Eagles Eye Home Inspection, LLC tm
Eagles Eye Home Inspection, LLC tm Doe

Inspection Report

Mr. John Doe

Property Address:
2300 Sample St
Decatur Georgia 30032

 

Eagles Eye Home Inspection, LLC tm

Quinton Goodrum
950 Eagles Landing Pkwy. Suite 134
Stockbridge, Georgia 30281
770-855-3073
1-888-523-6094

Top Table of Contents Bottom

Table of Contents

Top Table of Contents Bottom
Date: 6/24/2018 Time: 08:30 AM Report ID: Sample2300
Property:
2300 Sample St
Decatur Georgia 30032
Customer:
Mr. John Doe
Real Estate Professional:

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.

Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.

Not Present (NP) = This item, component or unit is not in this home or building.

Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.

In Attendance:
Customer

Type of building:
Single Family (2 story)

Approximate age of building:
Over 25 Years

Temperature:
Over 65 (F) = 18 (C)

Weather:
Clear

Ground/Soil surface condition:
Damp

Rain in last 3 days:
Yes

  

Top Table of Contents Bottom
1.  Roofing
The home inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components. The home inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing. The home inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors.
  IN NI NP RR
1.0 Roof Coverings    
1.1 Flashings      
1.2 Skylights, Chimneys and Roof Penetrations      
1.3 Roof Drainage Systems    
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR
Styles & Materials
Roof Covering:
3-Tab fiberglass
Viewed roof covering from:
Ladder
Walked roof
Sky Light(s):
None
Estimated AGE OF ROOF:
Over 25 years old
   
Comments:
1.0 One or more shingles damaged/missing and have hail and wind damaged. Recommend having a qualified roofing contractor evaluate and repair/replace/install a new roof.
1.0 Item 1(Picture)
1.0 Item 2(Picture)
1.0 Item 3(Picture)
1.0 Item 4(Picture)
1.3 One or more gutters missing around the home. Recommend having a qualified contractor evaluate and repair/replace.
1.3 Item 1(Picture)
The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
2.  Exterior
The home inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The home inspector shall: Describe wall cladding materials; Operate all entryway doors and a representative number of windows; Operate garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components where deterioration is suspected. The home inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks. The home inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility.
  IN NI NP RR
2.0 Wall Cladding Flashing and Trim    
2.1 Doors (Exterior)      
2.2 Windows    
2.3 Decks, Balconies, Stoops, Steps, Areaways, Porches, Patio/Cover and Applicable Railings    
2.4 Vegetation, Grading, Drainage, Driveways, Patio Floor, Walkways and Retaining Walls (With respect to their effect on the condition of the building)      
2.5 Eaves, Soffits and Fascias    
2.6 Wood Infeatation Insects    
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR
Styles & Materials
Siding Style:
Lap
Siding Material:
Cedar
Exterior Entry Doors:
Steel
Appurtenance:
Covered porch
Sidewalk
Driveway:
Concrete
 
Comments:
2.0 One or more siding boards around the home has wood rot/wood decay/damaged. Recommend having a qualified contractor evaluate and repair/replace.
2.0 Item 1(Picture)
2.2 One or more windows and window frames around the home is damaged/not operating correctly and have wood rot/wood decay. Recommend having a qualified contractor evaluate and repair/replace.
2.2 Item 1(Picture)
2.2 Item 2(Picture)
2.2 Item 3(Picture)
2.2 Item 4(Picture)
2.3 Decking around the home shows signs of settlement and wood rot/wood decay. Recommend having a qualified contractor evaluate and repair/replace and rebuild wrap around porch if needed.

One or more sections on front porch ceilings shows signs of active water intrusion. Recommend having a qualified contractor repair/replace roofing shingles,flashing,repair damaged/rotting wood and sheathing as needed.

