |
One GFCI outlet in mechanical room failed to reset. This is a safety hazard as the unit is not
working as intended.
![]() 6.2 Item 1(Picture) ![]() 6.2 Item 2(Picture) |
6.3 |
Operation of AFCI (ARC Fault Circuit Interrupters)
Comments: |
6.4 |
Smoke Detectors / Carbon Monoxide Detectors
Comments: |
More than one location in this property was missing carbon/smoke detector units. The following
areas should be equipped with these units:
• In the immediate vicinity of bedrooms within 15 feet and not less than 3 feet horizontally from the door or opening of a bathroom. • In all bedrooms • In each story of a dwelling unit, including basements and cellars • Within 20 feet of a kitchen and within 15 feet of gas fired appliances. |
6.5 |
Service Entrance Conductors
Comments: |
6.6 |
Location of Main and Distribution Panels
Comments: |
Both electrical panels were located in the basement.
![]() 6.6 Item 1(Picture) ![]() 6.6 Item 2(Picture) ![]() 6.6 Item 3(Picture) ![]() 6.6 Item 4(Picture) |
6.7 |
Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels
Comments: |
The east main electrical panel neutral bus did not appear grounded. Properly grounding the
panel protects it against electrical faults in the electrical system. I recommend further
evaluation and correction performed by a qualified electrician.
![]() 6.7 Item 1(Picture) ![]() 6.7 Item 2(Picture) ![]() 6.7 Item 3(Picture) |
6.8 |
Branch Circuit Conductors, Overcurrent Devices and Compatability of their Amperage and Voltage
Comments: |
The maximum breaker size allowed by the condenser manufacturing labels is 25 amps. The
condensers were protected with 30 amp circuit breakers and should be corrected so that the
breakers trip during an overload. If not repaired, electrical components in the unit can be
damaged.
![]() 6.8 Item 1(Picture) ![]() 6.8 Item 2(Picture) ![]() 6.8 Item 3(Picture) |
7.0 |
Heating Equipment
Comments: |
The life expectancy for a furnace is approximately 15 to 25 years. Both units were
manufactured in 2019.
![]() 7.0 Item 1(Picture) ![]() 7.0 Item 2(Picture) |
7.1 |
Normal Operating And Safety Controls
Comments: |
The furnace systems were operated using normal operating controls by turning on the
thermostats. The thermostats were properly mounted and secured. The inspector set the
thermostats back to their original setting.
The furnace systems were operated through a complete cycle. |
7.2 |
Distribution Systems (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)
Comments: |
I noticed dirty HVAC supply and return registers. I recommend cleaning all ducts upon moving
and at least every 5 years thereafter. This would limit the recirculation of pollutants in the home
and help air filters to efficiently perform better.
|
7.3 |
Presence of Installed Heat Source in Each Room
Comments: |
7.4 |
Chimneys, Flues and Vents (for fireplaces, gas water heaters or heat systems)
Comments: |
7.5 |
Cooling and Air Handler Equipment and Normal Operating Controls
Comments: |
The life expectancy for a condenser is approximately 8 to 20 years. Both systems were
manufactured in 2019.
![]() 7.5 Item 1(Picture) |
7.6 |
Cooling Equipment Findings
Comments: |
The AC systems responded properly to normal operating controls. The difference in
temperatures of the supply and return air was between 14 degrees and 22 degrees which
indicated that the units were cooling as intended. This indicated a proper differential
temperature of the system.
|
7.7 |
Presence of Installed Cooling Source in Each Room
Comments: |
8.0 |
Venting Systems (Kitchens, Baths and Laundry)
Comments: |
8.1 |
Ventilation of Attic and Foundation Areas
Comments: |
8.2 |
Insulation And Vapor Retarders In Unfinished Spaces
Comments: |
The crawlspace had no vapor retarder installed and as a consequence the crawlspace had
musty odors due to elevated moisture coming from the exposed ground. In order to keep
humidity down, the crawlspace should be encapsulated by means of a vapor retarder. I
recommend further evaluation and correction by a qualified crawlspace contractor.
![]() 8.2 Item 1(Picture) |
8.3 |
Insulation Behind Finished Walls
Comments: |
There were sections above cathedral ceilings in both units that lacked proper insulation. Poor
insulated ceilings will lead to higher energy costs. I recommend consulting a qualified insulation
contractor options for adding insulation in these areas.
![]() 8.3 Item 1(Picture) ![]() 8.3 Item 2(Picture) |
8.4 |
Dryer Vent Line
Comments: |
(1)
I recommend cleaning the dryer vent pipe because it was clogged and poses a fire hazard.
This maintenance item should be performed on a yearly basis.
![]() 8.4 Item 1(Picture) |
|
(2)
The dryer was vented using a flexible, ribbed, foil-like vent that is more likely to accumulate lint
than a smooth metal vent, creating a potential fire hazard. Excessive lint accumulation can also
increase drying time and shorten the dryer's lifespan.
![]() 8.4 Item 2(Picture) |
9.0 |
Refrigerator
Comments: |
9.1 |
Dishwasher
Comments: |
9.2 |
Range Hood (s)
Comments: |
9.3 |
Microwave Cooking Equipment
Comments: |
9.4 |
Ranges/Ovens/Cooktops
Comments: |
9.5 |
Washer
Comments: |
9.6 |
Dryer
Comments: |
221 W Dempster St
Des Plaines, IL, 60016
Customer
Joe C
Address
11 N Terrace Ave
Chicago IL 60018
1.3 | Skylights, Chimneys and Roof Penetrations | |
Repair or Replace, Inspected | ||
The chimney brick displayed brick spalling. Correction by a qualified chimney sweep
contractor is recommended so that further brick deterioration is avoided.
![]() 1.3 Item 1(Picture) |
2.0 | Wall Cladding Flashing and Trim | |
Repair or Replace, Inspected | ||
I recommend sealing exterior light fixtures against moisture. If not sealed, moisture can come
in contact with electrical wiring and create arcing.
![]() 2.0 Item 1(Picture) |
2.4 | Vegetation, Grading, Drainage, Driveways, Patio Floor, Walkways and Retaining Walls (With respect to their effect on the condition of the building) | |
Repair or Replace, Inspected | ||
(1) Tree limbs that are in contact with roof should be trimmed to avoid roof damage.
![]() 2.4 Item 1(Picture) |
||
(2) Tree in proximity with foundation may cause structural foundation damage in the future. I
recommend tree removal performed by a qualified arborist contractor.
Note: Observable areas in the basement did not display any signs of structural damage during
the inspection. ![]() 2.4 Item 2(Picture) |
3.1 | Walls | |
Repair or Replace, Inspected | ||
Walls were finished with drywall and exhibited wall damage, signs of sag, warp, loose tape
joints or nail pops. These were minor irregularities, normally seen in houses of this age. Have
these areas corrected as needed by a qualified drywall and paint contractor.
![]() 3.1 Item 1(Picture) |
3.2 | Floors | |
Repair or Replace, Inspected | ||
The kitchen floor in west unit was weak and needs to be reinforced or corrected from under
the crawlspace. I recommend further evaluation and correction performed by a qualified
general contractor.
![]() 3.2 Item 1(Picture) ![]() X
3.2 Item 2(Video) ![]() 3.2 Item 3(Picture) |
3.3 | Windows (representative number) | |
Repair or Replace, Inspected | ||
Interior windows displayed no signs of cracked glass or condensation stains. However, more
than one window operated poorly when tested. Have all windows serviced and repaired as
needed by a qualified window installer.
![]() 3.3 Item 1(Picture) |
3.5 | Steps, Stairways, Balconies and Railings | |
Repair or Replace, Inspected | ||
More than one stair handrail was loose. Make sure that all handrails are secured before or
upon moving.
![]() 3.5 Item 1(Picture) |
4.0 | Foundations, Basement and Crawlspace (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) | |
Significantly Deficient, Inspected | ||
There was one sill plate location in the crawlspace that was rotted. The affected area was more
or less located below the exterior spigot. The sill plate should be repaired or replaced to prevent
floor joist movement.
I recommend further evaluation and correction performed by a qualified general building contractor. ![]() 4.0 Item 1(Picture) ![]() 4.0 Item 2(Picture) |
5.0 | Main Water Shut-off Device (Describe location) | |
Repair or Replace, Inspected | ||
The main water shut off was located in the east basement area. One of the valve handles was
broken and should be replaced by a licensed plumber.
![]() 5.0 Item 1(Picture) ![]() 5.0 Item 2(Picture) |
5.4 | Interior Plumbing Fixtures | |
Repair or Replace, Inspected | ||
I recommend sealing shower and tub fixture against moisture damage. Because these fixtures
were not sealed, water can seep behind the tile if not repaired.
![]() 5.4 Item 1(Picture) |
5.7 | Hot Water Tank TPR (Temperature Pressure Relief Valve) | |
Significantly Deficient, Inspected | ||
The TPR (temperature pressure relief) pipe did not terminate at least 2 to 6 inches above the
floor. The pipes can severely burn someone if the TPR valve(s) release steam and someone is
near the tank(s). Correction by a qualified handyman contractor is recommended.
![]() 5.7 Item 1(Picture) ![]() 5.7 Item 2(Picture) ![]() 5.7 Item 3(Picture) |
5.10 | Exterior Hose Bibs | |
Repair or Replace, Inspected | ||
I recommend replacing the exterior hose bib with a frost proof valve known as anti-siphon
sillcock(s). During cold weather, exterior hose bibs are prone to crack due to cold water
expansion. Correction by a licensed plumber is recommended.
![]() 5.10 Item 1(Picture) ![]() 5.10 Item 2(Picture) |
6.0 | Connected Devices and Fixtures (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) | |
Repair or Replace, Inspected | ||
(1) The rear exterior light fixture did not appear weather proofed and should be replaced.
![]() 6.0 Item 1(Picture) |
||
(2) In the vacant unit, there was no switch next to main entry door that would turn on the lights in
the living room or dining room. This is for your information only.
![]() 6.0 Item 2(Picture) ![]() 6.0 Item 3(Picture) |
6.1 | Polarity and Grounding of Receptacles within 6 feet of interior plumbing fixtures, all receptacles in garage, carport and exterior walls of inspected structure | |
Significantly Deficient, Inspected | ||
Outlets in unfinished basement areas are required to be GFCI protected. More than one outlet
needs correction for safety.
I recommend further evaluation and correction performed by a qualified electrician. ![]() 6.1 Item 1(Picture) |
6.2 | Operation of GFCI (Ground Fault Circuit Interrupters) | |
Significantly Deficient, Inspected | ||
One GFCI outlet in mechanical room failed to reset. This is a safety hazard as the unit is not
working as intended.
![]() 6.2 Item 1(Picture) ![]() 6.2 Item 2(Picture) |
6.4 | Smoke Detectors / Carbon Monoxide Detectors | |
Significantly Deficient, Inspected | ||
More than one location in this property was missing carbon/smoke detector units. The following
areas should be equipped with these units:
• In the immediate vicinity of bedrooms within 15 feet and not less than 3 feet horizontally from the door or opening of a bathroom. • In all bedrooms • In each story of a dwelling unit, including basements and cellars • Within 20 feet of a kitchen and within 15 feet of gas fired appliances. |
6.7 | Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels | |
Significantly Deficient, Inspected | ||
The east main electrical panel neutral bus did not appear grounded. Properly grounding the
panel protects it against electrical faults in the electrical system. I recommend further
evaluation and correction performed by a qualified electrician.
![]() 6.7 Item 1(Picture) ![]() 6.7 Item 2(Picture) ![]() 6.7 Item 3(Picture) |
6.8 | Branch Circuit Conductors, Overcurrent Devices and Compatability of their Amperage and Voltage | |
Repair or Replace, Inspected | ||
The maximum breaker size allowed by the condenser manufacturing labels is 25 amps. The
condensers were protected with 30 amp circuit breakers and should be corrected so that the
breakers trip during an overload. If not repaired, electrical components in the unit can be
damaged.
![]() 6.8 Item 1(Picture) ![]() 6.8 Item 2(Picture) ![]() 6.8 Item 3(Picture) |
8.2 | Insulation And Vapor Retarders In Unfinished Spaces | |
Repair or Replace, Inspected | ||
The crawlspace had no vapor retarder installed and as a consequence the crawlspace had
musty odors due to elevated moisture coming from the exposed ground. In order to keep
humidity down, the crawlspace should be encapsulated by means of a vapor retarder. I
recommend further evaluation and correction by a qualified crawlspace contractor.
![]() 8.2 Item 1(Picture) |
8.3 | Insulation Behind Finished Walls | |
Repair or Replace, Inspected | ||
There were sections above cathedral ceilings in both units that lacked proper insulation. Poor
insulated ceilings will lead to higher energy costs. I recommend consulting a qualified insulation
contractor options for adding insulation in these areas.
![]() 8.3 Item 1(Picture) ![]() 8.3 Item 2(Picture) |
8.4 | Dryer Vent Line | |
Significantly Deficient, Inspected | ||
(1)
I recommend cleaning the dryer vent pipe because it was clogged and poses a fire hazard.
This maintenance item should be performed on a yearly basis.
![]() 8.4 Item 1(Picture) |
||
(2)
The dryer was vented using a flexible, ribbed, foil-like vent that is more likely to accumulate lint
than a smooth metal vent, creating a potential fire hazard. Excessive lint accumulation can also
increase drying time and shorten the dryer's lifespan.
![]() 8.4 Item 2(Picture) |
INVOICE |
Condo Home Inspections LLC
221 W Dempster St Des Plaines, IL, 60016 Inspected By: Julio C Patino Pacheco |
Inspection Date: 3/7/2022
Report ID: 20220307-1132-Hartrey-Ave |
Customer Info: | Inspection Property: |
Joe C
Customer's Real Estate Professional: Bosede Enyiema |
11 N Terrace Ave Chicago IL 60018 |
| ||||||||
Tax $0.00 | ||||||||
Total Price $525.00 |
Payment Method: Credit Card
Payment Status: Paid
Note:
The property roof was covered with architectural fiberglass asphalt shingles, also called "laminated" or dimensional" shingles and modified bitumen on the flat side of the roof. The life expectancy for architectural shingles is 30 years and the life expectancy for a flat roof system is 10 to 15 years. I recommend asking the seller how old the roof system is, and, if possible, to provide documentation regarding roof material warranty from manufacturer and installer.