Date: 3/4/19 Time: 03:40 PM Report ID: Sample Report2019
Property:
123 Your House Drive
Fort Lauderdale FL 33312
Customer:
Ms. Jane Doe
Real Estate Professional:

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.

Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.

Not Present (NP) = This item, component or unit is not in this home or building.

Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.

Accessibility Disclaimer = This home is occupied with furnishings, storage items, property, etc. with Limited visual accessibility. RMI Inspection Services and/or the licensed inspector is not responsible & makes no claims to those inaccessible areas.

Termite (WDO) Report Exclusion = RMI Inspection Services is not a pest control company and it's report and services are independent of the pest control inspection and services. The termite/pest control company performs that and only portion of the inspection as a 3rd party. Any & all issues arising from the termite(WDO) inspection is solely the pest control company responsibilities. RMI Inspections Services makes no claims or warranties.

In Attendance:
Client & Agent

Type of building:
Single Family (1 story)

Style of Home:
Ranch

Approximate age of building:
26 Years Old

Home Faces:
South

Temperature:
82 Degrees

Weather:
Clear

Ground/Soil surface condition:
Dry

Rain in last 3 days:
No

Radon Test:
Yes

Water Test:
No

Mold Testing:
Yes - See Inspector Lab Mold Analysis Report

Accessibility Disclaimer:
This home has accessibility issues. See Above Disclaimer

  

Top Table of Contents Bottom

1.  Roofing

The inspector shall inspect from ground level or eaves: The roof covering. The gutters. The downspouts. The vents, flashings, skylights, chimney and other roof penetrations. The general structure of the roof from the readily accessible panels, doors or stairs.

The inspector is not required to: Walk on any roof surface, predict the service life expectancy, inspect underground downspout diverter drainage pipes, remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces, move insulation, inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. Walk on any roof areas that appear, in the opinion of the inspector to be unsafe, and or cause damage. Perform a water test, warrant or certify the roof. Confirm proper fastening or installation of any roof material.

Concrete Tiles
Roof Ridge line
Drain Vent-line Roof Penetration
Styles & Materials
Roof Covering:
Concrete
Tile
Viewed roof covering from:
Walked roof
Sky Light(s):
None
Items
1.0 Roof Coverings
Comments: Inspected, Repair or Replace
(1)  

The roof covering is in very poor condition and is leaking. It has many signs that life expectancy has been reached. The roof appears to have many areas repairs were made. It comes to a point where repairs, damage and deteriorated roof needs to be re-roof. It is recommended that a new roof be installed. Note a roof in this condition will make it difficult to obtain home owners insurance.

1.0 Item 1(Picture) Roof Repairs Noted
1.0 Item 2(Picture) Cracked Tiles
1.0 Item 3(Picture) Cracked Tiles
1.0 Item 4(Picture) Cracked Tiles
1.0 Item 5(Picture) Signs Underlayment is Failing
1.0 Item 6(Picture) Poor Roof Repair Noted
(2)  

Tree limbs in contactor or hanging over the roof line should be removed. It causes premature wear of the roof covering and under layments. Have a licensed arborist and/or tree contactor trim or remove as needed.

1.0 Item 7(Picture) Tree Limbs
1.1 Flashings
Comments: Inspected
1.2 Skylights, Chimneys and Roof Penetrations
Comments: Inspected
1.3 Roof Drainage Systems
Comments: Inspected, Repair or Replace
 

Rain gutters are needed to prevent soil erosion. Have a licensed rain gutter contractor install as needed.

1.3 Item 1(Picture) Soil Erosion
The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom

2.  Exterior

The inspector shall inspect: The siding, flashing and trim. All exterior doors, decks, stoops, steps, stairs, porches, railings, eaves, soffits and fascias. And report as in need of repair any spacing between intermediate balusters, spindles, or rails for steps, stairways, balconies, and railings that permit the passage of an object greater than four inches in diameter. A representative number of windows. The vegetation, surface drainage and retaining walls when these are likely to adversely affect the structure. And describe the exterior wall covering.