2.3 Item 1(Picture)
2.3 Item 2(Picture)
2.3 Item 3(Picture)
2.3 Item 4(Picture)
2.5 One or more section around the home have wood rot/wood decay on soffits and fascias boards around the home. One or more gutters missing around the home. Recommend having a qualified contractor evaluate and repair/replace.
2.5 Item 1(Picture)
2.5 Item 2(Picture)
2.6 Recommend asking seller if home has a termite bond and if so, recommend asking seller if termite bond is transferable to new owner. If not recommend having home treated and protected from wood destroying insects/termites.
The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
3.  Interiors
The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installed cabinets; and A representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments.
Enclosed garage photo
  IN NI NP RR
3.0 Ceilings      
3.1 Walls      
3.2 Floors    
3.3 Steps, Stairways, Balconies and Railings      
3.4 Counters and Cabinets (representative number)      
3.5 Doors (representative number)    
3.6 Windows (representative number)      
3.7 Mildew/mold like substance/stains    
3.8 Moisture Control      
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR
Styles & Materials
Ceiling Materials:
Sheet-Rock
Walls:
Sheet-Rock
Floor Covering(s):
Carpet
Hardwood T&G
Linoleum
Interior Doors:
Hollow core
Window Types:
Single-hung
Casement
Window Manufacturer:
UNKNOWN
Cabinetry:
Veneer
Countertop:
Laminate
 
Comments:
3.0 One or more water stains found on one or more ceilings inside the home. Recommend having a qualified contractor evaluate and repair/replace and prevent any water intrusion.

One or more minor/medium cracks found on ceilings. Repair/Replace.

3.0 Item 1(Picture)
3.0 Item 2(Picture)
3.2 One or more floors inside home shows signs of settlement and warping/un-leveled. Recommend having a qualified contractor evaluate and repair/replace.
3.2 Item 1(Picture)
3.2 Item 2(Picture)
3.5 One or more doors binding. Recommend having a qualified contractor evaluate and repair/replace.
3.7 Mold and mildew found on one or more sections of walls in laundry room. Recommend having a qualified contractor evaluate and repair/replace and repair any plumbing leaks/water intrusion that caused the issue.
3.7 Item 1(Picture)
3.7 Item 2(Picture)
3.7 Item 3(Picture)
The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
4.  Structural Components
The Home Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilings and roof. The home inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The home inspector shall: Probe structural components where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to: Enter any area or perform any procedure that may damage the property or its components or be dangerous to or adversely effect the health of the home inspector or other persons.
  IN NI NP RR
4.0 Foundations, Basement and Crawlspace (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.)    
4.1 Walls (Structural)      
4.2 Columns or Piers      
4.3 Floors (Structural)    
4.4 Ceilings (Structural)      
4.5 Roof Structure and Attic    
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR
Styles & Materials
Foundation:
Masonry block
Method used to observe Crawlspace:
Crawled
Limited access
Floor Structure:
2 X 8
Wood joists
Wall Structure:
2 X 4 Wood
Columns or Piers:
Wood piers
Masonry block
Ceiling Structure:
Not visible
Roof Structure:
Engineered wood trusses
Plywood
Sheathing
Roof-Type:
Gable
Method used to observe attic:
Walked
Attic info:
Pull Down stairs
   
Comments:
4.0 Inspector noticed signs of some water intrusion entering into crawl space. Recommend having a qualified contractor evaluate and repair/replace.

Vapor barrier is missing. Recommend installing 6 mil polyethylene with seams overlapped at least 24" so no soil is exposed in the crawlspace.

No insulation under floor in crawl space. Recommend installing R19 or better (6" thick fiberglass batt) insulation below floor for energy efficiency.

Inspector also notices some mildew/mold like stains on joist and crawl space surfaces. Repair/Replace as needed.

4.0 Item 1(Picture)
4.0 Item 2(Picture)
4.3 Recommend having a qualified contractor evaluate and re-support floor structure to correct and repair settlement problems.
4.3 Item 1(Picture)
4.5 Inspector noticed signs of water intrusion entering into attic. Recommend having roof replaced.

Cover plate(s) are missing from one or more electric junction boxes inside attic. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard and poses a risk of both fire and shock. Recommend installing cover plates over junction boxes where missing.

