Property Address:
1234 Sample Drive
PGA West
La Quinta CA
Daniel D. Weinberg
5419 Alpine Blvd.
Alpine. CA 91901
619.274.1113
619.659.2118 (fax)
Date: 7/29/2010 | Time: 02:00 PM | Report ID: C0822102 |
Property: 1234 Sample Drive PGA West La Quinta CA |
Customer: Mr. Bill Smith |
Real Estate Professional: Sally Jones Real Estate Experts |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Standards of Practice: CREIA California, NACHI National Association of Certified Home Inspectors | In Attendance: Customer and their agent | Type of building: Single Family (1 story) |
Style of Home: Contemporary | Approximate age of building: Under 10 Years | Home Faces: North |
Temperature: Over 100 | Weather: Clear | Ground/Soil surface condition: Dry |
Rain in last 3 days: No | Radon Test: No | Water Test: No |
Viewed roof covering from: Ladder |
Roof-Type: Gable |
Roof Covering: Concrete Tile |
Chimney (exterior): Masonry Stucco |
Sky Light(s): None |
Roof Ventilation: Gable vents Ridge vents |
Method used to observe attic: From entry Walked |
Roof Structure: 2 X 4 Rafters |
Ceiling Structure: 2X4 |
Attic info: Attic access Light in attic Attic hatch |
Attic Insulation: Fiberglass R-19 or better |
IN | NI | NP | RR | ||
1.0 | ROOF COVERINGS | • | • | ||
1.1 | FLASHINGS | • | |||
1.2 | SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS | • | |||
1.3 | ROOF VENTILATION | • | |||
1.4 | ROOF STRUCTURE AND ATTIC (Report leak signs or condensation) | • | |||
1.5 | INSULATION IN ATTIC | • | |||
1.6 | VISIBLE ELECTRIC WIRING IN ATTIC | • | |||
IN | NI | NP | RR |
Inspector noted 2 broken roof tiles over the garage. Broken tiles can allow rain water to penetrate the underlayment of the roof and ultimately leak.
Inspector observed no obvious signs of leaking in the attic or ceiling above the broken tiles. However, we recommend further inspection/repair by a qualified roofing contractor.
Siding Style: Cement stucco |
Exterior Entry Doors: Wood |
Appurtenance: Sidewalk Deck Patio |
Driveway: Concrete |
IN | NI | NP | RR | ||
2.0 | WALL CLADDING FLASHING AND TRIM | • | |||
2.1 | DOORS (Exterior) | • | |||
2.2 | WINDOWS | • | |||
2.3 | DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS | • | |||
2.4 | VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) | • | • | ||
2.5 | EAVES, SOFFITS AND FASCIAS | • | |||
2.6 | PLUMBING WATER FAUCETS (hose bibs) | • | |||
2.7 | OUTLETS (exterior) | • | |||
2.8 | OTHER | • | |||
IN | NI | NP | RR |
We recommend correction by a qualified contractor.
Garage Door Type: Three automatic |
Garage Door Material: Metal |
Auto-opener Manufacturer: GENIE |
IN | NI | NP | RR | ||
3.0 | GARAGE CEILINGS | • | |||
3.1 | GARAGE WALLS (INCLUDING FIREWALL SEPARATION) | • | |||
3.2 | GARAGE FLOOR | • | |||
3.3 | GARAGE DOOR (S) | • | |||
3.4 | OCCUPANT DOOR FROM GARAGE TO INSIDE HOME | • | |||
3.5 | GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met with resistance) | • | • | ||
IN | NI | NP | RR |
We recommend further inspection/correction by a qualified contractor.