The inspector is not required to: Inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting, Inspect items, including window and door flashings, which are not visible or readily accessible from the ground, Inspect geological, geotechnical, hydrological and/or soil conditions, Inspect recreational facilities, playground equipment. Inspect seawalls, break-walls and docks, Inspect erosion control and earth stabilization measures, Inspect for safety type glass, Inspect underground utilities, Inspect underground items, Inspect wells or springs, Inspect solar, wind or geothermal systems, Inspect swimming pools or spas, Inspect wastewater treatment systems septic systems or cesspools, Inspect irrigation or sprinkler systems, Inspect drain fields or drywells, Determine the integrity of multi-pane window glazing or the thermal window seals.

Right Elevation
Left Elevation
Rear Elevation
Rear Elevation
Driveway
Walkway
Walkway Leading to Entry Doors
Front Entry
Styles & Materials
Siding Style:
Cement stucco
Siding Material:
Masonry
Exterior Entry Doors:
Steel
Appurtenance:
Covered porch
Driveway:
Pavers(Brick)
 
Items
2.0 Wall Cladding Flashing and Trim
Comments: Inspected
2.1 Doors (Exterior)
Comments: Inspected, Repair or Replace
 

In the hallway bathroom the exterior door that leads to outside patio area is oxidized and is very difficult to open or close door properly. Have a licensed door contractor repair or replace as needed.

2.1 Item 1(Picture) Rear Bathroom Door
2.2 Windows
Comments: Inspected
2.3 Decks, Balconies, Stoops, Steps, Areaways, Porches, Patio/Cover and Applicable Railings
Comments: Inspected
2.4 Vegetation, Grading, Drainage, Driveways, Patio Floor, Walkways and Retaining Walls (With respect to their effect on the condition of the building)
Comments: Inspected, Repair or Replace
 

On the left side of the paved driveway there are signs of uneven pavers. Have a licensed stone or paving contactor repair or replace as needed.

2.4 Item 1(Picture) Driveway
2.4 Item 2(Picture) Driveway
2.5 Eaves, Soffits and Fascias
Comments: Inspected, Repair or Replace
 

Many of the fascia boards and soffits throughout the home are deteriorated and have rot.Have a licensed roofing contractor repair or replace as needed.

2.5 Item 1(Picture) Fascia Boards
2.5 Item 2(Picture) Fascia Boards
2.5 Item 3(Picture) Fascia Boards
2.6 Additional Buildings on Property
Comments: Not Present
The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom

3.  Structural Components

The inspector shall inspect: The basement. The foundation. The crawlspace. The visible structural components. Any present conditions or clear indications of active water penetration observed by the inspector. And report any general indications of foundation movement that are observed by the inspector, such as but not limited to sheetrock cracks, brick cracks, out-of-square door frames or floor slopes.

The inspector is not required to: Enter any crawlspaces that are not readily accessible or where entry could cause damage or pose a hazard to the inspector, Move stored items or debris, Operate sump pumps with inaccessible floats, Identify size, spacing, span, location or determine adequacy of foundation bolting, bracing, joists, joist spans or support systems, Provide any engineering or architectural service, Report on the adequacy of any structural system or component.

Roof Trusses and Supporting Members
Styles & Materials
Foundation:
Monolithic Concrete Slab
Method used to observe Crawlspace:
No crawlspace
Floor Structure:
Slab
Wall Structure:
Masonry
Columns or Piers:
Masonry block
Ceiling Structure:
2X4
Roof Structure:
Engineered wood trusses
Plywood
Sheathing
Roof-Type:
Hip
Method used to observe attic:
From entry
Inaccessible
Attic info:
Light in attic
2 Attic Hatches
   
Items
3.0 Foundations, Basement and Crawlspace (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.)
Comments: Inspected
3.1 Walls (Structural)
Comments: Inspected
3.2 Columns or Piers
Comments: Inspected
3.3 Floors (Structural)
Comments: Inspected
3.4 Ceilings (Structural)
Comments: Inspected
3.5 Roof Structure and Attic
Comments: Inspected
The structure of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom

4.  Heating / Central Air Conditioning

The inspector shall inspect: The heating system and describe the energy source and heating method using normal operating controls. And report as in need of repair electric furnaces which do not operate. And report if inspector deemed the furnace inaccessible. The central cooling equipment using normal operating controls. The fireplace, and open and close the damper door if readily accessible and operable. Hearth extensions and other permanently installed components. And report as in need of repair deficiencies in the lintel, hearth and material surrounding the fireplace, including clearance from combustible materials.