4.5 Item 1(Picture)
4.5 Item 2(Picture)
4.5 Item 3(Picture)
The structure of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
5.  Plumbing System
The home inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; and Sump pumps. The home inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of main water supply shutoff device. The home inspector shall operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The home inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials.
  IN NI NP RR
5.0 Plumbing Drain, Waste and Vent Systems    
5.1 Plumbing Water Supply, Distribution System and Fixtures      
5.2 Hot Water Systems, Controls, Chimneys, Flues and Vents    
5.3 Main Water Shut-off Device (Describe location)      
5.4 Fuel Storage and Distribution Systems (Interior fuel storage, piping, venting, supports, leaks)      
5.5 Main Fuel Shut-off (Describe Location)      
5.6 Septic Tank System    
5.7 Water pressure      
5.8 Well Water    
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR
Styles & Materials
Water Source:
Well
Public
Water Filters:
None
Plumbing Water Supply (into home):
Not visible
Plumbing Water Distribution (inside home):
Copper
PVC
Washer Drain Size:
Not visible
Plumbing Waste:
PVC
Water Heater Power Source:
Electric
Water Heater Capacity:
50 Gallon (2-3 people)
Water Heater Location:
Utility Room
WH Manufacturer:
WHIRLPOOL
Extra Info : SN: 043817236
Septic Tank:
Below Ground, Not Inspected
Age Of Water Heater:
15 to 20 years old
Comments:
5.0 Recommend having septic tank inspected. Recommend pumping tank if last pumped more than 3 years ago.
5.2 The water heater's temperature-pressure relief valve drain line is missing. This poses a danger of  scalding if someone is standing next to the water heater when the valve releases. A qualified plumber  should install a drain line as per standard building practices. For example, extending to within 6" from the floor, or routed so as to drain outside.


Substandard wiring was found for the water heater's power supply. This is both a fire and a shock hazard. Recommend having a qualified, licensed electrician evaluate and make repairs as necessary. Typically, electric water heater power supply wires require flexible, armored "BX" conduit, bushing(s) and possibly a covered junction box.


The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be at this age or older. Recommend budgeting for a replacement in the near future.

It appears that water heater has been converted to electric due to above missing vent flue hole above water heater.

5.2 Item 1(Picture)
5.2 Item 2(Picture)
5.2 Item 3(Picture)
5.3 Located inside crawl space.
5.5 Located on right side of home.
5.6 Recommend having septic tank pump and evaluated by a qualified septic tank contractor.
5.7 Plumbing pipe has a leak/damaged. inspector could not check water pressure at the time of inspection.
5.8 If buyer would like to use well water for drinking. Recommend having well water tested before drinking.
The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
6.  Electrical System
The home inspector shall observe: Service entrance conductors; Service equipment, grounding equipment, main over current device, and main and distribution panels; Amperage and voltage ratings of the service; Branch circuit conductors, their over current devices, and the compatibility of their ampacities and voltages; The operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interior plumbing fixtures, and all receptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and Smoke detectors. The home inspector shall describe: Service amperage and voltage; Service entry conductor materials; Service type as being overhead or underground; and Location of main and distribution panels. The home inspector shall report any observed aluminum branch circuit wiring. The home inspector shall report on presence or absence of smoke detectors, and operate their test function, if accessible, except when detectors are part of a central system. The home inspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate any over current device except ground fault circuit interrupters; Dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; Security system devices, heat detectors, or carbon monoxide detectors; Telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or Built-in vacuum equipment.
  IN NI NP RR
6.0 Service Entrance Conductors      
6.1 Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels      
6.2 Branch Circuit Conductors, Overcurrent Devices and Compatability of their Amperage and Voltage      
6.3 Connected Devices and Fixtures (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)    
6.4 Polarity and Grounding of Receptacles within 6 feet of interior plumbing fixtures, all receptacles in garage, carport and exterior walls of inspected structure      
6.5 Location of Main and Distribution Panels      
6.6 Smoke Detectors      
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR
Styles & Materials
Electrical Service Conductors:
Overhead service
220 volts
Panel Capacity:
200 AMP
Panel Type:
Circuit breakers
Electric Panel Manufacturer:
GENERAL ELECTRIC
Branch wire 15 and 20 AMP:
Copper
Wiring Methods:
Romex
Comments:
6.3 Five or more open ground, 3-pronged receptacles were found in front room/family room. This is a safety hazard and poses a risk of electric shock. Recommend that a qualified, licensed electrician evaluate and make repairs as necessary. For example, replacing receptacles or correcting wiring circuits.

No ground fault circuit interrupter (GFCI) devices (receptacles or circuit breakers) are visible in one or more kitchen or bathrooms. GFCI devices help prevent electric shocks in areas that may have water present. Recommend having a qualified, licensed electrician install GFCI protection for receptacles over counter tops and around sinks as per standard building practices.