Dishwasher Brand: KITCHEN AIDE |
Disposer Brand: IN SINK ERATOR |
Exhaust/Range hood: NONE |
Range/Oven: KITCHEN AIDE |
Built in Microwave: KITCHEN AIDE |
Trash Compactors: NONE |
Cabinetry: Wood |
Countertop: Granite |
Refrigerator: KITCHENAIDE |
Refrigerator Opening Width: 41 inches |
Refrigerator Opening Height: 75 inches |
Clothes Dryer Vent Material: Flexible Metal |
Dryer Power Source: 220 Electric Gas Connection |
IN | NI | NP | RR | ||
4.0 | CEILINGS | • | |||
4.1 | WALLS | • | |||
4.2 | FLOORS | • | |||
4.3 | PANTRY/CLOSET DOORS | • | |||
4.4 | WINDOWS | • | |||
4.5 | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS | • | |||
4.6 | PLUMBING DRAIN AND VENT SYSTEMS | • | |||
4.7 | PLUMBING WATER SUPPLY FAUCETS AND FIXTURES | • | |||
4.8 | OUTLETS WALL SWITCHES and FIXTURES | • | |||
4.9 | DISHWASHER | • | |||
4.10 | RANGES/OVENS/COOKTOPS | • | |||
4.11 | RANGE HOOD | • | |||
4.12 | TRASH COMPACTOR | • | |||
4.13 | FOOD WASTE DISPOSER | • | |||
4.14 | MICROWAVE COOKING EQUIPMENT | • | |||
4.15 | CLOTHES DRYER VENT PIPING | • | |||
IN | NI | NP | RR |
Ceiling Materials: Drywall |
Wall Material: Drywall |
Floor Covering(s): Carpet Tile |
Window Types: Thermal/Insulated |
Window Manufacturer: UNKNOWN |
IN | NI | NP | RR | ||
5.0.A | CEILINGS | • | |||
5.1.A | WALLS | • | |||
5.2.A | FLOORS | • | |||
5.3.A | STEPS, STAIRWAYS, BALCONIES AND RAILINGS | • | |||
5.4.A | WINDOWS (REPRESENTATIVE NUMBER) | • | |||
5.5.A | OUTLETS SWITCHES AND FIXTURES | • | |||
IN | NI | NP | RR |
Ceiling Materials: Drywall |
Wall Material: Drywall |
Floor Covering(s): Carpet |
Interior Doors: Solid |
Window Types: Thermal/Insulated |
Window Manufacturer: UNKNOWN |
IN | NI | NP | RR | ||
5.0.B | CEILINGS | • | |||
5.1.B | WALLS | • | |||
5.2.B | FLOORS | • | |||
5.3.B | STEPS, STAIRWAYS, BALCONIES AND RAILINGS | • | |||
5.4.B | DOORS (REPRESENTATIVE NUMBER) | • | |||
5.5.B | WINDOWS (REPRESENTATIVE NUMBER) | • | |||
5.6.B | OUTLETS SWITCHES AND FIXTURES | • | |||
IN | NI | NP | RR |
Ceiling Materials: Drywall |
Wall Material: Drywall |
Floor Covering(s): Tile |
Window Types: Thermal/Insulated |
Window Manufacturer: UNKNOWN |
IN | NI | NP | RR | ||
5.0.C | CEILINGS | • | |||
5.1.C | WALLS | • | |||
5.2.C | FLOORS | • | |||
5.3.C | STEPS, STAIRWAYS, BALCONIES AND RAILINGS | • | |||
5.4.C | DOORS (REPRESENTATIVE NUMBER) | • | |||
5.5.C | WINDOWS (REPRESENTATIVE NUMBER) | • | |||
5.6.C | OUTLETS SWITCHES AND FIXTURES | • | |||
IN | NI | NP | RR |
Ceiling Materials: Drywall |
Wall Material: Drywall |
Floor Covering(s): Carpet Tile |
Interior Doors: Solid |
Window Types: Thermal/Insulated |
Window Manufacturer: UNKNOWN |
IN | NI | NP | RR | ||
5.0.D | CEILINGS | • | |||
5.1.D | WALLS | • | |||
5.2.D | FLOORS | • | |||
5.3.D | STEPS, STAIRWAYS, BALCONIES AND RAILINGS | • | |||
5.4.D | DOORS (REPRESENTATIVE NUMBER) | • | |||
5.5.D | WINDOWS (REPRESENTATIVE NUMBER) | • | |||
5.6.D | OUTLETS SWITCHES AND FIXTURES | • | |||
IN | NI | NP | RR |
Exhaust Fans: Fan only |
IN | NI | NP | RR | ||
6.0.A | COUNTERS AND CABINETS | • | |||
6.1.A | DOORS (REPRESENTATIVE NUMBER) | • | |||
6.2.A | WINDOWS | • | |||
6.3.A | PLUMBING DRAIN, WASTE AND VENT SYSTEMS | • | |||
6.4.A | PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES | • | |||
6.5.A | OUTLETS SWITCHES AND FIXTURES | • | |||
6.6.A | EXHAUST FAN | • | |||
IN | NI | NP | RR |
Exhaust Fans: Fan only |
IN | NI | NP | RR | ||
6.0.B | COUNTERS AND CABINETS | • | |||
6.1.B | DOORS (REPRESENTATIVE NUMBER) | • | |||
6.2.B | WINDOWS | • | |||
6.3.B | PLUMBING DRAIN, WASTE AND VENT SYSTEMS | • | |||
6.4.B | PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES | • | |||
6.5.B | OUTLETS SWITCHES AND FIXTURES | • | |||
6.6.B | EXHAUST FAN | • | |||
IN | NI | NP | RR |
Exhaust Fans: Fan only |
IN | NI | NP | RR | ||
6.0.C | COUNTERS AND CABINETS | • | |||
6.1.C | DOORS (REPRESENTATIVE NUMBER) | • | |||
6.2.C | WINDOWS | • | |||
6.3.C | PLUMBING DRAIN, WASTE AND VENT SYSTEMS | • | |||
6.4.C | PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES | • | |||
6.5.C | OUTLETS SWITCHES AND FIXTURES | • | |||
6.6.C | EXHAUST FAN | • | |||
IN | NI | NP | RR |
Foundation: Poured concrete |
Floor Structure: Slab |
Wall Structure: 2 X 4 Wood |
IN | NI | NP | RR | ||
7.0 | FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) | • | |||
7.1 | WALLS (Structural) | • | |||
7.2 | COLUMNS OR PIERS | • | |||
7.3 | CEILINGS (structural) | • | |||
7.4 | INSULATION UNDER FLOOR SYSTEM | • | |||
7.5 | VENTILATION OF FOUNDATION AREA (crawlspace or basement) | • | |||
IN | NI | NP | RR |
Water Source: Public |
Plumbing Water Supply (into home): Copper |
Plumbing Water Distribution (inside home): Copper |
Washer Drain Size: 2" Diameter |
Plumbing Waste Line: ABS |
Water Heater Power Source: Gas (quick recovery) |
Water Heater Capacity: 50 Gallon (2-3 people) |
Water Heater Manufacturer: RHEEM |
Water Heater Location: Main Floor |
IN | NI | NP | RR | ||
8.0 | PLUMBING DRAIN, WASTE AND VENT SYSTEMS | • | |||
8.1 | PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES | • | |||
8.2 | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS | • | |||
8.3 | MAIN WATER SHUT-OFF DEVICE (Describe location) | • | |||
8.4 | FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) | • | |||
8.5 | MAIN FUEL SHUT OFF (Describe Location) | • | |||
8.6 | SUMP PUMP | • | |||
IN | NI | NP | RR |
Electrical Service Conductors: Below ground |
Panel capacity: (2) 200 AMP service panel |
Panel Type: Circuit breakers |
Electric Panel Manufacturer: MURRAY |
Branch wire 15 and 20 AMP: Copper |
Wiring Methods: Romex |
IN | NI | NP | RR | ||
9.0 | SERVICE ENTRANCE CONDUCTORS | • | |||
9.1 | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS | • | |||
9.2 | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE | • | |||
9.3 | CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) | • | • | ||
9.4 | POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE | • | |||
9.5 | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) | • | |||
9.6 | LOCATION OF MAIN AND DISTRIBUTION PANELS | • | |||
9.7 | SMOKE DETECTORS | • | |||
9.8 | CARBON MONOXIDE DETECTORS | • | |||
IN | NI | NP | RR |
Trip hazard, we recommend correction by a qualified contractor.