The inspector is not required to: Inspect or evaluate interiors of flues or chimneys, fire chambers, heat exchangers, humidifiers, dehumidifiers, electronic air filters, solar heating systems, solar heating systems or fuel tanks. Inspect underground fuel tanks. Determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. Light or ignite pilot flames. Activate heating, heat pump systems, or other heating systems when ambient temperatures or when other circumstances are not conducive to safe operation or may damage the equipment. Override electronic thermostats. Evaluate fuel quality. Verify thermostat calibration, heat anticipation or automatic setbacks, timers, programs or clocks. Determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the cooling system. Inspect window units, through-wall units, or electronic air filters. Operate equipment or systems if exterior temperature is below 60 degrees Fahrenheit or when other circumstances are not conducive to safe operation or may damage the equipment. Inspect or determine thermostat calibration, heat anticipation or automatic setbacks or clocks. Examine electrical current, coolant fluids or gasses, or coolant leakage. Inspect the flue or vent system. Inspect the interior of chimneys or flues, fire doors or screens, seals or gaskets, or mantels. Determine the need for a chimney sweep. Operate gas fireplace inserts. Light pilot flames. Determine the appropriateness of such installation. Inspect automatic fuel feed devices. Inspect combustion and/or make-up air devices. Inspect heat distribution assists whether gravity controlled or fan assisted. Ignite or extinguish fires. Determine draft characteristics. Move fireplace inserts, stoves, or firebox contents. Determine adequacy of draft, perform a smoke test or dismantle or remove any component. Perform an NFPA inspection. Perform a Phase 1 fireplace and chimney inspection.

A/C Condensing Unit
A/C Condensing Unit Connections
A/C Condensing Unit Data Label 2/2005
Air Handler
Air Handler Data Label
Air Filter
Air Handler Cooling Fins
Styles & Materials
Heat Type:
Forced Air
Energy Source:
Electric
Number of Heat Systems (excluding wood):
One
Heat System Brand:
AMERICAN STANDARD
Ductwork:
Insulated
Filter Type:
Washable
Filter Size:
Adequate
Cooling Equipment Type:
Central Split Air Conditioning
Cooling Equipment Energy Source:
Electricity
Number of AC Only Units:
One
Central Air Brand:
AMERICAN STANDARD
 
Items
4.0 Heating Equipment
Comments: Inspected
4.1 Normal Operating Controls
Comments: Inspected
4.2 Automatic Safety Controls
Comments: Inspected
4.3 Distribution Systems (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)
Comments: Inspected, Repair or Replace
 

The A/C condensing unit securing bracket to the concrete slab is oxidized. Have a licensed HVAC contractor repair or replace as needed.

4.3 Item 1(Picture) A/C Securing Bracket
4.4 Presence of Installed Heat Source in Each Room
Comments: Inspected
4.5 Cooling and Air Handler Equipment
Comments: Inspected, Repair or Replace
(1)  

Note air handler wood water stains with microbial growth. Have a licensed mold remediator clean as needed.

4.5 Item 1(Picture) Air Handler
(2)  

Air vent, Air handler and register was swab for microbial growth. Air samples were taken throughout the home for mold evaluation due to roof leaks. See mold report.

4.5 Item 2(Picture) Air Handler
4.6 Normal Operating Controls
Comments: Inspected
4.7 Presence of Installed Cooling Source in Each Room
Comments: Inspected
The heating and cooling system of this home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom

5.  Plumbing System

The inspector shall: Verify the presence of and identify the location of the main water shutoff valve. Inspect the water heating equipment, including combustion air, venting, connections, energy sources, seismic bracing, and verify the presence or absence of temperature-pressure relief valves and/or Watts 210 valves. Flush toilets. Run water in sinks, tubs, and showers. Inspect the interior water supply including all fixtures and faucets. Inspect the drain, waste and vent systems, including all fixtures. Describe any visible fuel storage systems. Inspect the drainage sump pumps testing sumps with accessible floats. Inspect and describe the water supply, drain, waste and main fuel shut-off valves, as well as the location of the water main and main fuel shut-off valves. Inspect and determine if the water supply is public or private. Inspect and report as in need of repair deficiencies in the water supply by viewing the functional flow in two fixtures operated simultaneously. Inspect and report as in need of repair deficiencies in installation and identification of hot and cold faucets. Inspect and report as in need of repair mechanical drain-stops that are missing or do not operate if installed in sinks, lavatories and tubs. Inspect and report as in need of repair commodes that have cracks in the ceramic material, are improperly mounted on the floor, leak, or have tank components which do not operate.