6.3 Item 1(Picture)
6.5 Located on laundry room wall.
6.6 The smoke detector should be tested at common hallway to bedrooms upon moving in to home.
The electrical system of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
7.  Heating / Central Air Conditioning
The home inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to home; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The home inspector shall describe: Energy source; and Heating equipment and distribution type. The home inspector shall operate the systems using normal operating controls. The home inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The home inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.
No HVAC system or ductwork installed at the home. Inspector only noticed one or more window units.
  IN NI NP RR
7.0 Heating Equipment    
7.1 Normal Operating Controls    
7.2 Automatic Safety Controls    
7.3 Distribution Systems (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)    
7.4 Presence of Installed Heat Source in Each Room    
7.5 Chimneys, Flues and Vents (for fireplaces, gas water heaters or heat systems)    
7.6 Solid Fuel Heating Devices (Fireplaces, Woodstove)    
7.7 Gas/LP Firelogs and Fireplaces    
7.8 Cooling and Air Handler Equipment    
7.9 Normal Operating Controls    
7.10 Presence of Installed Cooling Source in Each Room    
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR
Styles & Materials
Heat Type:
None
Extra Info : Home has a propane tank in backyard. It's posiable that home used propane to heat the home.
Energy Source:
Propane
Number of Heat Systems (excluding wood):
None
Heat System Brand:
NONE
Ductwork:
Non-insulated
Types of Fireplaces:
None
Cooling Equipment Type:
Window AC
Number of AC Only Units:
None
Central Air Brand:
NONE
Comments:
7.0 Home has no HVAC system installed. Recommend having a qualified HVAC contractor evaluate and installed a HVAC system to heat and cool the home on the upper and lower level. It appears that home used propane to heat the home in one or more areas.
The heating and cooling system of this home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
8.  Insulation and Ventilation
The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics and foundation areas; Kitchen, bathroom, and laundry venting systems; and the operation of any readily accessible attic ventilation fan, and, when temperature permits, the operation of any readily accessible thermostatic control. The home inspector shall describe: Insulation in unfinished spaces; and Absence of insulation in unfinished space at conditioned surfaces. The home inspector shall: Move insulation where readily visible evidence indicates the need to do so; and Move insulation where chimneys penetrate roofs, where plumbing drain/waste pipes penetrate floors, adjacent to earth filled stoops or porches, and at exterior doors. The home inspector is not required to report on: Concealed insulation and vapor retarders; or Venting equipment that is integral with household appliances.
  IN NI NP RR
8.0 Insulation in Attic      
8.1 Vapor Retarders (in Crawlspace or basement)    
8.2 Ventilation of Attic and Foundation Areas      
8.3 Venting Systems (Kitchens, Baths and Laundry)    
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR
Styles & Materials
Attic Insulation:
Batt
Fiberglass
R-19 or better
Ventilation:
Gable vents
Exhaust Fans:
Fan only
Dryer Power Source:
220 Electric
Dryer Vent:
Metal
Floor System Insulation:
NONE
Comments:
8.1 Vapor barrier is missing. Recommend installing 6 mil polyethylene with seams overlapped at least 24" so no soil is exposed in the crawlspace.
8.1 Item 1(Picture)
8.3 One or more bathrooms with a shower don't have an exhaust fan installed. Even if a window that opens exists, it may not provide adequate ventilation, especially during cold weather when the window is less likely to be opened. Recommend having a qualified contractor install an exhaust fan, duct and vent cap as per standard building practices in bathrooms with showers where missing.
8.3 Item 1(Picture)
The insulation and ventilation of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Venting of exhaust fans or clothes dryer cannot be fully inspected and bends or obstructions can occur without being accessible or visible (behind wall and ceiling coverings). Only insulation that is visible was inspected. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
9.  Built-In Kitchen Appliances
The home inspector shall observe and operate the basic functions of the following kitchen appliances: Permanently installed dishwasher, through its normal cycle; Range, cook top, and permanently installed oven; Trash compactor; Garbage disposal; Ventilation equipment or range hood; and Permanently installed microwave oven. The home inspector is not required to observe: Clocks, timers, self-cleaning oven function, or thermostats for calibration or automatic operation; Non built-in appliances; or Refrigeration units. The home inspector is not required to operate: Appliances in use; or Any appliance that is shut down or otherwise inoperable.
  IN NI NP RR
9.0 Dishwasher      
9.1 Ranges/Ovens/Cooktops      
9.2 Range Hood (s)      
IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR
Styles & Materials
Dishwasher Brand:
NONE
Disposer Brand:
NONE
Exhaust/Range hood:
NONE
Range/Oven:
ROPER
Built in Microwave:
NONE
Trash Compactors:
NONE
The built-in appliances of the home were inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom

Summary


Eagles Eye Home Inspection, LLC tm

950 Eagles Landing Pkwy. Suite 134
Stockbridge, Georgia 30281
770-855-3073
1-888-523-6094

Customer
Mr. John Doe

Address
2300 Sample St
Decatur Georgia 30032

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the home. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

1.  Roofing
1.0  Roof Coverings  
Inspected, Repair or Replace
One or more shingles damaged/missing and have hail and wind damaged. Recommend having a qualified roofing contractor evaluate and repair/replace/install a new roof.
$2,501 - $5,000

1.0 Item 1(Picture)
1.0 Item 2(Picture)
1.0 Item 3(Picture)
1.0 Item 4(Picture)
1.3  Roof Drainage Systems  
Inspected, Repair or Replace
One or more gutters missing around the home. Recommend having a qualified contractor evaluate and repair/replace.
$501 - $1000

1.3 Item 1(Picture)

2.  Exterior
2.0  Wall Cladding Flashing and Trim  
Inspected, Repair or Replace
One or more siding boards around the home has wood rot/wood decay/damaged. Recommend having a qualified contractor evaluate and repair/replace.
$250 - $500

2.0 Item 1(Picture)
2.2  Windows  
Inspected, Repair or Replace
One or more windows and window frames around the home is damaged/not operating correctly and have wood rot/wood decay. Recommend having a qualified contractor evaluate and repair/replace.
$1,000 - $2,500

2.2 Item 1(Picture)
2.2 Item 2(Picture)
2.2 Item 3(Picture)
2.2 Item 4(Picture)
2.3  Decks, Balconies, Stoops, Steps, Areaways, Porches, Patio/Cover and Applicable Railings  
Inspected, Repair or Replace
Decking around the home shows signs of settlement and wood rot/wood decay. Recommend having a qualified contractor evaluate and repair/replace and rebuild wrap around porch if needed.

One or more sections on front porch ceilings shows signs of active water intrusion. Recommend having a qualified contractor repair/replace roofing shingles,flashing,repair damaged/rotting wood and sheathing as needed.

$1,000 - $2,500

2.3 Item 1(Picture)
2.3 Item 2(Picture)
2.3 Item 3(Picture)
2.3 Item 4(Picture)
2.5  Eaves, Soffits and Fascias  
Inspected, Repair or Replace
One or more section around the home have wood rot/wood decay on soffits and fascias boards around the home. One or more gutters missing around the home. Recommend having a qualified contractor evaluate and repair/replace.
$250 - $500

2.5 Item 1(Picture)
2.5 Item 2(Picture)
2.6  Wood Infeatation Insects  
Inspected, Repair or Replace
Recommend asking seller if home has a termite bond and if so, recommend asking seller if termite bond is transferable to new owner. If not recommend having home treated and protected from wood destroying insects/termites.

3.  Interiors
3.2  Floors  
Inspected, Repair or Replace
One or more floors inside home shows signs of settlement and warping/un-leveled. Recommend having a qualified contractor evaluate and repair/replace.
$2,501 - $5,000

3.2 Item 1(Picture)
3.2 Item 2(Picture)
3.5  Doors (representative number)  
Inspected, Repair or Replace
One or more doors binding. Recommend having a qualified contractor evaluate and repair/replace.
$101 - $250
3.7  Mildew/mold like substance/stains  
Inspected, Repair or Replace
Mold and mildew found on one or more sections of walls in laundry room. Recommend having a qualified contractor evaluate and repair/replace and repair any plumbing leaks/water intrusion that caused the issue.
$501 - $1000

3.7 Item 1(Picture)
3.7 Item 2(Picture)
3.7 Item 3(Picture)

4.  Structural Components
4.0  Foundations, Basement and Crawlspace (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.)  
Inspected, Repair or Replace
Inspector noticed signs of some water intrusion entering into crawl space. Recommend having a qualified contractor evaluate and repair/replace.

Vapor barrier is missing. Recommend installing 6 mil polyethylene with seams overlapped at least 24" so no soil is exposed in the crawlspace.

No insulation under floor in crawl space. Recommend installing R19 or better (6" thick fiberglass batt) insulation below floor for energy efficiency.

Inspector also notices some mildew/mold like stains on joist and crawl space surfaces. Repair/Replace as needed.