Heat Type: Forced Air |
Energy Source: Gas |
Number of Heat Systems (excluding wood): Two |
Ductwork: Insulated |
Filter Type: Disposable |
Filter Size: N/A |
Types of Fireplaces: Vented gas logs |
Operable Fireplaces: One |
Number of Woodstoves: None |
Cooling Equipment Type: Air conditioner unit |
Cooling Equipment Energy Source: Electricity |
Central Air Manufacturer: RHEEM |
Number of AC Only Units: Two |
IN | NI | NP | RR | ||
10.0 | HEATING EQUIPMENT | • | |||
10.1 | NORMAL OPERATING CONTROLS | • | |||
10.2 | AUTOMATIC SAFETY CONTROLS | • | |||
10.3 | DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) | • | |||
10.4 | PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM | • | |||
10.5 | CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat systems) | • | |||
10.6 | SOLID FUEL HEATING DEVICES (Fireplaces, Woodstove) | • | |||
10.7 | GAS/LP FIRELOGS AND FIREPLACES | • | |||
10.8 | COOLING AND AIR HANDLER EQUIPMENT | • | |||
10.9 | NORMAL OPERATING CONTROLS | • | |||
10.10 | PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM | • | |||
IN | NI | NP | RR |
A pool alarm with a loud speaker system to sound outside as well as inside the home could save a life. Even if you do not have children you should be concerned. 35% of children that drowned did so in someone else's pool. For more info, do an Internet search on pool safety or visit this website: http://www.ihf.org/foryourhealth/article_children.html
Style: Above ground |
Shape: Freeform |
Wall Material: Gunite (concrete) |
IN | Yes | NI | NP | RR | No | ||
11.0 | OPERATIONAL CONDITION OF POOL | • | |||||
11.1 | SURFACE WALLS AND FLOOR OF POOL | • | |||||
11.2 | POOL EQUIPMENT PLUMBING | • | • | ||||
11.3 | PUMPS FOR CIRCULATION OF WATER | • | |||||
11.4 | PUMPS FOR VACUUM OR CLEANING | • | |||||
11.5 | POOL HEATERS | • | |||||
11.6 | VERIFY THE ELECTRICAL OUTLET(S) AND ANY LIGHTING FOR POOL IS ON A GROUND FAULT CIRCUIT (GFCI) | • | |||||
11.7 | OVERFLOW SKIMMERS AND DRAINS | • | |||||
11.8 | CHEMICALS FOR POOL CAPABLE OF BEING STORED WITH A LOCK | • | |||||
11.9 | DOES POOL HAVE ANY RESCUE EQUIPMENT | • | |||||
11.10 | DO STEPS OR LADDERS EXIST ON BOTH SIDES OF THE POOL | • | • | ||||
11.11 | IS THE POOL DEPTH MARKED ON OUTSIDE AREA OF POOL | • | • | ||||
11.12 | IS THERE A DEPTH OF AT LEAST 8 FEET TO ALLOW SAFE DIVING | • | • | ||||
11.13 | ARE THERE ANY OBSTRUCTIONS (WALLS, SHRUBS etc.) THAT WOULD PREVENT FULL VIEW OF POOL FROM HOME | • | |||||
11.14 | IS THE POOL FENCED | • | • | ||||
11.15 | DOES FENCE HAVE A SELF CLOSING LATCH AND LOCK ON DOOR | • | |||||
11.16 | CAN FENCE BE CLIMBED BY THE USE OF PERSONAL ITEMS OR STRUCTURES AGAINST FENCE | • | |||||
11.17 | DOES THE DOOR LATCH HEIGHT AND LOCATION ATTEMPT TO BE REASONABLY DIFFICULT FOR YOUNG CHILDREN TO REACH | • | • | ||||
11.18 | ELECTRIC LIGHTS SECURE | • | • | ||||
11.19 | WATER LEVEL SHOULD BE WITHIN INCHES FROM RIM TO ALLOW AN EASIER CLIMB OUT | • | • | ||||
11.20 | POOL DESIGN AT WATERS EDGE SHOULD NOT INCLUDE OBVIOUS PROTRUSIONS THAT COULD INJURE SWIMMER | • | |||||
11.21 | DOES THE SURFACE AROUND POOL ENCOURAGE DRAINAGE AWAY FROM POOL | • | • | ||||
IN | Yes | NI | NP | RR | No |
We recommend further inspection/repair by a qualified pool equipment repair contractor.
Pool users should be aware that the pool depth is not sufficient to permit diving.
City of La Quinta ordinance # 85-1, 1985 (Pools located within the boundaries of a country club or similar walled residential development project are exempt.)
5419 Alpine Blvd.
Alpine. CA 91901
619.274.1113
619.659.2118 (fax)
Customer
Mr. Bill Smith
Address
1234 Sample Drive
PGA West
La Quinta CA
1. Roofing / Chimneys / Roof Structure and Attic | |||||||||
|
2. Exterior | |||||||||
|
3. Garage | |||||||||
|
9. Electrical System | |||||||||
|
INVOICE |
Certified Home Inspections
5419 Alpine Blvd. Alpine. CA 91901 619.274.1113 619.659.2118 (fax) Inspected By: Daniel D. Weinberg |
Inspection Date: 7/29/2010
Report ID: C0822102 |
Customer Info: | Inspection Property: |
Mr. Bill Smith
12345 Sample Drive La Quinta CA Customer's Real Estate Professional: Sally Jones Real Estate Experts |
1234 Sample Drive PGA West La Quinta CA |
| ||||||||||||
Tax $0.00 | ||||||||||||
Total Price $350.00 |
Payment Method:
Payment Status: Paid At Time Of Inspection
Note:
INSPECTION AGREEMENT
THIS IS A LEGALLY BINDING CONTRACT PLEASE READ IT CAREFULLY |
Address of Structure to be Inspected: |
1234 Sample Drive PGA West La Quinta CA |
Inspection Fee: |
$ 350.00 |
1. |
Client requests a visual inspection of the structure identified at the above address by Certified Home Inspections hereinafter collectively referred as the “Company” and Client hereby represents and warrants that all approvals necessary have been secured for the Company’s entrance on to the property. |
2. |
Client warrants that (a) Client has read this Agreement carefully, (b) Client understands the Client is bound by all the terms of this Agreement, and (c) Client will read the entire Inspection Report and follow every recommendation for repairs, maintenance, safety or further evaluation by a specialist. Furthermore, Client agrees that if such action is not undertaken and documented that the Company shall be held harmless for any subsequently alleged defects or deficiencies regarding that specific component/system or condition. |
3. |
CONFIDENTIAL REPORT: Client understands that the inspection and the Inspection Report are performed and prepared for Client’s sole, confidential use. Client agrees that Client will not transfer, disseminate or otherwise disclose any part of the Inspection Report to any other persons. The ONLY exceptions to this non-disclosure are as follows: (a) one copy may be provided to the current Seller (b) one copy may be provided to the Real Estate Agent directly representing Client and/or Client’s lending institution for the use in the Client’s transaction only. (c) one copy may be provided to the Attorney directly representing Client. IN THE EVENT THAT ANYONE OR ANY ENTITY CLAIMS DAMEGES AS ARESULT OF THE RELIANCE UPON THE INSPECTION REPORT, AND SEEKS RECOMPENSE FOR SAID DAMAGES FROM THE COMPANY, Client agrees to indemnify, defend, and hold Company and/or Inspector harmless from any third party claims arising out of Client’s unauthorized distribution of the Inspection Report, including, but not limited to, any claims caused by the alleged negligence, breach of contract, fraud, misrepresentation, or any other theory of liability of the company. |
4. |
Company agrees to perform a limited visual inspection of the structure at the above address and to provide Client with a written opinion as to the apparent general condition of the structure’s components and systems, including identification of significant observable deficiencies, as they exist at the time of the inspection. The inspection will be performed in a manner consistent with the Standards of Practice of the American Society of Home Inspectors (ASHI). A copy of these standards is attached to the Inspection Agreement |
5. |
SCOPE OF INSPECTION: The inspection only includes those systems and components expressly and specifically identified in the inspection report. Any area, which is not exposed to view, is concealed, is inaccessible because of soil, walls, floors, Carpets, ceilings, furnishings or any other thing, or those areas/items, which have been excluded is not included in this inspection. The inspection does not include any destructive testing or dismantling. In addition to the other LIMITATIONS provisions in this Agreement, Client agrees to assume all the risk for all conditions which are concealed from view at the time of the inspection or exist in any area excluded from Inspection by the terms of this agreement. Maintenance and other items may be discussed but will NOT form a part of the inspection report. The following areas/items, systems and components are among those NOT INCLUDED in the scope of inspection:
If inspection is desired in any of the areas/items, systems or components listed above, then Client shall contact the appropriate professionals. (Some of the above items may be included in this inspection for additional fees-check with your inspector) If your inspector recommends consulting other specialized experts, client must do so at client’s expense. |
6. |
CLIENT UNDERSTANDS THAT THE INSPECTION AND THE INSPECTION REPORT DO NOT, IN ANY WAY, CONSTITUTE A/AN: (1) GUARANTEE, (2) WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, (3) EXPRESS OR IMPLIED WARRANTY, OR (4) INSURANCE POLICY. ADDITIONALLY, NEITHER THE INSPECTION NOR THE INSPECTION REPORT IS SUITABLE FOR ANY REAL ESTATE TRANSFER DISCLOSURES THAT MAY BE REQUIRED BY LAW. |
7. |
The written report to be prepared by Company shall be considered the final and exclusive findings of Company of the structure. Client understands and agrees that Client will not rely on any oral statements made by the inspector prior or subsequent to the issuance of the written Inspection Report. Client further understands and agrees Company reserves the right to modify the inspection report for a period of time that shall not exceed two business days after the inspection report has first been delivered to the Client. |
8. |
LIMITATION ON LIABILITY: It is agreed that the Company, its employees, officers, owners, and heirs, are not in anyway insurers of the property inspected and that payments for the inspection services provided herein are based solely upon the value of those services, and it is not the intention of the parties that the Company assume responsibility: (1) for any loss occasioned by malfeasance or misfeasance in the performance of the services under this Agreement, (2) for any loss or damage sustained through burglary, theft, robbery, fire or other cause, or (3) for any liability on the part of the Company by virtue of this Agreement or because of the relationship hereby established. If there shall, notwithstanding the above provision, at any time be, or arise, any liability on the part of the Company by virtue of this Agreement, or because of the relationship hereby established, whether due to the negligence, omission, breach of contract, misrepresentation of the Company or otherwise, such liability is, and shall be limited to, a sum equal to the price charged for the inspection service, which sum shall be paid and received as liquidated damages. Such liability is herein set forth as liquidated damages and not as a penalty, and this liability shall be complete and exclusive. THE COMPANY MAKES NO WARRANTIES, EXPRESS OR IMPLIED, AND ANY SUCH WARRANTY IS SPECIFICALLY EXCLUDED AND DISCLAIMED. |
9. |
DISPUTES: Client understands and agrees that any claim for failure to accurately report the visually discernible conditions at the subject property, shall be made in writing and reported to the inspector within ten business days of discovery. Client further agrees that, with exception of emergency conditions, Client or Client’s agents, employees or independent contractors will make NO alterations, modifications or repairs to the claimed discrepancy prior to a re-inspection by the Inspector. Client understands and agrees that any failure to notify the Inspector as stated above shall constitute a waiver of any and all claims for said failure to accurately report the condition in question. |
10. |
ABRITRATION: It is agreed that any dispute, controversy, interpretation or claim, including claims for, but not limited to, breach of contract, any form of negligence, fraud or misrepresentation arising out of, from or related to, this contract or arising out of, from or related to, the inspection or inspection report, shall be submitted to final and binding arbitration under the Rules and Procedures of the Expedited Arbitration of Home Inspection Disputes of Construction Arbitration Services, Inc. The decision of the arbitrator appointed hereunder shall be final and binding and judgment on the award may be entered in any court of competent jurisdiction. CLIENT UNDERSTANDS AND AGREES THAT IN ANY SUCH ARBITRATION, ALL OF THE LIMITATIONS OF LIABILITY PROVISIONS OF THIS AGREEMENT SHALL APPLY. |
11. |
Any legal action, including the arbitration proceeding more specifically described above, including, but not limited to, those proceedings involving claims sounding in tort or contract, against the Company, or its officers, agents or employees, must be brought within one (1) year from the date of the inspection, or same will be deemed waived and forever barred. Time is expressly of the essence herein. This time period may be shorter than otherwise provided for by law. It is agreed and understood that the arbitrator, in rendering any decision above, is to apply the laws of the State of California. |
12. |
ATTORNEY’S FEES: The prevailing party in any dispute arising out of this agreement, the inspection, or Report(s) shall be awarded all reasonable attorney’s fees, arbitrator fees and other costs. |
13. |
Client understands and agrees that if he or she is not present at the time of the inspection or do not sign this Inspection Agreement that this Agreement will become part of the Inspection Report, and therefore delivery of the Inspection Report to the Client (by mail, in person or via internet) will constitute acceptance of ALL the terms and conditions of this Agreement. |
14. |
SEVERABILITY: If any portion of this Agreement is found to be invalid or unenforceable by any court or arbitrator the remaining terms shall remain in full force and effect between the parties. |
15. |
PAYMENT:Payment is due at time of inspection. A 10% late fee (per month) will be charged for all late payments. All costs, including but not limited to, collections, liens & legal fees to recover past due payments will be added to the customer final bill. A $50.00 fee will be added to all returned checks. |
16. |
ENTIRE CONTRACT: This Agreement represents the entire agreement
between the parties. No oral agreements, understandings or
representations shall change, modify or amend any part of this
agreement No change or modification shall be enforceable against
any party unless such changes or modifications are in writing and
signed by the parties. This Agreement shall be binding upon and
inure to the parties hereto and their spouses, heirs, executors,
administrators, successors, assigns and representatives of any kind
whatsoever. |
I have read, understand and agree to all the terms and conditions of this contract and to pay the fee listed above.
Dated_________________
Signature of Client_____________________________________________
Bill Smith
(One signature binds all)Printed Name of Client:________________________________________
Dated 7/29/2010
For the Company Daniel D. Weinberg