The inspector is not required to: Light or ignite pilot flames. Determine the size, temperature, age, life expectancy or adequacy of the water heater. Inspect interiors of flues or chimneys, water softening or filtering systems, well pumps or tanks, safety or shut-of valves, floor drains, lawn sprinkler systems or fire sprinkler systems. Determine the exact flow rate, volume, pressure, temperature, or adequacy of the water supply. Determine the water quality or potability or the reliability of the water supply or source. Open sealed plumbing access panels. Inspect clothes washing machines or their connections. Operate any main, branch or fixture valve. Test shower pans, tub and shower surrounds or enclosures for leakage. Evaluate the compliance with local or state conservation or energy standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. Determine the effectiveness of anti-siphon, back-flow prevention or drain-stop devices. Determine whether there are sufficient clean-outs for effective cleaning of drains. Evaluate gas, liquid propane or oil storage tanks. Inspect any private sewage waste disposal system or component of. Inspect water treatment systems or water filters. Inspect water storage tanks, pressure pumps or bladder tanks. Evaluate time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. Evaluate or determine the adequacy of combustion air. Test, operate, open or close safety controls, manual stop valves and/or temperature or pressure relief valves. Examine ancillary systems or components, such as, but not limited to, those relating to solar water heating, hot water circulation.

Water Heater Tank
Water Heater Tank TPR Valve
Water Heater Tank Data Label 11/2014
Master Sink
Under Master Sink Drain & Connections
Master Tub
2nd Master Sink
Under Sink Drain & Connections
Master Toilet
Master Toilet Water Supply
Master Shower
Master Shower Floor Drain
Hallway Bathroom Sink
Under Sink Hallway Bathroom
Hallway Bathroom Toilet
Toilet Water Supply
Laundry Room Deep Sink
Under Sink Drain & Connections
Washer Connections & Drain
Hallway Bathroom Sinks
Under Sink Drain& Connections
Under 2nd Sink Drain & Connections
Hallway Bathroom
Toilet Water Supply
Hallway Bathroom Shower
Hallway Bathroom
Back Bathroom Sink
Under Sink Drain & Connections
Back Bathroom Toilet
Toilet Water Supply
Back Bathroom Tub
Back Bathroom Shower
Styles & Materials
Water Source:
Public
Water Filters:
(We do not inspect filtration systems)
Plumbing Water Supply (into home):
Copper
Plumbing Water Distribution (inside home):
Copper
Washer Drain Size:
2" Diameter
Plumbing Waste:
PVC
Water Heater Power Source:
Electric
Water Heater Capacity:
40 Gallon (1-2 people)
Water Heater Location:
Garage
WH Manufacturer:
RHEEM
   
Items
5.0 Plumbing Drain, Waste and Vent Systems
Comments: Inspected
5.1 Plumbing Water Supply, Distribution System and Fixtures
Comments: Inspected, Repair or Replace
 

The hallway bathroom shower diverter, the pull pin that changes from tub to shower water flow is stuck in the shower position. Have a licensed plumbing contractor repair or replace as needed. 

5.1 Item 1(Picture) Hallway Bathroom
5.2 Hot Water Systems, Controls, Chimneys, Flues and Vents
Comments: Inspected, Repair or Replace
 

The dryer exhaust is dirty and outside diverter is crushed. Have a licensed contractor clean and repair or replace as needed.

5.2 Item 1(Picture) Dryer Exhaust Vent
5.2 Item 2(Picture) Dryer Vent
5.3 Main Water Shut-off Device
Comments: Inspected
5.4 Sump Pump
Comments: Not Present
5.5 Cabinets
Comments: Inspected
The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom

6.  Electrical System

The inspector shall inspect: The service line. The meter box. The main disconnect. And determine the rating of the service amperage. Panels, breakers and fuses. The service grounding and bonding. A representative sampling of switches, receptacles, light fixtures, AFCI receptacles and test all GFCI receptacles and GFCI circuit breakers observed and deemed to be GFCI's during the inspection. And report the presence of solid conductor aluminum branch circuit wiring if readily visible. And report on any GFCI-tested receptacles in which power is not present, polarity is incorrect, the receptacle is not grounded, is not secured to the wall, the cover is not in place, the ground fault circuit interrupter devices are not properly installed or do not operate properly, or evidence of arcing or excessive heat is present. The service entrance conductors and the condition of their sheathing. The ground fault circuit interrupters observed and deemed to be GFCI's during the inspection with a GFCI tester. And describe the amperage rating of the service. And report the absence of smoke detectors. Service entrance cables and report as in need of repair deficiencies in the integrity of the insulation, drip loop, or separation of conductors at weatherheads and clearances.

The inspector is not required to: Insert any tool, probe or device into the main panel, sub-panels, downstream panel, or electrical fixtures. Operate electrical systems that are shut down. Remove panel covers or dead front covers if not readily accessible. Operate over current protection devices. Operate non-accessible smoke detectors. Measure or determine the amperage or voltage of the main service if not visibly labeled. Inspect the alarm system and components. Inspect the ancillary wiring or remote control devices. Activate any electrical systems or branch circuits which are not energized. Operate overload devices. Inspect low voltage systems, electrical de-icing tapes, swimming pool wiring or any time-controlled devices. Verify the continuity of the connected service ground. Inspect private or emergency electrical supply sources, including but not limited to generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. Inspect spark or lightning arrestors. Conduct voltage drop calculations. Determine the accuracy of breaker labeling. Inspect exterior lighting.

Electrical Meter & Service Electrical Panel
200 Amp Service
Open Service Panel
Interior Electrical Panel
Electrical Panel Cover
Panel Model Number
Opened Electrical Panel
Top of the Panel
Right Side Breakers
Left Side Panel Breakers
Styles & Materials
Electrical Service Conductors:
Below ground
Panel Capacity:
200 AMP
Panel Type:
Circuit breakers
Electric Panel Manufacturer:
CHALLENGER
Branch wire 15 and 20 AMP:
Copper
Wiring Methods:
Romex
Items
6.0 Service Entrance Conductors
Comments: Inspected
6.1 Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels
Comments: Inspected
6.2 Branch Circuit Conductors, Overcurrent Devices and Compatability of their Amperage and Voltage
Comments: Inspected
6.3 Connected Devices and Fixtures (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)
Comments: Inspected
6.4 Polarity and Grounding of Receptacles within 6 feet of interior plumbing fixtures, all receptacles in garage, carport and exterior walls of inspected structure
Comments: Inspected
6.5 Operation of GFCI (Ground Fault Circuit Interrupters)
Comments: Inspected
6.6 Operation of AFCI (ARC Fault Circuit Interrupters)
Comments: Not Present
6.7 Location of Main and Distribution Panels
Comments: Inspected
The electrical system of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom

7.  Insulation and Ventilation

The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics and foundation areas; Kitchen, bathroom, and laundry venting systems; and the operation of any readily accessible attic ventilation fan, and, when temperature permits, the operation of any readily accessible thermostatic control. The home inspector shall describe: Insulation in unfinished spaces; and Absence of insulation in unfinished space at conditioned surfaces. The home inspector shall: Move insulation where readily visible evidence indicates the need to do so; and Move insulation where chimneys penetrate roofs, where plumbing drain/waste pipes penetrate floors, adjacent to earth filled stoops or porches, and at exterior doors. The home inspector is not required to report on: Concealed insulation and vapor retarders; or Venting equipment that is integral with household appliances.
Batt Insulation
Styles & Materials
Attic Insulation:
Batt
Fiberglass
R-19 or better
Ventilation:
Soffit Vents
Exhaust Fans:
Fan
Dryer Power Source:
220 Electric
Dryer Vent:
Flexible Metal
 
Items
7.0 Insulation in Attic
Comments: Inspected, Repair or Replace
 

Inside attic moisture meter was utilized. Wet insulation was found. This will the drywall to remain wet and mold issues to occur. Have a licensed contractor repair or replace as needed.

7.0 Item 1(Picture) Wet Insulation
7.1 Ventilation of Attic and Foundation Areas
Comments: Inspected
7.2 Venting Systems (Kitchens, Baths and Laundry)
Comments: Inspected
7.3 Ventilation Fans and Thermostatic Controls in Attic
Comments: Inspected
7.4 Attic Issues
Comments: Inspected
The insulation and ventilation of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Venting of exhaust fans or clothes dryer cannot be fully inspected and bends or obstructions can occur without being accessible or visible (behind wall and ceiling coverings). Only insulation that is visible was inspected. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom

8.  Interiors

The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installed cabinets; and A representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments.

The inspector shall: Open and close a representative number of doors and windows. Inspect the walls, ceilings, steps, stairways, and railings. Inspect garage doors and garage door openers by operating first by remote (if available) and then by the installed automatic door control. And report as in need of repair any installed electronic sensors that are not operable or not installed at proper heights above the garage door. And report as in need of repair any door locks or side ropes that have not been removed or disabled when garage door opener is in use. And report as in need of repair any windows that are obviously fogged or display other evidence of broken seals.

The inspector is not required to: Inspect paint, wallpaper, window treatments or finish treatments. Inspect central vacuum systems. Inspect safety glazing. Inspect security systems or components. Evaluate the fastening of countertops, cabinets, sink tops and fixtures, or firewall compromises. Move furniture, stored items, or any coverings like carpets or rugs in order to inspect the concealed floor structure. Move drop ceiling tiles. Inspect or move any household appliances. Inspect or operate equipment housed in the garage except as otherwise noted. Verify or certify safe operation of any auto reverse or related safety function of a garage door. Operate or evaluate security bar release and opening mechanisms, whether interior or exterior, including compliance with local, state, or federal standards. Operate any system, appliance or component that requires the use of special keys, codes, combinations, or devices. Operate or evaluate self-cleaning oven cycles, tilt guards/latches or signal lights. Inspect microwave ovens or test leakage from microwave ovens. Operate or examine any sauna, steam-jenny, kiln, toaster, ice-maker, coffee-maker, can-opener, bread-warmer, blender, instant hot water dispenser, or other small, ancillary devices. Inspect elevators. Inspect remote controls. Inspect appliances. Inspect items not permanently installed. Examine or operate any above-ground, movable, freestanding, or otherwise non-permanently installed pool/spa, recreational equipment or self-contained equipment. Come into contact with any pool or spa water in order to determine the system structure or components. Determine the adequacy of spa jet water force or bubble effect. Determine the structural integrity or leakage of a pool or spa.

Entry Doors
Dining Room
Living Room
Hallway Leading to Front Bedroom
Master His Walk-in Closet
Master Hers Walk-in Closet
Master Bedroom
Master Bedroom
Front Bedroom
Front Bedroom Walk-in Closet
Hallway Bathroom
Hallway Bathroom Shower Not Checked Due to Personal Items in the Shower
Personal Items in the Shower
Laundry Room
Family Room
Hallway Leading to Bedrooms
Linen Closet
3rd Bedroom
3rd Bedroom Closet
4th Bedroom
4th Bedroom Closet
Hallway Bathroom
5th Bedroom
5th Bedroom Closet
Back Bathroom
Styles & Materials
Ceiling Materials:
Gypsum Board
Wall Material:
Gypsum Board
Floor Covering(s):
Tile
Interior Doors:
Hollow core
Raised panel
Window Types:
Single pane
Cabinetry:
Laminate
Countertop:
Laminate
   
Items
8.0 Ceilings
Comments: Inspected, Repair or Replace
 

Upon conversation with selling agent ceiling and roof have been repairs made. Moisture meter and infrared camera were utilized and indicate throughout the home there are still signs of roof leaks. Have a licensed contractor repair or replace as needed.

8.0 Item 1(Picture) Infrared Camera Utilized
8.0 Item 2(Picture) Moisture Meter
8.0 Item 3(Picture) Infrared Camera Indicating Moisture on Ceiling
8.1 Walls
Comments: Inspected
 

In the dining room the floor boards and wall show signs of water stains.This indicates that moisture intrusion did occur. Water restoration appears to have been completed according to realtor. Wall cavity testing should be done to confirm no mold issues in the walls. Moisture meter and infrared camera was utilized and readings are in the normal range.

8.1 Item 1(Picture) Dining Room Floor Boards
8.2 Floors
Comments: Inspected
8.3 Steps, Stairways, Balconies and Railings
Comments: Not Present
8.4 Counters and Cabinets (representative number)
Comments: Inspected
8.5 Doors (representative number)
Comments: Inspected, Repair or Replace
 

This hallway closet door is not on track. Have a licensed door contractor repair or replace as needed.

8.5 Item 1(Picture) Hallway Closet
8.6 Windows (representative number)
Comments: Inspected, Repair or Replace
 

Dining room picture window has a crack. Have a licensed window contractor repair or replace as needed.

8.6 Item 1(Picture) Dining Room
The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom

9.  Garage/Carport

Garage Door
Garage Door Opener
Garage Door Sensor
Garage Door Sensor
Garage
Garage Ceiling
Garage Door
Styles & Materials
Garage Door Type:
One automatic
Garage Door Material:
Metal
Auto-opener Manufacturer:
LIFT-MASTER
1/2 HORSEPOWER
Items
9.0 Garage/Carport Ceilings
Comments: Inspected
9.1 Garage/Carport Walls (including Firewall Separation)
Comments: Inspected
9.2 Garage/Carport Floor
Comments: Inspected
9.3 Garage/Carport Door(s)
Comments: Inspected
9.4 Occupant Door (from garage/carport to inside of home)
Comments: Inspected, Repair or Replace
 

The occupant door that leads from the garage should be on a self closing devise. Have a licensed door contractor repair or replace as needed.

9.4 Item 1(Picture) Occupant Door
9.5 Garage Door Operators
Comments: Inspected
9.6 Garage window (s)
Comments: Inspected
Top Table of Contents Bottom

10.  Kitchen and Built-in Appliances

Kitchen
Eat-in Kitchen
Microwave Oven
Refrigerator
Refrigerator Ir Temp.Check
Freezer Ir Temp. Check
Kitchen Sink
Kitchen Sink Sprayer
Under Kitchen Sink Drain & Connections
Kitchen Cabinets
Kitchen Cabinets & Drawers
Range Ir Temp.Check
Kitchen Island Cabinet & Drawers
Items
10.0 Dishwasher
Comments: Inspected
10.1 Ranges/Ovens/Cooktops
Comments: Inspected
10.2 Range Hood (s)
Comments: Inspected
10.3 Trash Compactor
Comments: Not Present
10.4 Food Waste Disposer
Comments: Inspected
10.5 Microwave Cooking Equipment
Comments: Inspected
10.6 Cabinets/Drawers
Comments: Inspected
10.7 Washer/Dryer
Comments: Inspected
10.8 Counter Top(s)
Comments: Inspected
10.9 Kitchen Sink(s)
Comments: Inspected
10.10 Cabinets
Comments: Inspected
10.11 Refrigerator
Comments: Inspected
The built-in appliances of the home were inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom

Summary


RMI Inspections

5931 Ravenswood Road Unit A17
Fort Lauderdale, Florida 33312
954-609-2315

Customer
Ms. Jane Doe

Address
123 Your House Drive
Fort Lauderdale FL 33312

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the home. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

1.  Roofing
1.0  Roof Coverings  
Inspected, Repair or Replace
(1)

The roof covering is in very poor condition and is leaking. It has many signs that life expectancy has been reached. The roof appears to have many areas repairs were made. It comes to a point where repairs, damage and deteriorated roof needs to be re-roof. It is recommended that a new roof be installed. Note a roof in this condition will make it difficult to obtain home owners insurance.


1.0 Item 1(Picture) Roof Repairs Noted
1.0 Item 2(Picture) Cracked Tiles
1.0 Item 3(Picture) Cracked Tiles
1.0 Item 4(Picture) Cracked Tiles
1.0 Item 5(Picture) Signs Underlayment is Failing
1.0 Item 6(Picture) Poor Roof Repair Noted
(2)

Tree limbs in contactor or hanging over the roof line should be removed. It causes premature wear of the roof covering and under layments. Have a licensed arborist and/or tree contactor trim or remove as needed.


1.0 Item 7(Picture) Tree Limbs
1.3  Roof Drainage Systems  
Inspected, Repair or Replace

Rain gutters are needed to prevent soil erosion. Have a licensed rain gutter contractor install as needed.


1.3 Item 1(Picture) Soil Erosion

2.  Exterior
2.1  Doors (Exterior)  
Inspected, Repair or Replace

In the hallway bathroom the exterior door that leads to outside patio area is oxidized and is very difficult to open or close door properly. Have a licensed door contractor repair or replace as needed.


2.1 Item 1(Picture) Rear Bathroom Door
2.4  Vegetation, Grading, Drainage, Driveways, Patio Floor, Walkways and Retaining Walls (With respect to their effect on the condition of the building)  
Inspected, Repair or Replace

On the left side of the paved driveway there are signs of uneven pavers. Have a licensed stone or paving contactor repair or replace as needed.


2.4 Item 1(Picture) Driveway
2.4 Item 2(Picture) Driveway
2.5  Eaves, Soffits and Fascias  
Inspected, Repair or Replace

Many of the fascia boards and soffits throughout the home are deteriorated and have rot.Have a licensed roofing contractor repair or replace as needed.


2.5 Item 1(Picture) Fascia Boards
2.5 Item 2(Picture) Fascia Boards
2.5 Item 3(Picture) Fascia Boards

4.  Heating / Central Air Conditioning
4.3  Distribution Systems (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)  
Inspected, Repair or Replace

The A/C condensing unit securing bracket to the concrete slab is oxidized. Have a licensed HVAC contractor repair or replace as needed.


4.3 Item 1(Picture) A/C Securing Bracket
4.5  Cooling and Air Handler Equipment  
Inspected, Repair or Replace
(1)

Note air handler wood water stains with microbial growth. Have a licensed mold remediator clean as needed.


4.5 Item 1(Picture) Air Handler
(2)

Air vent, Air handler and register was swab for microbial growth. Air samples were taken throughout the home for mold evaluation due to roof leaks. See mold report.


4.5 Item 2(Picture) Air Handler

5.  Plumbing System
5.1  Plumbing Water Supply, Distribution System and Fixtures  
Inspected, Repair or Replace

The hallway bathroom shower diverter, the pull pin that changes from tub to shower water flow is stuck in the shower position. Have a licensed plumbing contractor repair or replace as needed. 


5.1 Item 1(Picture) Hallway Bathroom
5.2  Hot Water Systems, Controls, Chimneys, Flues and Vents  
Inspected, Repair or Replace

The dryer exhaust is dirty and outside diverter is crushed. Have a licensed contractor clean and repair or replace as needed.


5.2 Item 1(Picture) Dryer Exhaust Vent
5.2 Item 2(Picture) Dryer Vent

7.  Insulation and Ventilation
7.0  Insulation in Attic  
Inspected, Repair or Replace

Inside attic moisture meter was utilized. Wet insulation was found. This will the drywall to remain wet and mold issues to occur. Have a licensed contractor repair or replace as needed.


7.0 Item 1(Picture) Wet Insulation

8.  Interiors
8.0  Ceilings  
Inspected, Repair or Replace

Upon conversation with selling agent ceiling and roof have been repairs made. Moisture meter and infrared camera were utilized and indicate throughout the home there are still signs of roof leaks. Have a licensed contractor repair or replace as needed.


8.0 Item 1(Picture) Infrared Camera Utilized
8.0 Item 2(Picture) Moisture Meter
8.0 Item 3(Picture) Infrared Camera Indicating Moisture on Ceiling
8.5  Doors (representative number)  
Inspected, Repair or Replace

This hallway closet door is not on track. Have a licensed door contractor repair or replace as needed.


8.5 Item 1(Picture) Hallway Closet
8.6  Windows (representative number)  
Inspected, Repair or Replace

Dining room picture window has a crack. Have a licensed window contractor repair or replace as needed.


8.6 Item 1(Picture) Dining Room

9.  Garage/Carport
9.4  Occupant Door (from garage/carport to inside of home)  
Inspected, Repair or Replace

The occupant door that leads from the garage should be on a self closing devise. Have a licensed door contractor repair or replace as needed.


9.4 Item 1(Picture) Occupant Door