$1,000 - $2,500

4.0 Item 1(Picture)
4.0 Item 2(Picture)
4.3  Floors (Structural)  
Inspected, Repair or Replace
Recommend having a qualified contractor evaluate and re-support floor structure to correct and repair settlement problems.
$2,501 - $5,000

4.3 Item 1(Picture)
4.5  Roof Structure and Attic  
Inspected, Repair or Replace
Inspector noticed signs of water intrusion entering into attic. Recommend having roof replaced.

Cover plate(s) are missing from one or more electric junction boxes inside attic. They are intended to contain fire and prevent electric shock from exposed wires. This is a safety hazard and poses a risk of both fire and shock. Recommend installing cover plates over junction boxes where missing.

$5,000 - $10,000

4.5 Item 1(Picture)
4.5 Item 2(Picture)
4.5 Item 3(Picture)

5.  Plumbing System
5.0  Plumbing Drain, Waste and Vent Systems  
Inspected, Repair or Replace
Recommend having septic tank inspected. Recommend pumping tank if last pumped more than 3 years ago.
$250 - $500
5.2  Hot Water Systems, Controls, Chimneys, Flues and Vents  
Inspected, Repair or Replace
The water heater's temperature-pressure relief valve drain line is missing. This poses a danger of  scalding if someone is standing next to the water heater when the valve releases. A qualified plumber  should install a drain line as per standard building practices. For example, extending to within 6" from the floor, or routed so as to drain outside.


Substandard wiring was found for the water heater's power supply. This is both a fire and a shock hazard. Recommend having a qualified, licensed electrician evaluate and make repairs as necessary. Typically, electric water heater power supply wires require flexible, armored "BX" conduit, bushing(s) and possibly a covered junction box.


The estimated useful life for most water heaters is 8 to 12 years. This water heater appears to be at this age or older. Recommend budgeting for a replacement in the near future.

It appears that water heater has been converted to electric due to above missing vent flue hole above water heater.

$501 - $1000

5.2 Item 1(Picture)
5.2 Item 2(Picture)
5.2 Item 3(Picture)
5.6  Septic Tank System  
Inspected, Repair or Replace
Recommend having septic tank pump and evaluated by a qualified septic tank contractor.
$250 - $500

6.  Electrical System
6.3  Connected Devices and Fixtures (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)  
Inspected, Repair or Replace
Five or more open ground, 3-pronged receptacles were found in front room/family room. This is a safety hazard and poses a risk of electric shock. Recommend that a qualified, licensed electrician evaluate and make repairs as necessary. For example, replacing receptacles or correcting wiring circuits.

No ground fault circuit interrupter (GFCI) devices (receptacles or circuit breakers) are visible in one or more kitchen or bathrooms. GFCI devices help prevent electric shocks in areas that may have water present. Recommend having a qualified, licensed electrician install GFCI protection for receptacles over counter tops and around sinks as per standard building practices.

$101 - $250

6.3 Item 1(Picture)

8.  Insulation and Ventilation
8.1  Vapor Retarders (in Crawlspace or basement)  
Inspected, Repair or Replace
Vapor barrier is missing. Recommend installing 6 mil polyethylene with seams overlapped at least 24" so no soil is exposed in the crawlspace.
$250 - $500

8.1 Item 1(Picture)
8.3  Venting Systems (Kitchens, Baths and Laundry)  
Inspected, Repair or Replace
One or more bathrooms with a shower don't have an exhaust fan installed. Even if a window that opens exists, it may not provide adequate ventilation, especially during cold weather when the window is less likely to be opened. Recommend having a qualified contractor install an exhaust fan, duct and vent cap as per standard building practices in bathrooms with showers where missing.
$101 - $250

8.3 Item 1(Picture)


Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Quinton Goodrum
Top Table of Contents Bottom
  INVOICE

Eagles Eye Home Inspection, LLC tm
950 Eagles Landing Pkwy. Suite 134
Stockbridge, Georgia 30281
770-855-3073
1-888-523-6094
Inspected By:  Quinton Goodrum
Inspection Date: 6/24/2018
Report ID: Sample2300

Customer Info: Inspection Property:
Mr. John Doe
2300 Sample St
Warsaw New York 40567


Customer's Real Estate Professional:

 
2300 Sample St
Decatur Georgia 30032
 

Inspection Fee:

ServicePriceAmountSub-Total

Tax $0.00
Total Price $0.00

Payment Method: Check
Payment Status: Paid At Time Of Inspection
Note: